20. OFF DEFROST OPEARTION CONTROL
(1). OFF DEFROST OPERATION CONDITION
When operation stops in the [Heating operation] mode, if frost is adhered to the outdoor unit heat
exchanger, the defrost operation will proceed automatically. In this time, if indoor unit operation
lamp flashes slowly (7 sec ON / 2 sec OFF), the outdoor unit will allow the heat exchanger to defrost,
and then stop.
In heating operation, the outdoor heat exchanger temperature is less than - 25°F(-4°C), and
compressor operation integrating time lasts for more than 30 minutes.
ASU9RLQ
ASU12RLQ
ASU18RL
OFF Defrost Flow Chart
Heating operation stop
Outdoor heat exchanger temperature:
Below - 25°F(-4°C)
and
Compressor integrating operation:
Over 30 minutes
Defrost start
Defrost Indicater:
[Operation lamp]
Outdoor heat exchanger temperature:
Over 50°F(10°C) / 61°F(16°C)
or
Compressor ON time:
Over 15 minutes
Defrost end
(2). OFF DEFROST END CONDITION
Release Condition
Outdoor heat exchanger temperature sensor value is higher than 61°F(16°C) or
Compressor operation time has passed 15 minutes.
Outdoor heat exchanger temperature sensor value is higher than 61°F(16°C) or
Compressor operation time has passed 15 minutes.
Outdoor heat exchanger temperature sensor value is higher than 50°F(10°C) or
Compressor operation time has passed 15 minutes.
7 sec ON / 2 sec OFF
05-16
Содержание Halcyon AOU12RLQ
Страница 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Страница 7: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Страница 10: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 13: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 16: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 35: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Страница 67: ...9 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Страница 68: ...REPLACEMENT PARTS 09 01 Models ASU9RLQ ASU12RLQ ...
Страница 69: ...REPLACEMENT PARTS 09 02 Models ASU9RLQ ASU12RLQ ...
Страница 70: ...REPLACEMENT PARTS 09 03 Models AOU9RLQ AOU12RLQ ...
Страница 71: ...REPLACEMENT PARTS 09 04 Models ASU18CL ASU18RL ...
Страница 72: ...REPLACEMENT PARTS 09 05 Models ASU18CL ASU18RL ...
Страница 73: ...REPLACEMENT PARTS 09 06 Models ASU18CL ASU18RL ...
Страница 78: ...10 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Страница 81: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS01012006 JAN 2006 Printed in Japan ...