 CAUTION

12-Recovery

•  When removing refrigerant from a system, either for servicing or decommissioning, it 

is recommended good practice that all refrigerants are removed safely.

•  When transferring refrigerant into cylinders, ensure that only appropriate refrigerant 

recovery cylinders are employed.

•  Ensure that the correct number of cylinders for holding the total system charge are 

available. 

•  All cylinders to be used are designated for the recovered refrigerant and labelled for 

that refrigerant (i.e. special cylinders for the recovery of refrigerant). 

•  Cylinders shall be complete with pressure relief valve and associated shut-off valves 

in good working order.

•  Empty recovery cylinders are evacuated and, if possible, cooled before recovery 

occurs.

•  The recovery equipment shall be in good working order with a set of instructions 

concerning the equipment that is at hand and shall be suitable for the recovery of 

fl

 ammable refrigerants.

•  In addition, a set of calibrated weighing scales shall be available and in good working 

order.

•  Hoses shall be complete with leak-free disconnect couplings and in good condition.
•  Before using the recovery machine, check that it is in satisfactory working order, has 

been properly maintained and that any associated electrical components are sealed 
to prevent ignition in the event of a refrigerant release. 
Consult manufacturer if in doubt.

•  The recovered refrigerant shall be returned to the refrigerant supplier in the correct 

recovery cylinder, and the relevant Waste Transfer Note arranged. 

•  Do not mix refrigerants in recovery units and especially not in cylinders.
•  If compressors or compressor oils are to be removed, ensure that they have been 

evacuated to an acceptable level to make certain that 

fl

 ammable refrigerant does not 

remain within the lubricant. 

•  The evacuation process shall be carried out prior to returning the compressor to the 

suppliers. 

•  Only electric heating to the compressor body shall be employed to accelerate this 

process. 

•  When oil is drained from a system, it shall be carried out safely.

Explanation of symbols displayed on the indoor unit or outdoor unit.

WARNING

This symbol shows that this appliance uses a 

fl

 ammable 

refrigerant. 
If the refrigerant is leaked and exposed to an external igni-
tion source, there is a risk of 

fi

 re.

CAUTION

This symbol shows that the operation manual should be 
read carefully.

CAUTION

This symbol shows that a service personnel should be 
handling this equipment with reference to the installation 
manual.

CAUTION

This symbol shows that information is available such as 
the operating manual or installation manual.

2. PRODUCT SPECIFICATION

2. 1.   Installation tools

Tool name

Change from R22 to R32 (R410A)

Gauge manifold

Pressure is high and cannot be measured with a R22 
gauge. To prevent erroneous mixing of other refrigerants, 
the diameter of each port has been changed.
It is recommended to use gauge with seals -0.1 to 5.3 MPa 
(-1 to 53 bar) for high pressure.
-0.1 to 3.8 MPa (-1 to 38 bar) for low pressure.

Charge hose

To increase pressure resistance, the hose material and 
base size were changed. (R32/R410A)

Vacuum pump

A conventional vacuum pump can be used by installing a 
vacuum pump adapter.
(Use of a vacuum pump with a series motor is prohibited.)

Gas leakage detector

Special gas leakage detector for HFC refrigerant R410A or 
R32.

Copper pipes

It is necessary to use seamless copper pipes and it is desirable that the amount of residual 
oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or 
discolored portion (especially on the interior surface). Otherwise, the expansion value or 
capillary tube may become blocked with contaminants.
As an air conditioner using R32 (R410A) incurs pressure higher than when using R22, it is 
necessary to choose adequate materials. 

 WARNING

•  Do not use the existing (for R22) piping and 

fl

 are nuts.

If the existing materials are used, the pressure inside the refrigerant cycle will rise and 
cause failure, injury, etc. (Use the special R32/R410A materials.)

•  Use (re

fi

 ll or replace with) speci

fi

 ed refrigerant (R32) only. Use of unspeci

fi

 ed refriger-

ant can cause product malfunction, burst, or injury.

•  Do not mix any gas or impurities except speci

fi

 ed refrigerant (R32). In

fl

 ow of air or ap-

plication of unspeci

fi

 ed material makes the internal pressure of the refrigerant cycle too 

high, and may cause product malfunction, burst of piping, or injury.

•  For installation purposes, be sure to use the parts supplied by the manufacturer or 

other prescribed parts. The use of non-prescribed parts can cause serious accidents 
such as the unit falling, water leakage, electric shock, or 

fi

 re.

•  Do not turn on the power until all work has been completed.

 CAUTION

This manual describes how to install the indoor unit only. To install the outdoor unit or 
branch box, (if any), refer to the installation manual included in each product.

2. 2.   Accessories

 WARNING

For installation purposes, be sure to use the parts supplied by the manufacturer or other 
prescribed parts. 
The use of non-prescribed parts can cause serious accidents such as the unit falling, 
water leakage, electric shock, or 

fi

 re.

• The following installation parts are furnished. Use them as required.
• Keep the Installation Manual in a safe place and do not discard any other accessories 

until the installation work has been completed.

