Cooling circuit 1
901
U
Operating mode
Off, Automatic
Off
902
U
Comfort cooling setpoint
17... 40 °C
0,5 °C
24 °C
907
U
Release
24h/day, Time program HC,
Time program 5 / Refresh
Time
program 5
908
I
Flow temp setp at OT° 25°C
6... 35 °C
0,5 °C
20 °C
909
I
Flow temp setp at OT° 35°C
6... 35 °C
0,5 °C
16 °C
912
I
Cooling limit at OT°
--, 8... 35 °C
0,5 °C
24 °C
913
S
Lock time at end of heating
--, 8... 100
1 h
24 h
918
S
Summer comp start at OT°
20... 50 °C
1 °C
26 °C
919
S
Summer comp end at OT°
20... 50 °C
1 °C
40 °C
920
S
Summer comp setp increase
--, 1... 10 °C
1 °C
4 °C
923
S
Flow temp setp min OT° 25°C
6... 35 °C
0,5 °C
18 °C
924
S
Flow temp setp min OT° 35°C
6... 35 °C
0,5 °C
18 °C
928
S
Room influence
--, 1... 100 %
1 %
80 %
If the installation is fitted with an room sensor :
This function enables you to choose the ambient temperature's influence on the setting.
If no value is entered, the setting is made based on the temperature control.
If the parameter is set at 100%, the setting is only based on the ambient temperature.
932
S
Room temp limitation
--, 0,5... 4 °C
0,5 °C
0,5 °C
938
S
Mixing valve decrease
0... 20 °C
1 °C
0 °C
941
S
Actuator running time
30... 873 s
1 s
240 s
945
S
Mixing valve in heating mode
Control, Open
Control
946
S
Lock time dewpoint limiter
--, 10... 600 min
10 min
60 min
947
S
Flow temp setp incr hygro
--, 1... 20 °C
1 °C
10 °C
948
S
Flow setp incr start at r.h.
0... 100 %
1 %
60 %
950
S
Flow temp diff dewpoint
--, 0... 5 °C
1 °C
2 °C
963
S
With prim contr / system pump
No, Yes
No*
*Basic setting : 1 circuit = No ; 2 circuits = Yes
969
S
Operating mode changeover
No, Off, Automatic
Off
Heating, Circuit 2 (Only with the 2
nd
circuit kit option)
If the installation consists of 2 heating circuits
1010
U
Comfort heating setpoint
from reduced setpoint to 35°C
0,5 °C
20 °C
1012
U
Reduced setpoint
from frost protection setpoint…
to comfort setpoint
0,5 °C
18 °C
1014
U
Frost protection setpoint
from 4°C… to reduced setpoint
0,5 °C
8 °C
1016
S
Comfort setpoint max
20... 35 °C
1 °C
28 °C
1020
I
Heating curve slope (
figure 41)
0,1... 4
0,02
0,5
1021
I
Heating curve displacement
-4,5... 4,5 °C
0,5 °C
0
1026
S
Heating curve adaption (see
§ 3.3.2
)
Off, On
Off
Line
Function
Setting range
or display
Setting
increment
Basic
setting
Installation and operating manual "1364 - EN"
Heat pump split single service 3 phase
- 36 -