Trouble shooting 18
OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause:
Check Point 2 : Check ambient temp. around motor
OK
OK
Indicate or Display:
Refer to error code table.
Outdoor Unit Fan Motor Error
Outdoor Unit Main PCB Circuit
Outdoor Fan Motor
1. Fan rotation failure 2. Motor protection by surrounding temperature rise 3. Main PCB failure
Check Point 1 : Check rotation of Fan
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
Check excessively high temperature around the motor.
(If there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation.
Check Point 3 : Check Output Voltage of Main PCB
Check outdoor unit circuit diagram and the voltage.
(Measure at Main PCB side connector)
If the voltage is not correct, replace Main PCB.
When outdoor fan rotation speed is less than 100rpm in 20 seconds
after fan motor starts, fan motor stops.
After fan motor restarts, if the same operation within 60sec is repeated
3 times in a row, compressor and fan motor stops.
If and repeats 5 times in a row, compressor and fan motor stops
permanently.
CN802
1
2
3
4
5
6
RED
BLACK
WHITE
YELLOW
BLUE
FAN MOTOR
FM
Read wire DC voltage
Red - Black
White - Black
150 380V
15 1.5V
㨪
02-25
Содержание Inverter Halcyon ASU12RMLQ
Страница 3: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED DUCT CASSETTE type INVERTER MULTI ...
Страница 26: ...2 TROUBLE SHOOTING R410A WALL MOUNTED DUCT CASSETTE type INVERTER MULTI ...
Страница 76: ...3 REPLACEMENT PARTS R410A WALL MOUNTED DUCT CASSETTE type INVERTER MULTI ...
Страница 77: ...REPLACEMENT PARTS 03 01 Models ASU9RMLQ ASU12RMLQ ASU18RMLQ INVERTER ...
Страница 78: ...REPLACEMENT PARTS 03 02 Models ASU9RMLQ ASU12RMLQ ASU18RMLQ ...
Страница 79: ...Model ARU9RML 03 03 REPLACEMENT PARTS ...
Страница 80: ...Model ARU9RML 03 04 REPLACEMENT PARTS ...
Страница 81: ...Models ARU12RML ARU18RML 03 05 REPLACEMENT PARTS ...
Страница 82: ...Models ARU12RML ARU18RML 03 06 REPLACEMENT PARTS ...
Страница 83: ...Models ARU9RML ARU12RML ARU18RML 03 07 REPLACEMENT PARTS ...
Страница 84: ...40 Models AUU9RML AUU12RML AUU18RML REPLACEMENT PARTS ...
Страница 85: ...41 Models AUU9RML AUU12RML AUU18RML CONTROL UNIT REPLACEMENT PARTS ...
Страница 86: ...38 CASSETTE TYPE DECORATION PANEL UTG UFUB W REPLACEMENT PARTS ...
Страница 88: ...REPLACEMENT PARTS 03 08 Model AOU24RML AOU24RML1 ...
Страница 89: ...REPLACEMENT PARTS 03 09 Model AOU24RML AOU24RML1 ...
Страница 90: ...REPLACEMENT PARTS 03 10 Model AOU24RML AOU24RML1 ...
Страница 91: ...REPLACEMENT PARTS 03 11 Connector BLACK GREEN BLUE RED YELLOW WHITE Connector RED Model AOU24RML AOU24RML1 ...
Страница 92: ...REPLACEMENT PARTS 03 12 Model AOU36RML AOU36RML1 ...
Страница 93: ...REPLACEMENT PARTS 03 13 Model AOU36RML AOU36RML1 ...
Страница 94: ...REPLACEMENT PARTS 03 14 Model AOU36RML AOU36RML1 ...
Страница 95: ...REPLACEMENT PARTS 03 15 Connector BLACK GREEN BLUE RED YELLOW WHITE Connector RED Model AOU36RML AOU36RML1 ...
Страница 141: ...4 APPENDING DATA R410A WALL MOUNTED DUCT CASSETTE type INVERTER MULTI 1 PT CHART ...
Страница 145: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS06082006 JUN 2006 Printed in Japan ...