Installation and operating manual “1350-EN”
39
Heat pump, Split, single service
1014
U
Frost-free ambient temperature setpoint
from 4°C… to reduced
temperature
0,5 °C
8 °C
1016
S
Maximum comfort setpoint
20…35 °C
1 °C
28 °C
1020
I
Heating curve slope
0.1... 4
0,02
0.5
1021
I
Off-set of the heating curve
-4.50 °C… 4.5 °C
0,5 °C
0 °C
1026
S
Adaptation of the heating curve (see § 3.3.2)
off, ON
off
1030
I
Summer/Winter heating limits
8 °C … 30 °C
0,5 °C
18 °C
When the average of the outside temperatures over the past 24 hours reaches 18°C, the regulator switches off the
heating (as an economy measure).
During summer mode, the display shows "Eco".
This function is only active in automatic mode.
1032
S
Limit of daily heating
-10 °C … 10 °C
1 °C
-3 °C
This function enables you partially to offset the automatic summer/winter switchover during the intermediate seasons.
Increasing the value delays the switchover to summer regime.
Decreasing the value advances the switchover to summer regime.
This function is only active in automatic mode.
1050
I
Influence of the ambient temperature
1%... 100%
1%
20%
If the installation is fitted with a room thermostat:
This function enables you to choose the ambient temperature's influence on the setting.
If no value is entered, the setting is made based on the temperature control.
If the parameter is set at 100%, the setting is only based on the ambient temperature.
1090
S
Maximum optimisation on switch-on
0 … 360 min
10 min
120 min
1091
S
Maximum optimisation on switch-off
0 … 360 min
10 min
120 min
1100
S
Start of increase in reduced functioning mode
- 30 … 10 °C, --- °C
1 °C
---
1101
S
End of increase in reduced functioning mode
- 30 … 10 °C, --- °C
1 °C
- 5 °C
1130
S
Mixer valve increase
0 … 50 °C
1 °C
0 °C
1132
S
Type of servomotor
2-pos, 3-pos
3-pos
1133
S
Switching differential 2-pos
0 … 20 °C
0,5 °C
2 °C
1134
S
Servomotor travel time
30 … 873 s
1 s
240 s
1150
I
Floor controlled drying (fig. 44)
off
– off: Early interruption of the current programme, programme inactive
– Operational heating
– Heating ready for occupation
– Operational h ready heating
– Ready h operational heating
– Manual
Manual mode enables you to programme your own concrete slab drying time.The function ends automatically after
25 days.
1151
I
Manual floor drying setpoint
(if line 850 = manual)
0 °C… 95°C
1 °C
25 °C
This function enables you to set the custom concrete slab drying temperature. This temperature remains fixed. The
concrete slab-drying programme stops automatically after running for 25 days.
1156
I
Current drying day
0 ... 32
1157
I
Terminated drying days
0 ... 32
1161
S
Excess heat evacuation
off, Heating regime,
Permanent
Permanent
Line
Function
Setting range
or display
Setting
increment
Basic
setting