3. DRY OPERATION
3-1 INDOOR UNIT CONTROL
The compressor rotation frequency shall change according to the temperature, set temperature,
and room temperature variation which the room temperature sensor of the indoor unit body has
detected as shown in the Table 3. However, after the compressor is driven, the indoor unit shall
run at operation frequency of 58Hz, for a minute.
Operating
frequency
ASU9RLQ
33Hz
ASU12RLQ
33Hz
ASU18CL
24Hz
room room
temperature
temperature
compressor ON
Ts+3°F(1.5°C)
Ts+1°F(0.5°C)
compressor OFF
Compressor
ON
OFF
Indoor fan
Dry air flow
S
-
Lo
OFF
( Table 3 : Compressor frequency )
( Fig.3 : Compressor Control based on Room Temperature )
( Fig.4 : Indoor Fan Control )
05-03
When an IAQ works in 9/12LA models, it operate with S-LO without stopping.
10
30
60
180
60
180
60 10
30
(SEC)
ASU18RL
24Hz
Содержание Halcyon AOU12RLQ
Страница 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Страница 7: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Страница 10: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 13: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 16: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 35: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Страница 67: ...9 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Страница 68: ...REPLACEMENT PARTS 09 01 Models ASU9RLQ ASU12RLQ ...
Страница 69: ...REPLACEMENT PARTS 09 02 Models ASU9RLQ ASU12RLQ ...
Страница 70: ...REPLACEMENT PARTS 09 03 Models AOU9RLQ AOU12RLQ ...
Страница 71: ...REPLACEMENT PARTS 09 04 Models ASU18CL ASU18RL ...
Страница 72: ...REPLACEMENT PARTS 09 05 Models ASU18CL ASU18RL ...
Страница 73: ...REPLACEMENT PARTS 09 06 Models ASU18CL ASU18RL ...
Страница 78: ...10 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Страница 81: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS01012006 JAN 2006 Printed in Japan ...