2-8. E: 42. Indoor unit heat exchanger sensor error (Indoor unit)
Indicator
Indoor unit
Operation indicator
4 time flash
Timer indicator
2 time flash
Economy indicator
Continuous flash
Error code
E: 42
Detective actuator
Indoor unit main PCB
When heat exchanger temperature thermistor open or
short circuit is detected.
Heat exchanger temperature
thermistor
Forecast of cause
Connector connection failure
Thermistor failure
Main PCB failure
Check point 1. Check connection of connector
•
Check if connector is loose or removed.
•
Check erroneous connection.
•
Check if thermistor cable is open
-> Reset power when reinstalling due to removed connector or incorrect wiring.
↓
Check point 2. Remove connector and check thermistor resistance value
•
For the heat exchanger thermistor resistance value, refer to
•
If thermistor is either open or shorted, replace it and reset the power.
↓
Check point 3. Check voltage of main PCB
Make sure circuit diagram of each indoor unit and check terminal voltage at thermis-
tor (DC 5.0 V).
NOTE:
For details of thermistor connector, refer to
TECHNICAL DATA AND PARTS LIST on page 02-18.
(09-12 model: CN11)
If the voltage does not appear, replace main PCB.
↓
End
2-8. E: 42. Indoor unit heat exchanger sensor error (Indoor unit)
- (03-12) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Содержание AOUH09LPAS1
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2022 10 18 SR_CH01_AS050EF_02 ...
Страница 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 04 15 SR_CH02_AS050EF_02 ...
Страница 39: ...3 TROUBLESHOOTING 2021 07 XX SR_CH03_AS050EF_01 ...
Страница 41: ...5 2 Outdoor unit 03 43 CONTENTS continued ...
Страница 42: ......
Страница 87: ...4 CONTROL AND FUNCTIONS 2021 07 XX SR_CH04_AS050EF_01 ...
Страница 123: ...5 FILED WORKING 2021 06 28 SR_CH05_AS050EF_03 ...