background image

En-9

3. 6. 1.  Pipe connection

 

Flaring

Use special pipe cutter and 

fl

 are tool designed for R410A or R32 pipework.

(1)  Cut the connection pipe to the necessary length with a pipe cutter.
(2)  Hold the pipe downward so that cuttings will not enter the pipe and remove any burrs.
(3) Insert 

the 

fl

 are nut (always use the 

fl

 are nut attached to the indoor unit(s) and outdoor 

unit or branch box respectively) onto the pipe and perform the 

fl

 are processing with a 

fl

 are tool. Use the special R410A or R32 

fl

 are tool, or the conventional 

fl

 are tool. Leak-

age of refrigerant may result if other 

fl

 are nuts are used.

(4)  Protect the pipes by pinching them or with tape to prevent dust, dirt, or water from 

entering the pipes.

Check if [L] is 

fl

 ared uniformly 

and is not cracked or scratched.

Pipe

Die

B

A

L

Pipe outside 

diameter 

[mm (in.)]

Dimension A [mm]

Dimension B

-

0

0.4

 [mm]

Flare tool for R32, 

clutch type

6.35 (1/4)

0 to 0.5

9.1

9.52 (3/8)

13.2

12.70 (1/2)

16.6

15.88 (5/8)

19.7

19.05 (3/4)

24.0

When using conventional 

fl

 are tools to 

fl

 are R32 pipes, the dimension A should be 

approximately 0.5 mm more than indicated in the table (for 

fl

 aring with R32 

fl

 are tools) to 

achieve the speci

fi

 ed 

fl

 aring. Use a thickness gauge to measure the dimension A.

Width across 

fl

 ats

Pipe outside 

diameter [mm (in.)]

Width across 

fl

 ats 

of Flare nut [mm]

6.35 (1/4)

17

9.52 (3/8)

22

12.70 (1/2)

26

15.88 (5/8)

29

19.05 (3/4)

36

NOTE

:  The 

fl

 are nut speci

fi

 cation is compliant with ISO14903.

 

Bending pipes

• If pipes are shaped by hand, be careful not to collapse them.
• Do not bend the pipes in an angle more than 90°.
• When pipes are repeatedly bend or stretched, the material will harden, making it dif

fi

 cult 

to bend or stretch them any more. 

• Do not bend or stretch the pipes more than 3 times.

 CAUTION

• To prevent breaking of the pipe, avoid sharp bends. Bend the pipe with a radius of 

curvature of 150 mm or over.

• If the pipe is bent repeatedly at the same place, it will break.

 

Flare connection

 CAUTION

• Be sure to apply the pipe against the port on the indoor unit correctly. If the centering 

is improper, the 

fl

 are nut cannot be tightened smoothly. If the 

fl

 are nut is forced to 

turn, the threads will be damaged.

• Do not remove the 

fl

 are nut from the indoor unit pipe until immediately before 

connecting the connection pipe.

• Do not use mineral oil on 

fl

 ared part. Prevent mineral oil from getting into the system 

as this would reduce the lifetime of the units.

(1)  Detach the caps and plugs from the pipes.
(2)  Centering the pipe against port on the indoor unit, turn the 

fl

 are nut with your hand.

(3) When the 

fl

 are nut is tightened properly by your hand, hold the body side coupling with 

a separate spanner, then tighten with a torque wrench. (See the table below for the 

fl

 are nut tightening torques.)

 CAUTION

• Hold the torque wrench at its grip, keeping it in the right angle with the pipe, in order 

to tighten the 

fl

 are nut correctly.

• Tighten the 

fl

 are nuts with a torque wrench using the speci

fi

 ed tightening method. 

Otherwise, the 

fl

 are nuts could break after a prolonged period, causing refrigerant to 

leak and generate a hazardous gas if the refrigerant comes into contact with a 

fl

 ame.

Connection pipe

Tighten with 2 wrenches.

Holding Wrench

Flare nut

Torque wrench

Indoor unit pipe 
(Body side)

Flare nut [mm (in.)]

Tightening torque [N·m (kgf·cm)]

6.35 (1/4) dia.

16 to 18 (160 to 180)

9.52 (3/8) dia.

32 to 42 (320 to 420)

12.70 (1/2) dia.

49 to 61 (490 to 610)

15.88 (5/8) dia.

63 to 75 (630 to 750)

19.05 (3/4) dia.

90 to 110 (900 to 1,100)

3. 7.  Fresh air intake

 

Processing before use

(1)  When taking in fresh air, cut out the slit of the cabinet on the left side of the outer case 

with nippers.

Slit

Cabinet (iron plate)

 CAUTION

• When removing the cabinet (iron plate), be careful not to damage the indoor unit 

internal parts and surrounding area (outer case).

• When processing the cabinet (iron plate), be careful not to injure yourself with burrs, 

etc.

• When using the Fresh air intake, set the Room temperature sensor switching (Aux.) 

to “Wired Remote Controller” (01), or to use the Remote sensor.

(2)  Install the round 

fl

 ange to the fresh air intake.

Round 

fl

 ange (Locally purchased)

(3)  Connect the duct to the round 

fl

 ange.

(4)  Seal with a band and vinyl tape, etc. so that air does not leak from the connection.

Duct

9381386215-01_IM.indb   9

9381386215-01_IM.indb   9

12/5/2018   2:57:36 PM

12/5/2018   2:57:36 PM

Содержание ARXG-KHTAP Series

Страница 1: ...lation must be performed in accordance with regulations codes or standards for electrical wiring and equipment in each country region or the installation place Do not use means to accelerate the defrosting process or to clean other than those recommended by the manufacturer This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or ...

Страница 2: ...ance with an industry recognised assessment specification Servicing shall only be performed as recommended by the equipment manufacturer Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants Servicing shall be performed only as recommended by the manufacturer 2 2 Work Prior ...

Страница 3: ...nce to electrical components shall include initial safety checks and component inspection procedures If a fault exists that could compromise safety then no electrical supply shall be con nected to the circuit until it is satisfactorily dealt with If the fault cannot be corrected immediately but it is necessary to continue operation an adequate temporary solution shall be used This shall be reporte...

Страница 4: ...ure 0 1 to 3 8 MPa 1 to 38 bar for low pressure Charge hose To increase pressure resistance the hose material and base size were changed R32 R410A Vacuum pump A conventional vacuum pump can be used by installing a vacuum pump adapter Use of a vacuum pump with a series motor is prohibited Gas leakage detector Special gas leakage detector for HFC refrigerant R410A or R32 Copper pipes It is necessary...

Страница 5: ...g such work with an insufficient number of people or with inadequate equip ment could result in dropping of the unit or personal injury CAUTION For installation details refer to the technical data 3 1 Selecting an installation location Decide the mounting position together with the customer as follows WARNING Install the indoor unit where is capable to support the weight of the unit Secure the uni...

Страница 6: ...ent could result in dropping of the unit or personal injury If the job is done with the panel frame only there is a risk that the unit will come loose Please take care When fastening the hangers make the bolt positions uniform CAUTION Confirm the directions of the air intake and outlet before installing the unit The unit takes in air from the evaporator side and expels it from the fan side 3 3 1 P...

Страница 7: ...pply Room Duct Field supply When connecting the duct perform duct insulation appropriate for the installing environment Inappropriate insulation work may cause condensation on the surface of the insulat ing material and may lead to condensation dripping 3 5 Drain installation CAUTION Install the drain hose in accordance with the instructions in this installation manual and keep the area warm enoug...

Страница 8: ...ing installation make sure that the refrigerant pipe is attached firmly before you run the compressor Do not operate the compressor under the condition of refrigerant piping not attached properly with 2 way or 3 way valve open This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury During the pump down operation make sure that the compressor is turned off...

Страница 9: ...are nut cannot be tightened smoothly If the flare nut is forced to turn the threads will be damaged Do not remove the flare nut from the indoor unit pipe until immediately before connecting the connection pipe Do not use mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units 1 Detach the caps and plugs from the pipes 2 Centering t...

Страница 10: ... ground cable to a gas pipe water pipe lightning rod or a telephone earth ground cable Improper earthing grounding may cause electric shocks Do not connect power supply cables to the transmission or remote control terminals as this will damage the product Never bundle the power supply cable and transmission cable together Bundling these cables together will cause miss operation When handling PCB s...

Страница 11: ...ternal in out PCB CN47 External out This air conditioner can be connected with the following optional kits For details on how to install optional parts refer to the installation manual included in each item Connector No Option type CN48 IR Receiver UTY LBT M CN8 Remote sensor UTY XSZX CN47 1 Connect wire UTY XWZXZG CN65 2 External input and output PCB UTY XCSX 1 For external output terminal settin...

Страница 12: ... is used The original connector should be insulated to ensure that it does not come into contact with other electrical circuitry Setting for room temperature correction When a remote sensor is connected set the function setting of indoor unit as indicated below Set Function Number 30 Room temperature control for cooling to 00 Set Function Number 31 Room temperature control for heating to 01 5 REMO...

Страница 13: ...on details Filter sign Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated amount of dust in the air of the room If the indication is not required select No indication 03 Factory setting Function Number Setting Value Setting Description 11 00 Standard 2500 hours 01 Long interval 4400 hours 02 Short interval 1250 hours 03 No indication Room temp...

Страница 14: ... outdoor unit is stopped the indoor unit fan operates intermittently at a very low speed 02 Enable or disable this function by remote controller setting When using a wired remote controller without Indoor unit fan control for energy saving for cooling function or when connecting a single split converter the setting cannot be made by using the remote controller Set to 00 or 01 To confirm if the rem...

Страница 15: ...unded Is the connection cable the specified thickness Are the inlets and outlets free of any obstacles After installation is completed has the proper operation and handling been explained to the user Operate the unit according to the operating manual provided and check that it is operating normally 8 TEST RUN 8 1 Check items Is operation of each button on the remote control unit normal Does each l...

Страница 16: ...ed remote controller error 4 1 Room temp sensor error 4 2 Indoor unit heat ex middle temp sensor error 4 4 Human sensor error 5 1 Indoor unit fan motor error 5 3 Drain pump error 5 7 Damper error 5 15 Indoor unit error 6 1 Outdoor unit reverse missing phase and wiring error Error display Wired remote controller Error code Description OPERATION lamp green TIMER lamp orange ECONOMY lamp green 6 2 Ou...

Отзывы: