1030
I
Summer / Winter heating limits
8... 30 °C
0,5 °C
18 °C
When the average of the outdoor temperatures over the past 24 hours reaches 18°C, the regulator switches off the
heating (as an economy measure).
During summer mode, the display shows "Eco".
This function is only active in automatic mode.
1032
S
24-hour heating limit
-10... 10 °C
1 °C
-3 °C
This function enables you partially to offset the automatic summer/winter switchover during the intermediate seasons.
Increasing the value delays the switchover to summer regime.
Decreasing the value advances the switchover to summer regime.
This function is only active in automatic mode.
1040
S
Flow temp setpoint min (for fan convectors)
8... 95 °C
1 °C
8 °C
1041
S
Flow temp setpoint max
8... 95 °C
1 °C
55 °C
Floor heating system = 50 °C / Higher temperature radiator = 65 °C
1050
S
Room influence
1 %... 100 %
1 %
20 %
If the installation is fitted with a room thermostat:
This function enables you to choose the ambient temperature's influence on the setting.
If no value is entered, the setting is made based on the temperature control.
If the parameter is set at 100%, the setting is only based on the ambient temperature.
1090
S
Optimum start control max
0... 360 min
10 min
120 min
1091
S
Optimum stop control max
0... 360 min
10 min
120 min
1100
S
Reduced setp increase start
-30... 10 °C, --°C
1 °C
--
1101
S
Reduced setp increase end
-30... 10 °C, --°C
1 °C
-5 °C
1130
S
Mixing valve boost
0... 50 °C
1 °C
0
1134
S
Actuator running time
30... 873 s
1 s
240 s
1150
I
Floor curing function (
figure 44
)
Off
-Off : Early interruption of the current programme, programme inactive
-Functional heating
-Heating ready for occupation
-Functional h curing heating
-Curing h Functional heating
-Manually
Manual mode enables you to programme your own concrete slab drying time.The function ends automatically after
25 days.
1151
I
Floor curing setp manually
(if line 1150 = manual)
0... 95 °C
1 °C
25 °C
This function enables you to set the custom concrete slab drying temperature. This temperature remains fixed. The
concrete slab-drying programme stops automatically after running for 25 days.
1156
I
Floor curing day current
0... 32
1157
I
Days complete.current
0... 32
1200
S
Operating mode changeover
None, Protection mode,
Reduced, Comfort, Automatic
Protection
mode
Operating mode at end of concrete slab drying period
Domestic Hot Water (Only with the DHW kit option)
1610
U
Nominal setpoint
Reduced setting (line 1612)… to
65 °C setpoint
1
50 °C
The backup electrical system is required to reach this level.
1612
U
Reduced setpoint
8 °C...
to Nominal setpoint (line 1610)
1
25 °C
Line
Function
Setting range
or display
Setting
increment
Basic
setting
Installation and operating manual "1364 - EN"
- 37 -
Heat pump split single service 3 phase