6. SYSTEM DESIGN
Fix the unit (For wall installation)
<Horizontal installation>
(1) Secure the hangers (accessories) with the
screws (2 pieces, Ø 4 x 10mm, accessories).
(4 places)
• Install the unit with its top side facing
upwards.
Screw
Hanger
Top side
(2) For temporary mounting of the unit, install two
of the Ø 4×25mm screws in the wall, allowing
the space of 5 to 10mm (3/16 to 3/8 inch)
between the wall and the screw heads. Then
hook the unit over these two screws.
(5 to 10 mm)
3/16 to 3/8 in.
18-15/32 in. (469 mm)
Pitch for securing
the tapping screws
Space
between wall
and head of
screw:
Tapping
screws
(3) After checking that the unit is fl at, secure and
mount the branch box with the 8 screws (Ø
4 x 25mm, accessories) provided including
the tapping screws. (The unit’s slope must be
within ±5° in all directions.)
Screw
Screw
Screw
Screw
<Vertical installation>
(1) Secure the hangers (accessories) with the
screws (2 pieces, Ø 4 x 10mm, accessories).
(4 places)
• Install the unit with the control box facing
upwards.
Screw
Hanger
Control box
(2) For temporary mounting of the unit, install two
of the Ø 4×25mm screws in the wall, allowing
the space of 5 to 10mm (3/16 to 3/8 inch)
between the wall and the screw heads. Then
hook the unit over these two screws.
18-15/32 in. (469 mm)
(5 to 10 mm)
3/16 to 3/8 in.
Pitch for securing
the tapping screws
Tapping
screws
Space
between wall
and head of
screw:
(3) After checking that the unit is fl at, secure and
mount the branch box with the 8 screws (Ø
4 x 25mm, accessories) provided including
the tapping screws. (The unit’s slope must be
within ±5° in all directions.)
Screw
Screw
Screw
Screw
- (06 - 34) -
SY
S
T
E
M
DE
SIGN
SY
S
T
E
M
DE
SIGN
Содержание ARU12RLF
Страница 1: ...VD014E 06 FUJITSU GENERAL LIMITED DESIGN TECHNICAL MANUAL Hybrid Flex Inverter System DTR_BMU001E_05 ...
Страница 3: ...1 GENERAL INFORMATION DTR_BMU001E_03 CHAPTER01 2010 08 25 Hybrid Flex Inverter System ...
Страница 18: ...2 MODEL SELECTION DTR_BMU001E_04 CHAPTER02 2010 10 04 Hybrid Flex Inverter System ...
Страница 38: ...3 OUTDOOR UNIT BRANCH BOX Hybrid Flex Inverter System DTR_BMU001E_04 CHAPTER03 2010 10 04 ...
Страница 58: ...4 INDOOR UNITS Hybrid Flex Inverter System DTR_BMU001E_05 CHAPTER04 2010 11 12 ...
Страница 82: ...4 INDOOR UNITS SLIM DUCT TYPE 5 2 MODELS ARU9RLF ARU12RLF ARU18RLF ARU24RLF 04 22 INDOOR UNITS INDOOR UNITS ...
Страница 83: ...4 INDOOR UNITS COMPACT WALL MOUNTED TYPE 5 3 MODELS AS U7RLF ASU9RLF ASU12RLF 04 23 INDOOR UNITS INDOOR UNITS ...
Страница 84: ...4 INDOOR UNITS WALL MOUNTED TYPE 5 4 MODELS AS U18RLF ASU24RLF 04 24 INDOOR UNITS INDOOR UNITS ...
Страница 116: ...5 CONTROL SYSTEM DTR_BMU001E_04 CHAPTER05 2010 10 04 Hybrid Flex Inverter System ...
Страница 152: ...6 SYSTEM DESIGN DTR_BMU001E_04 CHAPTER06 2010 10 04 Hybrid Flex Inverter System ...
Страница 287: ...7 OPTIONAL PARTS Hybrid Flex Inverter System DTR_BMU001E_03 CHAPTER07 2010 08 25 ...
Страница 288: ...CONTENTS 7 OPTIONAL PARTS 1 SEPARATION TUBE 07 01 2 BRANCH BOX 07 02 3 CONTROLLER 07 04 4 OTHERS 07 05 ...