![Fujitsu AOUH09LPAS1 Скачать руководство пользователя страница 95](http://html.mh-extra.com/html/fujitsu/aouh09lpas1/aouh09lpas1_service-manual_2344153095.webp)
•
Heating mode
F zone
E zone
D zone
C zone
B zone
A zone
66.2°F
(19°C)
32.0°F
(0°C)
5.0°F
(-15°C)
-13.0°F
(-25°C)
41.0°F
(5°C)
Model name
Outdoor temperature zone
Limitation of compressor
frequency
AOUH09LPAS1
A zone
43 rps
B zone
43 rps
C zone
30 rps
D zone
18 rps
E zone
16 rps
F zone
16 rps
AOUH12LPAS1
A zone
37 rps
B zone
37 rps
C zone
36 rps
D zone
15 rps
E zone
15 rps
F zone
1 rps
1-5. Limitation of compressor rotation number by outdoor temperature