2. MODEL SELECTION
CAPACITY COMPENSATION COEFFICIENT
5.
COMPENSATION COEFFICIENT OF PIPE LENGTH
5-1.
The figures give the compensation coefficient of pipe length owing to installation position.
CAPACITY CHANGE RATE BY MAIN PIPING LENGTH
Change rate in capacity
Main piping length
ft.
16.4
32.8
49.2
65.6
82.0
98.4
114.8
131.2
147.6
164.0
180.4
m
5
10
15
20
25
30
35
40
45
50
55
Change rate in
cooling capacity
%
100
98.0
96.0
94.0
92.0
90.0
88.0
86.0
84.0
82.0
80.0
Change rate in
heating capacity
%
100
99.6
99.2
98.9
98.5
98.1
97.7
97.3
97.0
96.6
96.2
0
0
16.4
32.8
49.2
180.4
ft.
m
164.0
147.6
131.2
114.8
98.4
82.0
65.6
55
50
45
40
35
30
25
20
15
10
75
80
85
90
95
100
5
Change rate in c
apac
it
y (
%
)
Main piping length
Cooling
Heating
CAPACITY CHANGE RATE BY BRANCH PIPING LENGTH
Change rate in capacity
Refrigerant piping connection diameter: Liquid ø1/4in. (6.35mm) , Gas ø3/8in. (9.52mm)
●
Main piping length
ft.
9.8
16.4
32.8
49.2
m
3
5
10
15
Change rate in
cooling capacity
%
100
98.3
94.2
90.0
Change rate in
heating capacity
%
100
98.9
96.2
93.5
Refrigerant piping connection diameter: Liquid ø1/4in. (6.35mm) , Gas ø1/2in. (12.70mm)
●
Main piping length
ft.
9.8
16.4
32.8
49.2
m
3
5
10
15
Change rate in
cooling capacity
%
100
99.2
97.1
95.0
Change rate in
heating capacity
%
100
99.5
98.3
97.0
Refrigerant piping connection diameter: Liquid ø1/4in. (6.35mm) , Gas ø5/8in. (15.88mm)
●
Main piping length
ft.
9.8
16.4
32.8
49.2
m
3
5
10
15
Change rate in
cooling capacity
%
100
99.6
98.5
97.5
Change rate in
heating capacity
%
100
99.9
99.5
99.0
- (02 - 17) -
MODEL
SEL
E
CTI
ON
MODEL
SEL
E
CTI
ON
Содержание ARU12RLF
Страница 1: ...VD014E 06 FUJITSU GENERAL LIMITED DESIGN TECHNICAL MANUAL Hybrid Flex Inverter System DTR_BMU001E_05 ...
Страница 3: ...1 GENERAL INFORMATION DTR_BMU001E_03 CHAPTER01 2010 08 25 Hybrid Flex Inverter System ...
Страница 18: ...2 MODEL SELECTION DTR_BMU001E_04 CHAPTER02 2010 10 04 Hybrid Flex Inverter System ...
Страница 38: ...3 OUTDOOR UNIT BRANCH BOX Hybrid Flex Inverter System DTR_BMU001E_04 CHAPTER03 2010 10 04 ...
Страница 58: ...4 INDOOR UNITS Hybrid Flex Inverter System DTR_BMU001E_05 CHAPTER04 2010 11 12 ...
Страница 82: ...4 INDOOR UNITS SLIM DUCT TYPE 5 2 MODELS ARU9RLF ARU12RLF ARU18RLF ARU24RLF 04 22 INDOOR UNITS INDOOR UNITS ...
Страница 83: ...4 INDOOR UNITS COMPACT WALL MOUNTED TYPE 5 3 MODELS AS U7RLF ASU9RLF ASU12RLF 04 23 INDOOR UNITS INDOOR UNITS ...
Страница 84: ...4 INDOOR UNITS WALL MOUNTED TYPE 5 4 MODELS AS U18RLF ASU24RLF 04 24 INDOOR UNITS INDOOR UNITS ...
Страница 116: ...5 CONTROL SYSTEM DTR_BMU001E_04 CHAPTER05 2010 10 04 Hybrid Flex Inverter System ...
Страница 152: ...6 SYSTEM DESIGN DTR_BMU001E_04 CHAPTER06 2010 10 04 Hybrid Flex Inverter System ...
Страница 287: ...7 OPTIONAL PARTS Hybrid Flex Inverter System DTR_BMU001E_03 CHAPTER07 2010 08 25 ...
Страница 288: ...CONTENTS 7 OPTIONAL PARTS 1 SEPARATION TUBE 07 01 2 BRANCH BOX 07 02 3 CONTROLLER 07 04 4 OTHERS 07 05 ...