Cooling operation
Switch the airflow AUTO, and indoor fan motor will run according to room temperature, as below.
On the other hand, if switched in HIGH—QUIET, indoor motor will run at a constant airflow of COOL
operation modes QUIET, LOW, MED, HIGH as shown in “Fan speed” above.
Airflow change over (Cooling: Auto)
When room
temperature rises
When room
temperature drops
Tr - Ts ≥ 2
°C
HIGH mode
MED mode
LOW mode
2
°C
> Tr - Ts ≥ 1
°C
1
°C > Tr - Ts
Tr - Ts ≥ 2.5
°C
2.5
°C
> Tr - Ts ≥ 1.5
°C
1.5
°C > Tr - Ts
¢
Dry operation
During dry operation, fan speed setting can not be changed as shown in “Fan speed” above.
¢
Heating operation
Switch the airflow AUTO, and the indoor fan motor will run according to a room temperature, as be-
low.
On the other hand, if switched in HIGH—QUIET, the indoor motor will run at a constant airflow of
HEAT operation modes QUIET, LOW, MED, HIGH as shown in “Fan speed” above.
Airflow change over (Heating: Auto)
When the room
temperature rises
When the room
temperature drops
LOW mode
MED mode
MED+ mode
Tr - Ts ≥ -1
°C
-2
°C > Tr - Ts
Tr - Ts ≥ -1.5
°C
-1.5
°C
> Tr - Ts ≥ -2.5
°C
-2.5
°C > Tr - Ts
-1
°C
> Tr - Ts ≥ -2
°C
3-1. Indoor fan control
- (04-8) -
3. Fan control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание AOUG09LMAS1
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2019 12 20 SR_CH01_AS023EF_01 ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 01 28 SR_CH02_AS023EF_01 ...
Страница 33: ...3 TROUBLESHOOTING 2020 01 30 SR_CH03_AS023EF_02 ...
Страница 77: ...4 CONTROL AND FUNCTIONS 2020 03 25 SR_CH04_AS023EF_02 ...
Страница 107: ...5 FILED WORKING 2020 02 03 SR_CH05_AS023EF_01 ...