( Fig. 1 : Limit of Maximum Frequency based on Outdoor Temperature )
1. COOLING OPERATION
1-1 COOLING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is 4°F(2°C) higher than a set temperature, the compressor operation
frequency will attain to maximum performance.
* If the room temperature is 5°F(2.5°C) lower than a set temperature, the compressor will be
stopped.
* When the room temperature is b4°F(+2°C) to -5°F(-2.5°C) of the setting temperature,
the compressor frequency is controlled within the range shown in Table1.
However, the maximum frequency is limited in the range shown in Figure 1 based on the
fan speed mode and the outdoor temperature.
minimum
frequency
maximum
frequency
maximum
frequency
ASU9RLQ
18Hz
61Hz
80Hz
ASU12RLQ
18Hz
80Hz
96Hz
ASU18CL
18Hz
70Hz
90Hz
Outside air Outside air
temperature temperature
97°F(36°C)
A zone
93°F(34°C)
90°F(32°C)
B zone
86°F(30°C)
70°F(21°C)
C zone
66°F(19°C)
D zone
Hi
Me
Lo
Quiet
A zone
80Hz
61Hz
51Hz
33Hz
B zone
80Hz
61Hz
51Hz
33Hz
C zone
80Hz
61Hz
51Hz
33Hz
9RLQ
D zone
51Hz
42Hz
36Hz
27Hz
E zone
51Hz
42Hz
36Hz
27Hz
F zone
51Hz
42Hz
36Hz
27Hz
A zone
96Hz
61Hz
51Hz
33Hz
12RLQ
B zone
96Hz
61Hz
51Hz
33Hz
C zone
96Hz
61Hz
51Hz
33Hz
D zone
57Hz
42Hz
36Hz
27Hz
E zone
57Hz
42Hz
36Hz
27Hz
18CL
F zone
57Hz
42Hz
36Hz
27Hz
A zone
B zone
C zone
D zone
E zone
F zone
( Table 1 : Compressor Frequency Range )
When the compressor operates for 30 minutes continuously at over the maximum frequency ,
the maximum frequency is changed from Maximum Frequency to Maximum Frequency .
The room temperature is controlled 2°F(1°C) lower than the setting temperature for 40 minutes
after starting the operation.
After 40 minutes, it is controlled based on the normal setting temperature.
05-01
E zone
F zone
50°F(10°C)
32°F(0°C)
54°F(12°C)
36°F(2°C)
90Hz
45Hz
42Hz
30Hz
90Hz
45Hz
42Hz
30Hz
90Hz
45Hz
42Hz
30Hz
58Hz
38Hz
34Hz
24Hz
58Hz
38Hz
34Hz
24Hz
58Hz
38Hz
34Hz
24Hz
ASU18RL
18Hz
70Hz
90Hz
18RL
A zone
B zone
C zone
D zone
E zone
F zone
90Hz
45Hz
42Hz
30Hz
90Hz
45Hz
42Hz
30Hz
90Hz
45Hz
42Hz
30Hz
58Hz
38Hz
34Hz
24Hz
58Hz
38Hz
34Hz
24Hz
58Hz
38Hz
34Hz
24Hz
Содержание Halcyon AOU12RLQ
Страница 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Страница 7: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Страница 10: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 13: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 16: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 35: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Страница 67: ...9 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Страница 68: ...REPLACEMENT PARTS 09 01 Models ASU9RLQ ASU12RLQ ...
Страница 69: ...REPLACEMENT PARTS 09 02 Models ASU9RLQ ASU12RLQ ...
Страница 70: ...REPLACEMENT PARTS 09 03 Models AOU9RLQ AOU12RLQ ...
Страница 71: ...REPLACEMENT PARTS 09 04 Models ASU18CL ASU18RL ...
Страница 72: ...REPLACEMENT PARTS 09 05 Models ASU18CL ASU18RL ...
Страница 73: ...REPLACEMENT PARTS 09 06 Models ASU18CL ASU18RL ...
Страница 78: ...10 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Страница 81: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS01012006 JAN 2006 Printed in Japan ...