background image

En-15

b. Automatic air

fl

 ow adjustment

 CAUTION

• This function cannot be used when there is a booster fan between the ducts.
• Be sure that the static pressure is within the allowed range. Incorrect setting may 

cause incorrect adjustment and may result in insuf

fi

 cient air

fl

 ow or water leakage.

• When the external static pressure is changeable in the installation by use of 

automatic changeable dampers, etc., set so that the external static pressure is the 
lowest.

NOTE:

Be sure to conduct this setting before any other operation. If the motor is warm or the heat 
exchanger is wet, false detection may lead to incorrect adjustments.
Check if the electrical wirings and duct installations are complete.
If there is a damper installed in the system, make sure the damper is open.
Check if the air 

fi

 lter (optional) is attached.

If there are several inlet, outlet ports, make sure the air

fl

 ow rates of each port match the 

designed air

fl

 ow rate by adjusting the throttles.

Automatic air

fl

 ow adjustment is possible by the following procedures.

1)   Change the setting of Function 26 to "Automatic air

fl

 ow adjustment" (32).

2)  Run the air conditioner on Fan mode (High). 

*  For instructions on how to operate the air conditioner, refer to the operation manual 

of the remote controller.

 During 

Automatic 

air

fl

 ow adjustment, the mode will be 

fi

 xed at Fan mode (High).

  When this function is active, do not operate the Outdoor unit.

3)  The air conditioner will run for about 1 to 8 min. then stop automatically. 

*  Do not change the throttles of the inlet and outlet ports during operation.
  When used in a Group control system, the setting will take about 10 min.

4)  Turn the air conditioner off and on again.
5)  Check the setting value of Function 26 and record the obtained setting value in the 

following table.

 

* If the setting value has not changed, repeat the procedure from step 1. 
 

 

Function Number

Setting value

26

 CAUTION

• If the detected setting value is not within the range of static pressure, please check 

and re-arrange the installation, then repeat the procedure from step 1. Incorrect 
setting may result in insuf

fi

 cient air

fl

 ow or water leakage.

• When the duct or outlet installations are changed after the Automatic air

fl

 ow 

adjustment is completed, repeat the procedure from step 1.

7. CHECK LIST

Pay special attention to the check items below when installing the indoor unit(s). After 
installation is complete, be sure to check the following check items again.

Check items

Check box

Has the indoor unit been installed correctly?
Has there been a check for gas leaks (refrigerant pipes)?
Has heat insulation work been completed?
Does water drain easily from the indoor units?
Is the voltage of the power source the same as that indicated on the label 
on the indoor unit?
Are the wires and pipes all connected completely?
Is the indoor unit grounded?
Is the connection cable the speci

fi

 ed thickness?

Are the inlets and outlets free of any obstacles?
After installation is completed, has the proper operation and handling 
been explained to the user?
Operate the unit according to the operating manual provided, and check 
that it is operating normally.

8. TEST RUN

8. 1.  Check items

 Is operation of each button on the remote control unit normal?

 Does each lamp light normally?

 Is the drain normal?

 Do not have an abnormal noise and vibration during operation?

Do not operate the air conditioner in test run for a long time.

8. 2.  Operation method

Depending on your installation, choose from the following:

 

By the wireless remote controller (with [TEST RUN] button) 

•  To start test run, press the [START/STOP] button and the [TEST RUN] button on the 

remote controller. 

•  To end test run, press the remote controller [START/STOP] button. 

 

By the indoor unit or IR receiver unit 

•  To start test run, press the [MANUAL AUTO] button of the unit for more than 10 seconds 

(forced cooling).

•  To end test run, press the [MANUAL AUTO] button for more than 3 seconds or press 

the remote controller [START/STOP] button. 

•  The Operation indicator lamp and Timer indicator lamp will simultaneously 

fl

 ash during 

the test run mode. 

 

By the wired remote controller

•  For the operation method, refer to the installation manual and the operating manual of 

the wired remote controller. 

Heating test run will begin in a few minutes when HEAT is selected by the remote controller 
[reverse cycle model only].

9. FINISHING

Install the heat insulation material after performing a refrigerant leak check (see the 
installation manual for the outdoor unit for details).

Coupler heat insulation

No gaps

Indoor unit side

Cable ties (large)
(Accessory)

Pipes

(Gas and liquid pipes)

Coupler heat insulation 
(Accessory)

Be sure to overlap 
the insulation.

 CAUTION

There should be no gaps between the insulation and the product.

 CAUTION

• After connecting the piping, check the all joints for gas leakage with gas leak detector.
• Once the pressure checking has been completed using nitrogen, please refer to the 

outdoor unit installation manual to complete the evacuation process.

• Install heat insulation around both the large (gas) and small (liquid) pipes. Failure to 

do so may cause water leaks.

10. CUSTOMER GUIDANCE

Explain the following to the customer in accordance with the operating manual:
(1)  Starting and stopping method, operation switching, temperature adjustment, timer, air 

fl

 ow switching, and other remote controller operations.

(2)  Cleaning and maintenance of the product, and other items such as air 

fi

 lters and air 

louvers if applicable.

(3) Give the operating and installation manuals to the customer.
(4)  If the indoor unit custom code is changed, and the installation includes a wireless 

remote controller, inform the customer the changed code. (On some wireless remote 
controllers, the custom code may return to A when batteries are replaced.)

