Model: AOUH12LPAS1
•
1st time defrosting after starting operation
Compressor integrating
operation time
Less than 17 min.
17 to 57 min.
More than 57 min.
Condition
Does not operate
Tn ≤ 15.8°F (-9°C) and
Tn-Ta ≥ 9.0°F (5°C)
Tn ≤ 23.0°F (-5°C)
•
2nd time and after
Compressor integrating
operation time
Less than 40 min.
More than 40 min.
Condition
Does not operate
Tn-Tn10 < -9.0°F (-5°C) (Tn ≤ 21.2°F [-6°C])
Tn-Tnb < -3.6°F (-2°C) (Tn ≤ 21.2°F [-6°C])
Tn ≤ 1.4°F (-17°C) (Ta ≥ 14.0°F [-10°C])
Tn ≤ 19.4°F (-7°C) or Tn ≤ -4.0°F (-20°C) (Ta <
14.0°F [-10°C])
•
Integrating defrost (Constant monitoring)
Compressor integrating
operation time
More than 240 min. (For
long continuous
operation)
More than 213 min. (For
long continuous
operation
Less than 10 min.* (For
intermittent operation)
Condition
Tn ≤ 26.6°F (-3°C)
Tn ≤ 23.0°F (-5°C)
Count of the compressor
off: 40 times
*: If the compressor continuous operation time is less than 10 minutes, the number of the
compressor off is counted. If any defrost operated, the compressor off count is cleared.
•
Release condition
The defrost operation is released when either one of the conditions below is satisfied.
Outdoor unit heat exchanger temperature
(after 1 minute or later since compressor start)
60.8°F (16°C) or more
Compressor operation time
15 minutes
- (04-23) -
6. Defrost operation control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание AOUH09LPAS1
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2022 10 18 SR_CH01_AS050EF_02 ...
Страница 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 04 15 SR_CH02_AS050EF_02 ...
Страница 39: ...3 TROUBLESHOOTING 2021 07 XX SR_CH03_AS050EF_01 ...
Страница 41: ...5 2 Outdoor unit 03 43 CONTENTS continued ...
Страница 42: ......
Страница 87: ...4 CONTROL AND FUNCTIONS 2021 07 XX SR_CH04_AS050EF_01 ...
Страница 123: ...5 FILED WORKING 2021 06 28 SR_CH05_AS050EF_03 ...