4) Room temperature control for wired remote controller sensor
NOTE:
Before performing this setting, refer to Function 95.
Depending on the installed environment, correction of the wire remote temperature sensor may be
required. Select the appropriate control setting according to the installed environment.
To change this setting, set Function 42 to Both “01”.
Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
*When Function 95-01 (High insulation) is set, the Standard setting "00" will be the same as "No cor-
rection 0.0 °C" (01).
Function number
Setting value
Setting description
Factory
setting
35
(For cooling)
36
(For heating)
00
Standard setting*
♦
01
No correction 0.0 °F (0.0 °C)
02
-1 °F (-0.5 °C)
More cooling
Less heating
03
-2 °F (-1.0 °C)
04
-3 °F (-1.5 °C)
05
-4 °F (-2.0 °C)
06
-5 °F (-2.5 °C)
07
-6 °F (-3.0 °C)
08
-7 °F (-3.5 °C)
09
-8 °F (-4.0 °C)
10
+1 °F (+0.5 °C)
Less cooling
More heating
11
+2 °F (+1.0 °C)
12
+3 °F (+1.5 °C)
13
+4 °F (+2.0 °C)
14
+5 °F (+2.5 °C)
15
+6 °F (+3.0 °C)
16
+7 °F (+3.5 °C)
17
+8 °F (+4.0 °C)
5) Auto restart
Enables or disables automatic restart after a power interruption.
Function number
Setting value
Setting description
Factory setting
40
00
Enable
♦
01
Disable
NOTE:
Auto restart is an emergency function such as for power outage etc. Do not attempt to use
this function in normal operation. Be sure to operate the unit by remote controller or exter-
nal device.
6) Room temperature sensor switching
(Only for wired remote controller)
When using the wired remote controller temperature sensor, change the setting to "Both" (01).
Function number
Setting value
Setting description
Factory setting
42
00
Indoor unit
♦
01
Both
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller are active.
NOTE:
Remote controller sensor must be turned on by using the remote controller.
1-1. Function settings by using remote controller
- (05-5) -
1. Function settings
FIELD
WORKING
FIELD
WORKING
Содержание AOUG09LMAS1
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2019 12 20 SR_CH01_AS023EF_01 ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 01 28 SR_CH02_AS023EF_01 ...
Страница 33: ...3 TROUBLESHOOTING 2020 01 30 SR_CH03_AS023EF_02 ...
Страница 77: ...4 CONTROL AND FUNCTIONS 2020 03 25 SR_CH04_AS023EF_02 ...
Страница 107: ...5 FILED WORKING 2020 02 03 SR_CH05_AS023EF_01 ...