11. ERROR CODES

If you use a wired type remote controller, error codes will appear on the remote control-
ler display. If you use a wireless remote controller, the lamps on the IR receiver unit will 
output error codes by way of blinking patterns. See the lamp blinking patterns and error 
codes in the table below. An error display is displayed only during operation.
For more details, refer to the installation manual of the remote controller.

Error display

Wired 

remote 

controller 

Error code

Description

OPERATION 
lamp (green)

TIMER 

lamp 

(orange)

ECONOMY 

lamp 

(green)

(1)

(1)

Serial communication error

(1)

(2)

Wired remote controller 
communication error

(1)

(5)

Check run un

fi

 nished

Automatic air

fl

 ow adjustment error

(1)

(6)

Peripheral unit transmission PCB 
connection error

(1)

(8)

External communication error

(2)

(1)

Unit number or Refrigerant circuit 
address setting error 
[Simultaneous Multi]

(2)

(2)

Indoor unit capacity error

(2)

(3)

Combination error

(2)

(4)

• Connection unit number 

error (indoor secondary unit) 
[Simultaneous Multi]

• Connection unit number error 

(indoor unit or branch unit) 
[Flexible Multi]

(2)

(6)

Indoor unit address setting error

(2)

(7)

Primary unit, secondary unit setup 
error [Simultaneous Multi]

(2)

(9)

Connection unit number error in 
wired remote controller system

(3)

(1)

Power supply interruption error

(3)

(2)

Indoor unit PCB model 
information error

(3)

(3)

Indoor unit motor electricity 
consumption detection error

(3)

(5)

Manual auto switch error

(3)

(9)

Indoor unit power supply error for 
fan motor 

(3)

(10)

Indoor unit communication circuit 
(wired remote controller) error

(4)

(1)

Room temp. sensor error 

(4)

(2)

Indoor unit heat ex. middle temp. 
sensor error

(4)

(4)

Human sensor error

(5)

(1)

Indoor unit fan motor error

(5)

(3)

Drain pump error

(5)

(7)

Damper error 

(5)

(15)

Indoor unit error

(6)

(1)

Outdoor unit reverse/missing 
phase and wiring error

Error display

Wired 

remote 

controller 

Error code

Description

OPERATION 
lamp (green)

TIMER 

lamp 

(orange)

ECONOMY 

lamp 

(green)

(6)

(2)

Outdoor unit main PCB 
model information error or 
communication error

(6)

(3)

Inverter error 

(6)

(4)

Active 

fi

 lter error, PFC circuit error 

(6)

(5)

Trip terminal L error

(6)

(8)

Outdoor unit rush current limiting 
resister temp. rise error

(6)

(10)

Display PCB microcomputers 
communication error

(7)

(1)

Discharge temp. sensor error

(7)

(2)

Compressor temp. sensor error

(7)

(3)

Outdoor unit Heat Ex. liquid temp. 
sensor error

(7)

(4)

Outdoor temp. sensor error

(7)

(5)

Suction Gas temp. sensor error

(7)

(6)

• 2-way valve temp. sensor error
• 3-way valve temp. sensor error

(7)

(7)

Heat sink temp. sensor error

(8)

(2)

• Sub-cool Heat Ex. gas inlet 

temp. sensor error

• Sub-cool Heat Ex. gas outlet 

temp. sensor error

(8)

(3)

Liquid pipe temp. sensor error

(8)

(4)

Current sensor error

(8)

(6)

• Discharge pressure sensor error
• Suction pressure sensor error
• High pressure switch error

(9)

(4)

Trip detection

(9)

(5)

Compressor rotor position 
detection error (permanent stop) 

(9)

(7)

Outdoor unit fan motor 1 error

(9)

(8)

Outdoor unit fan motor 2 error

(9)

(9)

4-way valve error

(9)

(10)

Coil (expansion valve) error

(10)

(1)

Discharge temp. error

(10)

(3)

Compressor temp. error

(10)

(4)

High pressure error

(10)

(5)

Low pressure error

(13)

(2)

Branch boxes error 
[Flexible Multi]

Display mode 

 : 0.5s ON / 0.5s OFF

 

 : 0.1s ON / 0.1s OFF

 ( )  : Number of 

fl

 ashing

9381386215-01_IM.indb   16

9381386215-01_IM.indb   16

12/5/2018   2:57:37 PM

12/5/2018   2:57:37 PM

Содержание ARXG-KHTAP Series

Страница 1: ...lation must be performed in accordance with regulations codes or standards for electrical wiring and equipment in each country region or the installation place Do not use means to accelerate the defrosting process or to clean other than those recommended by the manufacturer This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or ...

Страница 2: ...ance with an industry recognised assessment specification Servicing shall only be performed as recommended by the equipment manufacturer Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants Servicing shall be performed only as recommended by the manufacturer 2 2 Work Prior ...

