Time programme 5 / Cooling
If the installation is fitted with the cooling kit (Only with the cooling kit option).
600
U
Pre-selection (Day / Week)
Mon-Sun Mon-Fri Sat-Sun Monday Tuesday…
Mon-Sun
601
U
1
st
phase On (start)
00:00... --:--
10 min
8:00
602
U
1
st
phase Off (end)
00:00... --:--
10 min
20:00
603
U
2
nd
phase On (start)
00:00... --:--
10 min
--:--
604
U
2
nd
phase Off (end)
00:00... --:--
10 min
--:--
605
U
3
rd
phase On (start)
00:00... --:--
10 min
--:--
606
U
3
rd
phase Off (end)
00:00... --:--
10 min
--:--
616
U
Default values
No, Yes
No
Yes + OK : The Default values memorised in the regulator replace and cancel the customised heating programmes. Your
customised settings are therefore lost.
Holidays, heating circuit 1
641
U
Preselection
Period 1 to 8
Period 1
642
U
Start (Day / Month)
01.01... 31.12
1
643
U
End (Day / Month)
01.01... 31.12
1
648
U
Operating level (during the holidays)
Frost protection, Reduced
Frost
protection
Holidays, heating circuit 2
If the installation consists of 2 heating circuits (Only with the 2
nd
circuit kit option)
651
U
Preselection
Period 1 to 8
Period 1
652
U
Start (Day / Month)
01.01... 31.12
1
653
U
End (Day / Month)
01.01... 31.12
1
658
U
Operating level (during the holidays)
Frost protection, Reduced
Frost
protection
Heating, circuit 1
710
U
Comfort heating setpoint
from reduced setpoint to 35°C
0,5 °C
20 °C
712
U
Reduced setpoint
from frost protection setpoint…
to comfort setpoint
0,5 °C
18 °C
714
U
Frost protection setpoint
from 4°C…
to reduced setpoint
0,5 °C
8 °C
716
S
Comfort setpoint max
20 °C... 35 °C
1 °C
28 °C
720
I
Heating curve slope (See
figure 41
).
0,1... 4
0,02
0,5
721
I
Heating curve displacement
-4,5 °C... 4,5 °C
0,5 °C
0
726
I
Heating curve adaption (
see § 3.3.2
)
Off, On
Off
730
I
Summer / Winter heating limits
8 °C... 30 °C
0,5 °C
18 °C
When the average of the outdoor temperatures over the past 24 hours reaches 18°C, the regulator switches off the
heating (as an economy measure).
During summer mode, the display shows "Eco". This function is only active in automatic mode.
732
S
24-hour heating limit
-10 °C... 10 °C
1 °C
-3 °C
This function enables you partially to offset the automatic summer / winter switchover during the intermediate seasons.
Increasing the value delays the switchover to summer regime.
Decreasing the value advances the switchover to summer regime.
This function is only active in automatic mode.
740
S
Flow temp setpoint min (for fan convectors)
8... 95 °C
1 °C
8 °C
Line
Function
Setting range
or display
Setting
increment
Basic
setting
Installation and operating manual "1364 - EN"
Heat pump split single service 3 phase
- 34 -