Trouble shooting 18
OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 : Check connection of around the Compressor components
OK
OK
OK
OK
Indicate or Display:
Check Point 3: Replace Main PCB
Outdoor unit Main PCB
Compressor
Compressor rotor position
detection error
1. Defective connection of electric components 2. Main PCB failure 3. Compressor failure
If Check Point 1,2 do not improve the symptom, change Main PCB.
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
(Refer to PARTS INFORMATION 2)
For Compressor Terminal, Main PCB
While running the compressor, if the detected rotor location is out of
phase with actual rotor location more than 105°,
the compressor stops.
After the compressor restarts, if the same operation is repeated
within 40sec, the compressor stops again.
If and repeats 5 times, the compressor stops permanently.
02-20
Check Point 1 : Check Noise from Compressor
Turn on Power and check operation noise.
If an abnormal noise show, replace Compressor.
OK
OK
Check Point 4: Replace Compressor
If Check Point 3 do not improve the symptom, change Compressor.
Outdoor Unit : LED 0.1sec ON/ 2sec OFF
Indoor Unit : Operation lamp: 9 times Flash, Timer lamp: 5 times Flash
Economy lamp: Continuous flash.
ERROR CODE : [E : 95]
Содержание AOTG36LATT
Страница 4: ...2008 11 20 3 31 12 330 900 1290 9 21 OUTDOOR UNIT unit mm 650 400 370 air flow ...
Страница 30: ...1204G4067 ...
Страница 34: ...Unit mm 2012 05 29 3 AOTG12LVCC OUTDOOR UNIT AOTG09LVCC 540 290 790 540 540 660 290 450 ...
Страница 60: ...1205G4083 ...
Страница 85: ...1307G4239 ...
Страница 113: ......
Страница 114: ...1 DESCRIPTION OF EACH CONTROL OPERATION WALL MOUNTED type INVERTER ...
Страница 135: ......
Страница 136: ...2 TROUBLE SHOOTING WALL MOUNTED type INVERTER ...
Страница 169: ......
Страница 170: ...3 APPENDING DATA WALL MOUNTED type INVERTER ...
Страница 176: ...4 INSTALLATION WORK WALL MOUNTED type INVERTER ...
Страница 181: ......
Страница 187: ......
Страница 188: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan September 2013 Printed in Japan ...
Страница 190: ...1 INDOOR UNIT WALL MOUNTED TYPE ASTG18KMCA ASTG22KMCA ASTG24KMCA DTR_AS082E_02 2013 09 13 ...
Страница 198: ... 01 07 WALL MOUNTED TYPE ASTG18 24KMCA WALL MOUNTED TYPE ASTG18 24KMCA INSTALLATION PLACE Unit mm ...
Страница 210: ... 01 19 WALL MOUNTED TYPE ASTG18 24KMCA WALL MOUNTED TYPE ASTG18 24KMCA SOUND LEVEL CHECK POINT 88888 ...
Страница 221: ...2 OUTDOOR UNIT SINGLE TYPE AOTG18KMCA AOTG22KMCA AOTG24KMCA DTR_AO144E_02 2013 09 13 ...
Страница 227: ... 02 05 OUTDOOR UNIT AOTG18 24KMCA OUTDOOR UNIT AOTG18 24KMCA WIRING DIAGRAMS 444 MODEL AOTG18KMCA AOTG22KMCA AOTG24KMCA ...
Страница 236: ... 02 14 OUTDOOR UNIT AOTG18 24KMCA OUTDOOR UNIT AOTG18 24KMCA SOUND LEVEL CHECK POINT 88888 ...
Страница 264: ...1208G4097 ...