Страница 3: ...nce to electrical components shall include initial safety checks and component inspection procedures If a fault exists that could compromise safety then no electrical supply shall be con nected to the circuit until it is satisfactorily dealt with If the fault cannot be corrected immediately but it is necessary to continue operation an adequate temporary solution shall be used This shall be reporte...

Страница 4: ...ure 0 1 to 3 8 MPa 1 to 38 bar for low pressure Charge hose To increase pressure resistance the hose material and base size were changed R32 R410A Vacuum pump A conventional vacuum pump can be used by installing a vacuum pump adapter Use of a vacuum pump with a series motor is prohibited Gas leakage detector Special gas leakage detector for HFC refrigerant R410A or R32 Copper pipes It is necessary...

Страница 5: ...g such work with an insufficient number of people or with inadequate equip ment could result in dropping of the unit or personal injury CAUTION For installation details refer to the technical data 3 1 Selecting an installation location Decide the mounting position together with the customer as follows WARNING Install the indoor unit where is capable to support the weight of the unit Secure the uni...

Страница 6: ...ent could result in dropping of the unit or personal injury If the job is done with the panel frame only there is a risk that the unit will come loose Please take care When fastening the hangers make the bolt positions uniform CAUTION Confirm the directions of the air intake and outlet before installing the unit The unit takes in air from the evaporator side and expels it from the fan side 3 3 1 P...

Страница 7: ...pply Room Duct Field supply When connecting the duct perform duct insulation appropriate for the installing environment Inappropriate insulation work may cause condensation on the surface of the insulat ing material and may lead to condensation dripping 3 5 Drain installation CAUTION Install the drain hose in accordance with the instructions in this installation manual and keep the area warm enoug...

Страница 8: ...ing installation make sure that the refrigerant pipe is attached firmly before you run the compressor Do not operate the compressor under the condition of refrigerant piping not attached properly with 2 way or 3 way valve open This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury During the pump down operation make sure that the compressor is turned off...

Страница 9: ...are nut cannot be tightened smoothly If the flare nut is forced to turn the threads will be damaged Do not remove the flare nut from the indoor unit pipe until immediately before connecting the connection pipe Do not use mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units 1 Detach the caps and plugs from the pipes 2 Centering t...

Страница 10: ... ground cable to a gas pipe water pipe lightning rod or a telephone earth ground cable Improper earthing grounding may cause electric shocks Do not connect power supply cables to the transmission or remote control terminals as this will damage the product Never bundle the power supply cable and transmission cable together Bundling these cables together will cause miss operation When handling PCB s...

Страница 11: ...ternal in out PCB CN47 External out This air conditioner can be connected with the following optional kits For details on how to install optional parts refer to the installation manual included in each item Connector No Option type CN48 IR Receiver UTY LBT M CN8 Remote sensor UTY XSZX CN47 1 Connect wire UTY XWZXZG CN65 2 External input and output PCB UTY XCSX 1 For external output terminal settin...

Страница 12: ... is used The original connector should be insulated to ensure that it does not come into contact with other electrical circuitry Setting for room temperature correction When a remote sensor is connected set the function setting of indoor unit as indicated below Set Function Number 30 Room temperature control for cooling to 00 Set Function Number 31 Room temperature control for heating to 01 5 REMO...

Страница 13: ...on details Filter sign Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated amount of dust in the air of the room If the indication is not required select No indication 03 Factory setting Function Number Setting Value Setting Description 11 00 Standard 2500 hours 01 Long interval 4400 hours 02 Short interval 1250 hours 03 No indication Room temp...

Страница 14: ... outdoor unit is stopped the indoor unit fan operates intermittently at a very low speed 02 Enable or disable this function by remote controller setting When using a wired remote controller without Indoor unit fan control for energy saving for cooling function or when connecting a single split converter the setting cannot be made by using the remote controller Set to 00 or 01 To confirm if the rem...

Страница 15: ...unded Is the connection cable the specified thickness Are the inlets and outlets free of any obstacles After installation is completed has the proper operation and handling been explained to the user Operate the unit according to the operating manual provided and check that it is operating normally 8 TEST RUN 8 1 Check items Is operation of each button on the remote control unit normal Does each l...

Страница 16: ...ed remote controller error 4 1 Room temp sensor error 4 2 Indoor unit heat ex middle temp sensor error 4 4 Human sensor error 5 1 Indoor unit fan motor error 5 3 Drain pump error 5 7 Damper error 5 15 Indoor unit error 6 1 Outdoor unit reverse missing phase and wiring error Error display Wired remote controller Error code Description OPERATION lamp green TIMER lamp orange ECONOMY lamp green 6 2 Ou...

Отзывы: