Trouble shooting 33
INDOOR UNIT
OUTDOOR UNIT Error Method:
Indicate or Display:
Refer to error code table.
Detective Actuators:
Detective details:
Forecast of Cause :
Compressor temperature error
Outdoor Unit Main PCB Circuit
Compressor Temperature Thermistor
02-38
When the compressor temperature becomes higher than 125°C,
the compressor stops.
Check Point 1 :
Check if Gas Valve is open
If it is not open, open it and check the operation.
Check Point 3 : Check if gas leak or less gas
Measure Gas pressure, if there is a leak, correct it.
>>If recharging refrigerant, make sure to perform
vacuuming and
recharge the specified amount.
Check Point 5 : Check Outdoor FAN, Heat Exchanger
Is there anything obstructing the air distribution circuit?
Is there any clogging of Outdoor Heat Exchanger?
Is the Fan rotating? (Check by hand and if it is locked, replace the motor)
Check Outdoor Fan Motor.
>>If the Fan Motor is defective, replace it.
Check Point 4 : Check Compressor Thermistor
Isn’t it fallen off the holder?
Is there a cable pinched?
>> Check characteristics of thermistor (Refer to Trouble shooting 12),
If defective, replace the thermistor
Check Point 2 : Check EEV and Strainer
Are EEV and Strainer open?
(Refer to PARTS INFORMATION 4)
>>If EEV or Strainer is defective, replace it.
OK
OK
OK
OK
OK
OK
MPa MPa
1. Valve is close 2. EEV failure 3. Gas Leak, less 4. Compressor Thermistor failure
5. Outdoor Fan Operation failure 6. Outdoor Heat Exchanger clogged
< Cooling mode >
< Heating mode >
Check Point 1 :
Check if LIquid Valve is open
If it is not open, open it and check the operation.
Check Point 2 : Check EEV and Strainer
Are EEV and Strainer open?
(Refer to PARTS INFORMATION 4)
>>If EEV or Strainer is defective, replace it.
Содержание Inverter Halcyon ASU12RMLQ
Страница 3: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED DUCT CASSETTE type INVERTER MULTI ...
Страница 26: ...2 TROUBLE SHOOTING R410A WALL MOUNTED DUCT CASSETTE type INVERTER MULTI ...
Страница 76: ...3 REPLACEMENT PARTS R410A WALL MOUNTED DUCT CASSETTE type INVERTER MULTI ...
Страница 77: ...REPLACEMENT PARTS 03 01 Models ASU9RMLQ ASU12RMLQ ASU18RMLQ INVERTER ...
Страница 78: ...REPLACEMENT PARTS 03 02 Models ASU9RMLQ ASU12RMLQ ASU18RMLQ ...
Страница 79: ...Model ARU9RML 03 03 REPLACEMENT PARTS ...
Страница 80: ...Model ARU9RML 03 04 REPLACEMENT PARTS ...
Страница 81: ...Models ARU12RML ARU18RML 03 05 REPLACEMENT PARTS ...
Страница 82: ...Models ARU12RML ARU18RML 03 06 REPLACEMENT PARTS ...
Страница 83: ...Models ARU9RML ARU12RML ARU18RML 03 07 REPLACEMENT PARTS ...
Страница 84: ...40 Models AUU9RML AUU12RML AUU18RML REPLACEMENT PARTS ...
Страница 85: ...41 Models AUU9RML AUU12RML AUU18RML CONTROL UNIT REPLACEMENT PARTS ...
Страница 86: ...38 CASSETTE TYPE DECORATION PANEL UTG UFUB W REPLACEMENT PARTS ...
Страница 88: ...REPLACEMENT PARTS 03 08 Model AOU24RML AOU24RML1 ...
Страница 89: ...REPLACEMENT PARTS 03 09 Model AOU24RML AOU24RML1 ...
Страница 90: ...REPLACEMENT PARTS 03 10 Model AOU24RML AOU24RML1 ...
Страница 91: ...REPLACEMENT PARTS 03 11 Connector BLACK GREEN BLUE RED YELLOW WHITE Connector RED Model AOU24RML AOU24RML1 ...
Страница 92: ...REPLACEMENT PARTS 03 12 Model AOU36RML AOU36RML1 ...
Страница 93: ...REPLACEMENT PARTS 03 13 Model AOU36RML AOU36RML1 ...
Страница 94: ...REPLACEMENT PARTS 03 14 Model AOU36RML AOU36RML1 ...
Страница 95: ...REPLACEMENT PARTS 03 15 Connector BLACK GREEN BLUE RED YELLOW WHITE Connector RED Model AOU36RML AOU36RML1 ...
Страница 141: ...4 APPENDING DATA R410A WALL MOUNTED DUCT CASSETTE type INVERTER MULTI 1 PT CHART ...
Страница 145: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS06082006 JUN 2006 Printed in Japan ...