1. Compressor frequency control
1-1. Cooling operation
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference
or variation between a set temperature and present room temperature, and controls the operation
frequency of the compressor.
• If the room temperature is 6.0 °C higher than a set temperature, the compressor operation fre-
quency will attain to maximum performance.
• If the room temperature is 1.0 °C lower than a set temperature, the compressor will be stopped.
• When the room temperature is within the range of +6.0°C to -1.0°C of the setting temperature, the
compressor frequency is controlled within the range shown in the table below. However, the maxi-
mum frequency is limited in the range shown in the figure below based on the indoor fan mode
and the outdoor temperature.
•
Compressor frequency range
Model name
Minimum frequency
Maximum frequency
ASUG09LMAS
12 rps
67 rps
ASUG12LMAS
12 rps
89 rps
•
Limit of maximum speed based on outdoor temperature
36°C
A zone
34°C
32°C
B zone
30°C
21°C
C zone
19°C
D zone
E zone
F zone
10°C
0°C
12°C
2°C
Outdoor
temperature drops
Outdoor
temperature rises
Unit: rps
Model name
Outdoor
temperature
zone
Indoor unit fan mode
HIGH
MED
LOW
QUIET
ASUG09LMAS
A zone
67
47
36
26
B zone
67
47
36
26
C zone
67
47
36
26
D zone
54
42
34
26
E zone
54
42
34
26
F zone
54
42
34
26
ASUG12LMAS
A zone
89
54
38
26
B zone
89
54
38
26
C zone
89
54
38
26
D zone
62
44
38
26
E zone
62
44
38
26
F zone
62
44
38
26
1-1. Cooling operation
- (04-1) -
1. Compressor frequency control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание AOUG09LMAS1
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2019 12 20 SR_CH01_AS023EF_01 ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 01 28 SR_CH02_AS023EF_01 ...
Страница 33: ...3 TROUBLESHOOTING 2020 01 30 SR_CH03_AS023EF_02 ...
Страница 77: ...4 CONTROL AND FUNCTIONS 2020 03 25 SR_CH04_AS023EF_02 ...
Страница 107: ...5 FILED WORKING 2020 02 03 SR_CH05_AS023EF_01 ...