3. PRECAUTION FOR SERVICING
Feature 1 Refrigerant oil is different from before.
Refrigerant oil for
New Refrigerant
Synthetic oil
Ether
Esther
Different point from
previous one
Previously it was
mineral oil.
Absorbent character
is high.
Contamination occurs
when mixed withe other
kind of oil.
Use the gauge manifold and charge hose
for New Refrigerant(HFC), which shall
be segregated from those of R22.
Attach the stop valve on the vacuum pump
and avoid the oil from reverse frow.
It is necessary to use the vacuum pump
which can obtain the high vacuum condition.
Precaution on Tools
Feature 2 New Refrigerant has Approx 1.6 times higher pressure than previous refrigerant.
R410A
High Pressure
Different point from
previous one
Diameter of Service port
has been changed from
1/4 Flare to 5/16 Flare.
It requires the gauge manifold and charge
hose exclusively for R410A.
It requires the flare tool and torque wrench
that satisfies New JIS standard.
Precaution on Tools
R410A
R22
1.6 times of R22.
JIS standard of flare
process It became lager
To keep thethickness of
copper tube.
(1/4,3/3=more than 0.8mm)
Previous flare tool + flare adapter can be used as well.
06-04
Содержание Halcyon AOU12RLQ
Страница 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Страница 7: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Страница 10: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 13: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 16: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 35: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Страница 67: ...9 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Страница 68: ...REPLACEMENT PARTS 09 01 Models ASU9RLQ ASU12RLQ ...
Страница 69: ...REPLACEMENT PARTS 09 02 Models ASU9RLQ ASU12RLQ ...
Страница 70: ...REPLACEMENT PARTS 09 03 Models AOU9RLQ AOU12RLQ ...
Страница 71: ...REPLACEMENT PARTS 09 04 Models ASU18CL ASU18RL ...
Страница 72: ...REPLACEMENT PARTS 09 05 Models ASU18CL ASU18RL ...
Страница 73: ...REPLACEMENT PARTS 09 06 Models ASU18CL ASU18RL ...
Страница 78: ...10 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Страница 81: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS01012006 JAN 2006 Printed in Japan ...