1. Rotation number control of compressor
1-1. Cooling operation
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference
or variation between a set temperature and present room temperature, and controls the operation
rotation number of the compressor.
• If the room temperature is 11 °F (6.0 °C) higher than a set temperature, the operation rotation
number of compressor will attain to maximum performance.
• If the room temperature is 2 °F (1.0 °C) lower than a set temperature, the compressor will be
stopped.
• When the room temperature is within the range of +11 °F (6.0 °C) to -2 °F (1.0 °C) of the setting
temperature, the rotation number of compressor is controlled within the range shown in the table
below. However, the maximum rotation number is limited in the range shown in the figure below
based on the indoor fan mode and the outdoor temperature.
•
Rotation number range of compressor
Unit: rps
Model name
Minimum frequency
Maximum frequency
ASUH09LPAS
14
90
ASUH12LPAS
12
89
1-1. Cooling operation
- (04-1) -
1. Rotation number control of compressor
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание AOUH09LPAS1
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2022 10 18 SR_CH01_AS050EF_02 ...
Страница 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 04 15 SR_CH02_AS050EF_02 ...
Страница 39: ...3 TROUBLESHOOTING 2021 07 XX SR_CH03_AS050EF_01 ...
Страница 41: ...5 2 Outdoor unit 03 43 CONTENTS continued ...
Страница 42: ......
Страница 87: ...4 CONTROL AND FUNCTIONS 2021 07 XX SR_CH04_AS050EF_01 ...
Страница 123: ...5 FILED WORKING 2021 06 28 SR_CH05_AS050EF_03 ...