Name and Shape

Q’ty

Description

Operating Manual

1

Operating Manual 
(CD-ROM)

1

Installation Manual
(indoor unit)

1

(This  book)

Special nut A
(large 

fl

 ange) 

4

For suspending the indoor unit 
from ceiling

Special nut B
(small 

fl

 ange) 

 

 

4

Washer

8

Coupler heat insulation (large)

1

For indoor side pipe joint 
(gas pipe)

Coupler heat insulation (small)

1

For indoor side pipe joint 
(liquid pipe)

Cable tie (large)

4

For 

fi

 xing the heat insulation

Cable tie (medium)

1

For 

fi

 xing the remote controller 

cable

Cable tie (small)

1

For 

fi

 xing the remote controller 

cable

Drain hose insulation 

1

Insulates the drain hose and 
vinyl hose

Drain hose

1

For installing drain pipe
VP25 (O.D.32, I.D.25)

Hose Band

1

For installing drain hose

9381386215-01_IM.indb   4

9381386215-01_IM.indb   4

12/5/2018   2:57:35 PM

12/5/2018   2:57:35 PM

Содержание ARXG-KHTAP Series

Страница 1: ...lation must be performed in accordance with regulations codes or standards for electrical wiring and equipment in each country region or the installation place Do not use means to accelerate the defrosting process or to clean other than those recommended by the manufacturer This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or ...

Страница 2: ...ance with an industry recognised assessment specification Servicing shall only be performed as recommended by the equipment manufacturer Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants Servicing shall be performed only as recommended by the manufacturer 2 2 Work Prior ...

Страница 3: ...nce to electrical components shall include initial safety checks and component inspection procedures If a fault exists that could compromise safety then no electrical supply shall be con nected to the circuit until it is satisfactorily dealt with If the fault cannot be corrected immediately but it is necessary to continue operation an adequate temporary solution shall be used This shall be reporte...

Страница 4: ...ure 0 1 to 3 8 MPa 1 to 38 bar for low pressure Charge hose To increase pressure resistance the hose material and base size were changed R32 R410A Vacuum pump A conventional vacuum pump can be used by installing a vacuum pump adapter Use of a vacuum pump with a series motor is prohibited Gas leakage detector Special gas leakage detector for HFC refrigerant R410A or R32 Copper pipes It is necessary...

Страница 5: ...g such work with an insufficient number of people or with inadequate equip ment could result in dropping of the unit or personal injury CAUTION For installation details refer to the technical data 3 1 Selecting an installation location Decide the mounting position together with the customer as follows WARNING Install the indoor unit where is capable to support the weight of the unit Secure the uni...

Страница 6: ...ent could result in dropping of the unit or personal injury If the job is done with the panel frame only there is a risk that the unit will come loose Please take care When fastening the hangers make the bolt positions uniform CAUTION Confirm the directions of the air intake and outlet before installing the unit The unit takes in air from the evaporator side and expels it from the fan side 3 3 1 P...

Страница 7: ...pply Room Duct Field supply When connecting the duct perform duct insulation appropriate for the installing environment Inappropriate insulation work may cause condensation on the surface of the insulat ing material and may lead to condensation dripping 3 5 Drain installation CAUTION Install the drain hose in accordance with the instructions in this installation manual and keep the area warm enoug...

Страница 8: ...ing installation make sure that the refrigerant pipe is attached firmly before you run the compressor Do not operate the compressor under the condition of refrigerant piping not attached properly with 2 way or 3 way valve open This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury During the pump down operation make sure that the compressor is turned off...

Страница 9: ...are nut cannot be tightened smoothly If the flare nut is forced to turn the threads will be damaged Do not remove the flare nut from the indoor unit pipe until immediately before connecting the connection pipe Do not use mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units 1 Detach the caps and plugs from the pipes 2 Centering t...

Страница 10: ... ground cable to a gas pipe water pipe lightning rod or a telephone earth ground cable Improper earthing grounding may cause electric shocks Do not connect power supply cables to the transmission or remote control terminals as this will damage the product Never bundle the power supply cable and transmission cable together Bundling these cables together will cause miss operation When handling PCB s...

Страница 11: ...ternal in out PCB CN47 External out This air conditioner can be connected with the following optional kits For details on how to install optional parts refer to the installation manual included in each item Connector No Option type CN48 IR Receiver UTY LBT M CN8 Remote sensor UTY XSZX CN47 1 Connect wire UTY XWZXZG CN65 2 External input and output PCB UTY XCSX 1 For external output terminal settin...

Страница 12: ... is used The original connector should be insulated to ensure that it does not come into contact with other electrical circuitry Setting for room temperature correction When a remote sensor is connected set the function setting of indoor unit as indicated below Set Function Number 30 Room temperature control for cooling to 00 Set Function Number 31 Room temperature control for heating to 01 5 REMO...

Страница 13: ...on details Filter sign Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated amount of dust in the air of the room If the indication is not required select No indication 03 Factory setting Function Number Setting Value Setting Description 11 00 Standard 2500 hours 01 Long interval 4400 hours 02 Short interval 1250 hours 03 No indication Room temp...

Страница 14: ... outdoor unit is stopped the indoor unit fan operates intermittently at a very low speed 02 Enable or disable this function by remote controller setting When using a wired remote controller without Indoor unit fan control for energy saving for cooling function or when connecting a single split converter the setting cannot be made by using the remote controller Set to 00 or 01 To confirm if the rem...

Страница 15: ...unded Is the connection cable the specified thickness Are the inlets and outlets free of any obstacles After installation is completed has the proper operation and handling been explained to the user Operate the unit according to the operating manual provided and check that it is operating normally 8 TEST RUN 8 1 Check items Is operation of each button on the remote control unit normal Does each l...

Страница 16: ...ed remote controller error 4 1 Room temp sensor error 4 2 Indoor unit heat ex middle temp sensor error 4 4 Human sensor error 5 1 Indoor unit fan motor error 5 3 Drain pump error 5 7 Damper error 5 15 Indoor unit error 6 1 Outdoor unit reverse missing phase and wiring error Error display Wired remote controller Error code Description OPERATION lamp green TIMER lamp orange ECONOMY lamp green 6 2 Ou...

Отзывы: