3. OUTDOOR UNIT & BRANCH BOX
BRANCH BOX
3-2.
The branch box can be installed onto the wall or hanging from the ceiling.
●
The branch box can be installed and set horizontally or vertically.
●
Provide a service access for maintenance and inspection purposes as shown in the figure
●
below.
It is not necessary to provide drainage for the branch box.
●
The slope of the top side must be within ±5° in all directions of the horizontal plane.
●
Use M8 or M10 (5/16" or 3/8") for the bolt size when hanging.
●
HORIZONTAL INSTALLATION
3-2-1.
Be sure to install so that the top side faces up.
1-3/4 (44)
Top side
18-15/32 (469)
Hanger bolt pitch
Hanger bolt pitch
10-3/32 (256)
(13 (304))
15/16 (24)
Top side
Outdoor unit side
Indoor unit side
(33 (838))
17-1/16 (433)
6-1/16 (154)
9-7/8 (251)
(13 (304))
4-3/4 (120)
7-11/16 (195)
2-23/32 (69)
Installation dimensions
Service access
34 (850) or more
15 (360) or more
21 (530) or more
)
e
c
a
p
s
e
c
i
v
r
e
S
(
)
e
c
a
p
s
e
c
i
v
r
e
S
(
(Service space)
12 (300)
or more
28 (700) or more
UNIT
A
UNIT
B
UNIT
C
Wall installation
63/64
(25)
5-53/64
(148)
1-9/16 (40)
1-9/16 (40)
2-15/16 (75)
3-3/4 (95)
3-1
1/32 (85)
1-5/8 (42)
2-1/4 (57)
3-3/4
(95)
3-3/4
(95)
- (03 - 08) -
OU
TDOOR
UNITS
OU
TDOOR
UNITS
Содержание ARU12RLF
Страница 1: ...VD014E 06 FUJITSU GENERAL LIMITED DESIGN TECHNICAL MANUAL Hybrid Flex Inverter System DTR_BMU001E_05 ...
Страница 3: ...1 GENERAL INFORMATION DTR_BMU001E_03 CHAPTER01 2010 08 25 Hybrid Flex Inverter System ...
Страница 18: ...2 MODEL SELECTION DTR_BMU001E_04 CHAPTER02 2010 10 04 Hybrid Flex Inverter System ...
Страница 38: ...3 OUTDOOR UNIT BRANCH BOX Hybrid Flex Inverter System DTR_BMU001E_04 CHAPTER03 2010 10 04 ...
Страница 58: ...4 INDOOR UNITS Hybrid Flex Inverter System DTR_BMU001E_05 CHAPTER04 2010 11 12 ...
Страница 82: ...4 INDOOR UNITS SLIM DUCT TYPE 5 2 MODELS ARU9RLF ARU12RLF ARU18RLF ARU24RLF 04 22 INDOOR UNITS INDOOR UNITS ...
Страница 83: ...4 INDOOR UNITS COMPACT WALL MOUNTED TYPE 5 3 MODELS AS U7RLF ASU9RLF ASU12RLF 04 23 INDOOR UNITS INDOOR UNITS ...
Страница 84: ...4 INDOOR UNITS WALL MOUNTED TYPE 5 4 MODELS AS U18RLF ASU24RLF 04 24 INDOOR UNITS INDOOR UNITS ...
Страница 116: ...5 CONTROL SYSTEM DTR_BMU001E_04 CHAPTER05 2010 10 04 Hybrid Flex Inverter System ...
Страница 152: ...6 SYSTEM DESIGN DTR_BMU001E_04 CHAPTER06 2010 10 04 Hybrid Flex Inverter System ...
Страница 287: ...7 OPTIONAL PARTS Hybrid Flex Inverter System DTR_BMU001E_03 CHAPTER07 2010 08 25 ...
Страница 288: ...CONTENTS 7 OPTIONAL PARTS 1 SEPARATION TUBE 07 01 2 BRANCH BOX 07 02 3 CONTROLLER 07 04 4 OTHERS 07 05 ...