90 mm
(S)
505 mm
240 mm
150 mm
200 mm
305 mm
2 5 Installing the hydraulic unit
2 5 1 Installation precautions
• The room in which the appliance operates must comply
with the prevailing regulations.
• To facilitate maintenance and to allow access to
the various components, we recommend that you
provide sufficient space all around the hydraulic unit
(
figure 13
).
• Be careful not to bring inflammable gas near to the
heat pump during its installation, in particular when
it requires brazing. The appliances are not fireproof
and should not therefore be installed in a potentially
explosive atmosphere.
2 5 2 Positioning the hydraulic unit
-Remove the front panel (2 screws
A
,
figure 14
)
-Remove the sides (4 screws
B
,
figure 15
).
-Fix the support solidly (3 screws and plugs) to a flat,
hard-wearing wall (not a light partition) ensuring that it
is correctly levelled.
-Hook the appliance onto its support.
-Refit the sides.
-Refit the front panel.
200 mm
1000 mm
150 mm
150 mm
Figure 13 - Minimum installation clearances
around the hydraulic unit
and distances to the combustible partitions
Figure 14 - Removing the front panel
Figure 15 - Removing the sides and fixing the support
3
2
1
A
5
5
4
B
(S)
B
Installation and operating manual "1364 - EN"
- 15 -
Heat pump split single service 3 phase