01-02
When the air conditioner is set to the AUTO mode by remote control, operation starts in the optimum
mode from among the HEATING, COOLING and MONITORING modes. During operation, the
optimum mode is automatically swiched in accordance with temperature changes. The temperature
can be set between 18°C and 30°C in 1 degC steps.
When operation starts, only the indoor fan is operated for 1 minute. (Air flow mode: S- Lo)
After 1 minute, depends on the room temperature and outdoor unit's operarion mode,
the operation mode is selected in accordance with the table below.
( Table 1 : Operation mode selection table )
1
Room temperature :TR
Operation mode
TR > Ts +2 degC
Ts +2 degC > TR
=
=
Ts +2 degC > TR > Ts-2 degC
Cooling
Monitoring
Heating
Ts : Setting temperature
TR: Room temperature
When COOLING was selected at
, the same operation as COOLING OPERATION is performed.
When HEATING was selected at
, the same operation as HEATING OPERATION is performed.
When the compressor was stopped for 6 consecutive minutes by the temperature control function
after the COOLING or HEATING operation mode was selected at
above, operation is switched
to MONITORING and the operation mode is selected again.
1
2
3
1
4
1
2-2 For AR type
Содержание Inverter Halcyon ASU12RMLQ
Страница 3: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED DUCT CASSETTE type INVERTER MULTI ...
Страница 26: ...2 TROUBLE SHOOTING R410A WALL MOUNTED DUCT CASSETTE type INVERTER MULTI ...
Страница 76: ...3 REPLACEMENT PARTS R410A WALL MOUNTED DUCT CASSETTE type INVERTER MULTI ...
Страница 77: ...REPLACEMENT PARTS 03 01 Models ASU9RMLQ ASU12RMLQ ASU18RMLQ INVERTER ...
Страница 78: ...REPLACEMENT PARTS 03 02 Models ASU9RMLQ ASU12RMLQ ASU18RMLQ ...
Страница 79: ...Model ARU9RML 03 03 REPLACEMENT PARTS ...
Страница 80: ...Model ARU9RML 03 04 REPLACEMENT PARTS ...
Страница 81: ...Models ARU12RML ARU18RML 03 05 REPLACEMENT PARTS ...
Страница 82: ...Models ARU12RML ARU18RML 03 06 REPLACEMENT PARTS ...
Страница 83: ...Models ARU9RML ARU12RML ARU18RML 03 07 REPLACEMENT PARTS ...
Страница 84: ...40 Models AUU9RML AUU12RML AUU18RML REPLACEMENT PARTS ...
Страница 85: ...41 Models AUU9RML AUU12RML AUU18RML CONTROL UNIT REPLACEMENT PARTS ...
Страница 86: ...38 CASSETTE TYPE DECORATION PANEL UTG UFUB W REPLACEMENT PARTS ...
Страница 88: ...REPLACEMENT PARTS 03 08 Model AOU24RML AOU24RML1 ...
Страница 89: ...REPLACEMENT PARTS 03 09 Model AOU24RML AOU24RML1 ...
Страница 90: ...REPLACEMENT PARTS 03 10 Model AOU24RML AOU24RML1 ...
Страница 91: ...REPLACEMENT PARTS 03 11 Connector BLACK GREEN BLUE RED YELLOW WHITE Connector RED Model AOU24RML AOU24RML1 ...
Страница 92: ...REPLACEMENT PARTS 03 12 Model AOU36RML AOU36RML1 ...
Страница 93: ...REPLACEMENT PARTS 03 13 Model AOU36RML AOU36RML1 ...
Страница 94: ...REPLACEMENT PARTS 03 14 Model AOU36RML AOU36RML1 ...
Страница 95: ...REPLACEMENT PARTS 03 15 Connector BLACK GREEN BLUE RED YELLOW WHITE Connector RED Model AOU36RML AOU36RML1 ...
Страница 141: ...4 APPENDING DATA R410A WALL MOUNTED DUCT CASSETTE type INVERTER MULTI 1 PT CHART ...
Страница 145: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS06082006 JUN 2006 Printed in Japan ...