9381386215-01_IM.indb   15

9381386215-01_IM.indb   15

12/5/2018   2:57:37 PM

12/5/2018   2:57:37 PM

Содержание ARXG-KHTAP Series

Страница 1: ...lation must be performed in accordance with regulations codes or standards for electrical wiring and equipment in each country region or the installation place Do not use means to accelerate the defrosting process or to clean other than those recommended by the manufacturer This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or ...

Страница 2: ...ance with an industry recognised assessment specification Servicing shall only be performed as recommended by the equipment manufacturer Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants Servicing shall be performed only as recommended by the manufacturer 2 2 Work Prior ...

Страница 3: ...nce to electrical components shall include initial safety checks and component inspection procedures If a fault exists that could compromise safety then no electrical supply shall be con nected to the circuit until it is satisfactorily dealt with If the fault cannot be corrected immediately but it is necessary to continue operation an adequate temporary solution shall be used This shall be reporte...

Страница 4: ...ure 0 1 to 3 8 MPa 1 to 38 bar for low pressure Charge hose To increase pressure resistance the hose material and base size were changed R32 R410A Vacuum pump A conventional vacuum pump can be used by installing a vacuum pump adapter Use of a vacuum pump with a series motor is prohibited Gas leakage detector Special gas leakage detector for HFC refrigerant R410A or R32 Copper pipes It is necessary...

Страница 5: ...g such work with an insufficient number of people or with inadequate equip ment could result in dropping of the unit or personal injury CAUTION For installation details refer to the technical data 3 1 Selecting an installation location Decide the mounting position together with the customer as follows WARNING Install the indoor unit where is capable to support the weight of the unit Secure the uni...

Страница 6: ...ent could result in dropping of the unit or personal injury If the job is done with the panel frame only there is a risk that the unit will come loose Please take care When fastening the hangers make the bolt positions uniform CAUTION Confirm the directions of the air intake and outlet before installing the unit The unit takes in air from the evaporator side and expels it from the fan side 3 3 1 P...

Страница 7: ...pply Room Duct Field supply When connecting the duct perform duct insulation appropriate for the installing environment Inappropriate insulation work may cause condensation on the surface of the insulat ing material and may lead to condensation dripping 3 5 Drain installation CAUTION Install the drain hose in accordance with the instructions in this installation manual and keep the area warm enoug...

Страница 8: ...ing installation make sure that the refrigerant pipe is attached firmly before you run the compressor Do not operate the compressor under the condition of refrigerant piping not attached properly with 2 way or 3 way valve open This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury During the pump down operation make sure that the compressor is turned off...

Страница 9: ...are nut cannot be tightened smoothly If the flare nut is forced to turn the threads will be damaged Do not remove the flare nut from the indoor unit pipe until immediately before connecting the connection pipe Do not use mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units 1 Detach the caps and plugs from the pipes 2 Centering t...

Страница 10: ... ground cable to a gas pipe water pipe lightning rod or a telephone earth ground cable Improper earthing grounding may cause electric shocks Do not connect power supply cables to the transmission or remote control terminals as this will damage the product Never bundle the power supply cable and transmission cable together Bundling these cables together will cause miss operation When handling PCB s...

Страница 11: ...ternal in out PCB CN47 External out This air conditioner can be connected with the following optional kits For details on how to install optional parts refer to the installation manual included in each item Connector No Option type CN48 IR Receiver UTY LBT M CN8 Remote sensor UTY XSZX CN47 1 Connect wire UTY XWZXZG CN65 2 External input and output PCB UTY XCSX 1 For external output terminal settin...

Страница 12: ... is used The original connector should be insulated to ensure that it does not come into contact with other electrical circuitry Setting for room temperature correction When a remote sensor is connected set the function setting of indoor unit as indicated below Set Function Number 30 Room temperature control for cooling to 00 Set Function Number 31 Room temperature control for heating to 01 5 REMO...

Страница 13: ...on details Filter sign Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated amount of dust in the air of the room If the indication is not required select No indication 03 Factory setting Function Number Setting Value Setting Description 11 00 Standard 2500 hours 01 Long interval 4400 hours 02 Short interval 1250 hours 03 No indication Room temp...

Страница 14: ... outdoor unit is stopped the indoor unit fan operates intermittently at a very low speed 02 Enable or disable this function by remote controller setting When using a wired remote controller without Indoor unit fan control for energy saving for cooling function or when connecting a single split converter the setting cannot be made by using the remote controller Set to 00 or 01 To confirm if the rem...

Страница 15: ...unded Is the connection cable the specified thickness Are the inlets and outlets free of any obstacles After installation is completed has the proper operation and handling been explained to the user Operate the unit according to the operating manual provided and check that it is operating normally 8 TEST RUN 8 1 Check items Is operation of each button on the remote control unit normal Does each l...

Страница 16: ...ed remote controller error 4 1 Room temp sensor error 4 2 Indoor unit heat ex middle temp sensor error 4 4 Human sensor error 5 1 Indoor unit fan motor error 5 3 Drain pump error 5 7 Damper error 5 15 Indoor unit error 6 1 Outdoor unit reverse missing phase and wiring error Error display Wired remote controller Error code Description OPERATION lamp green TIMER lamp orange ECONOMY lamp green 6 2 Ou...

Отзывы: