Forced thermostat off function
Rotary SW on External
Input and Output PCB
External input
Input signal
Command
2
B
C
External Input and Output PCB
CN313
Off → On
Thermostat off
On → Off
Normal operation
On
Off
On
Off
Compressor
Room temp.
Set temp.
Input
¢
Control output function
•
Operation/Stop status
Rotary SW on External
Input and Output PCB
External output
Output
signal
Command
1
B
C
D
External Input and Output PCB
CN310
Off → On
Operation
On → Off
Stop
The output is low when the unit is stopped.
Operation
Stop
On
Off
CN310
Indoor unit
•
Error status
Rotary SW on External
Input and Output PCB
External output
Output
signal
Command
1
C
External Input and Output PCB
CN311
Off → On
Error
On → Off
Normal
D
CN312
Off → On
Error
On → Off
Normal
The output is ON when an error is generated for the indoor unit.
Error
Normal
On
Off
CN311―312
Indoor unit
2-4. Details of function
- (05-21) -
2. External input and output
FIELD
WORKING
FIELD
WORKING
Содержание AOUH09LPAS1
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2022 10 18 SR_CH01_AS050EF_02 ...
Страница 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 04 15 SR_CH02_AS050EF_02 ...
Страница 39: ...3 TROUBLESHOOTING 2021 07 XX SR_CH03_AS050EF_01 ...
Страница 41: ...5 2 Outdoor unit 03 43 CONTENTS continued ...
Страница 42: ......
Страница 87: ...4 CONTROL AND FUNCTIONS 2021 07 XX SR_CH04_AS050EF_01 ...
Страница 123: ...5 FILED WORKING 2021 06 28 SR_CH05_AS050EF_03 ...