6.3
Information display
Various data can be displayed by pressing the info
button.
Depending on the type of unit, configuration and
operating state, some of the info lines listed below
may not appear.
-
Possible error messages from the error code list
(See table, page 57).
-
Possible service messages from the maintenance
code list.
-
Possible special mode messages.
-
Various data (See below).
Designation
Line
Floor drying current setpoint
-
Current drying day
-
Terminated drying days
-
Room temperature
8721
State heat pump
8006
State supplementary source
8022
State DHW
8003
State swimming pool
8011
State heating circuit 1
8000
State cooling circuit 1
8001
State heating circuit 2
8004
Outside temperature
8700
Room setpoint 1
8740
Flow temperature 1
8743
Flow temperature setpoint1
Room setpoint 2
8771
Flow temperature 2
8773
Flow temperature setpoint 2
DHW (domestic hot water) temperature
8830
Heat pump return temperature
8410
Setpoint (flow) HP
Heat pump flow temperature
8412
Setpoint (flow) HP
Swimming pool temperature
8900
Swimming pool temperature setpoint
Installation and operating manual “1350-EN”
59
Heat pump, Split, single service
Outside unit,
Reference AOYA45LATL, AOYA45LBTL (Model 128) and Reference AOY54LJBYL (Model 155)
Diode display
Erroneous element
1 Flash
Transmission error, "hydraulic module - outside unit"
2 Flashes
Defective “discharge” temperature sensor
3 Flashes
Defective “evaporator” temperature sensor
4 Flashes
Defective “outside” temperature sensor
5 Flashes (Model 128)
Defective “evaporator centre” temperature sensor
6 Flashes (Model 128)
Abnormal discharge temperature
7 Flashes
Defective compressor temperature sensor
8 Flashes
Defective “compressor casing” temperature sensor
9 Flashes
Defective HP pressure switch
10 Flashes (Model 128)
Abnormal compressor temperature
12 Flashes
Defective IPM card
13 Flashes
Position of the compressor’s rotor not detected
14 Flashes
Compressor is not operating
15 Flashes
Defective upper fan motor
16 Flashes
Defective lower fan motor
5 seconds lit and 1 seconds unlit
Switched to safety mode
1 seconds lit and 1 seconds unlit (Model 128)
Switched to vacuum
Permanently lit
No error