Self - diagnosis function and Checking points
Error Indication
Operation
(RED)
Timer
(GREEN)
Wired remote
controller
Error
(Protection)
Diagnosis Method
0.5 sec
2 times
The detection value of the outdoor heat exchanger thermistor is either open or shorted.
> Compressor, outdoor fan : OFF (It automatically releases when the normal value is detected.)
The detection value of the outdoor temperature thermistor is either open or shorted.
> Compressor, outdoor fan : OFF (It automatically releases when the normal value is detected.)
0.5 sec
3 times
00
07
-0
4
Forced auto switch error
Outdoor temperature ther-
mistor error
Outdoor heat exchanger
thermistor error
Discharge thermistor error
The detection value of the discharge thermistor is either open or shorted.
> Compressor, outdoor fan : OFF (It automatically releases when the normal value is detected.)
[Diagnosis Point]
Check thermistor resistance value (Refer to "Thermistor characteristics table").
Controller PCB defective.
[Diagnosis Point]
Check thermistor resistance value (Refer to "Thermistor characteristics table").
Controller PCB defective.
[Diagnosis Point]
Check thermistor resistance value (Refer to "Thermistor characteristics table").
Controller PCB defective.
Forced auto switch becomes ON for 30 consecutive seconds.
> It indicates the error but the operation continues.
[Diagnosis Point]
Check if forced auto switch is kept pressed.
Forced auto switch defective.
Controller PCB defective.
06
0A
No Display
No Display
No Display
After 2 minutes 20 seconds of stopping operation, the signal from outdoor unit is received even though the main relay is OFF.
> Main relay OFF continues (outdoor unit OFF command)
[Diagnosis Point]
Main relay defective
Controller PCB defective.
The power supply frequency can not be recognized after 4 seconds of power ON.
> Permanent stop.
[Diagnosis Point]
Controller PCB defective.
Main relay error
Power supply frequency
detection error
0.5 sec
3 times
0.5 sec
4 times
0.5 sec
2 times
0.5 sec
3 times
0.5 sec
4 times
0.5 sec
4 times
Содержание Halcyon AOU12RLQ
Страница 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Страница 7: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Страница 10: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 13: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 16: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 35: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Страница 67: ...9 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Страница 68: ...REPLACEMENT PARTS 09 01 Models ASU9RLQ ASU12RLQ ...
Страница 69: ...REPLACEMENT PARTS 09 02 Models ASU9RLQ ASU12RLQ ...
Страница 70: ...REPLACEMENT PARTS 09 03 Models AOU9RLQ AOU12RLQ ...
Страница 71: ...REPLACEMENT PARTS 09 04 Models ASU18CL ASU18RL ...
Страница 72: ...REPLACEMENT PARTS 09 05 Models ASU18CL ASU18RL ...
Страница 73: ...REPLACEMENT PARTS 09 06 Models ASU18CL ASU18RL ...
Страница 78: ...10 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Страница 81: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS01012006 JAN 2006 Printed in Japan ...