3-2. Outdoor fan control
¢
Outdoor fan motor
This outdoor unit has a DC fan motor. (Control method is different between AC and DC motors.)
¢
Fan speed
Model: AOUG09LMAS1
Fan speed is defined by outdoor temperature and compressor frequency.
•
Outside air temperature zone selection
21
°C
Outside air
temperature rises
Z zone
Y zone
F zone
G zone
Outside air
temperature drops
12
°C
2
°C
19
°C
10
°C
0
°C
Unit: rpm
Fan step
Cooling
Heating
Dry
Cooling or dry
Y zone
Y zone
Z zone
F zone
G zone
S-HIGH2
—
1,070
—
—
—
—
S-HIGH1
990
1,070
—
—
—
—
HIGH1
990
1,070
—
—
—
—
10
—
1,070
—
—
—
—
9
990
1,070
990
350
260
200
8
990
1,070
990
350
260
200
7
820
1,040
820
350
260
200
6
820
820
820
250
200
170
5
820
700
820
220
200
170
4
740
610
740
220
200
170
3
660
510
660
220
200
170
2
610
510
610
220
200
170
1
600
510
600
220
200
170
NOTE:
After defrost control on the heating mode, the fan speed is kept higher regardless of the
compressor frequency.
Fan speed after defrost control: 1,070 rpm
3-2. Outdoor fan control
- (04-11) -
3. Fan control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание AOUG09LMAS1
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2019 12 20 SR_CH01_AS023EF_01 ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 01 28 SR_CH02_AS023EF_01 ...
Страница 33: ...3 TROUBLESHOOTING 2020 01 30 SR_CH03_AS023EF_02 ...
Страница 77: ...4 CONTROL AND FUNCTIONS 2020 03 25 SR_CH04_AS023EF_02 ...
Страница 107: ...5 FILED WORKING 2020 02 03 SR_CH05_AS023EF_01 ...