4. AUTO CHANGEOVER OPERATION
When the air conditioner is set to the AUTO mode by remote cintrol, operation starts in the optimum
mode from amoung the HEATING, COOLING, DRY and MONITORING modes. During operation, the
optimum mode is automatically swiched in accordance with temperature changes. The temperature
can be set between 64°F(18°C) and 88°F(30°C) in 2°F(1°C) steps.
.When operation starts, only the indoor and outdoor fans are operated for 1 minute. After 1 minute,
the room temperature and outside air temperature are sensed and the operation mode is
selected in accordance with the table below.
C zone
90°F(32°C)
B zone
14°F(-10°C)
A zone
( Table.4 Operation mode selection table)
Outside air temperature (TO)
Room temperature(TB)
A zone
B zone
C zone
TB > TS+4°F(2°C)
Monitoring
Cooling
(automatic dry)
Cooling
(automatic dry)
TS+4°F(2°C) TB TS - 4°F(2°C)
Monitoring
Monitoring
Monitoring
TB TS- 4°F(2°C)
*Heating
*Heating
*18CL is Monitoring
Monitoring
.When COOING was selected at
, the air conditioner operates as follow:
The same operation as COOLING OPERATION of item 1 above is performed.
When the room temperature has remained at (set tempareure -2°F(1°C)) for 8 minutes, operation is
automatically switched to DRY and the same operation as DRY OPERATION of item 3 above
is performed.
If the room temperature reaches (set temp4°F(2°C) during DRY operation, operation returns to
COOLING operation.
.When HEATING was selected at , the same operation as HEATING OPERATION of item 2
above is performed.
When the compressor was stopped for 6 consecutive minutes by the temperature control function
after the COOLING or HEATING operation mode was selected at above, operation is switched
to MONITORING and the operation mode is selected again.
1
<
1
2
3
1
4
1
( Fig.5 : Outside air temperature zone selection )
05-04
Содержание Halcyon AOU12RLQ
Страница 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Страница 7: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Страница 10: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 13: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 16: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 35: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Страница 67: ...9 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Страница 68: ...REPLACEMENT PARTS 09 01 Models ASU9RLQ ASU12RLQ ...
Страница 69: ...REPLACEMENT PARTS 09 02 Models ASU9RLQ ASU12RLQ ...
Страница 70: ...REPLACEMENT PARTS 09 03 Models AOU9RLQ AOU12RLQ ...
Страница 71: ...REPLACEMENT PARTS 09 04 Models ASU18CL ASU18RL ...
Страница 72: ...REPLACEMENT PARTS 09 05 Models ASU18CL ASU18RL ...
Страница 73: ...REPLACEMENT PARTS 09 06 Models ASU18CL ASU18RL ...
Страница 78: ...10 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Страница 81: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS01012006 JAN 2006 Printed in Japan ...