Trouble shooting 11
INDOOR UNIT
OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
OK
OK
OK
OK
PFC circuit error
Outdoor unit Main PCB
1. External cause 2. Connector connection failure 3. Main PCB failure
Check Point 2 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 3 : Replace Main PCB
If Check Point 1, 2 do not improve the symptom, change Main PCB.
Check Point 1 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop : Check if there is a large load electric apparatus in the same circuit.
Momentary power failure : Check if there is a defective contact or leak current
in the power supply circuit.
Noise : Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
02-13
When inverter output DC voltage is higher than 420V for over 3 seconds,
the compressor stops.
If the same operation is repeated 5 times, the compressor stops permanently.
Outdoor Unit : No indication
Indoor Unit : Operation lamp: 6 times Flash, Timer lamp: 4 times Flash
Economy lamp: Continuous flash.
ERROR CODE : [E : 64]
Содержание AOTG36LATT
Страница 4: ...2008 11 20 3 31 12 330 900 1290 9 21 OUTDOOR UNIT unit mm 650 400 370 air flow ...
Страница 30: ...1204G4067 ...
Страница 34: ...Unit mm 2012 05 29 3 AOTG12LVCC OUTDOOR UNIT AOTG09LVCC 540 290 790 540 540 660 290 450 ...
Страница 60: ...1205G4083 ...
Страница 85: ...1307G4239 ...
Страница 113: ......
Страница 114: ...1 DESCRIPTION OF EACH CONTROL OPERATION WALL MOUNTED type INVERTER ...
Страница 135: ......
Страница 136: ...2 TROUBLE SHOOTING WALL MOUNTED type INVERTER ...
Страница 169: ......
Страница 170: ...3 APPENDING DATA WALL MOUNTED type INVERTER ...
Страница 176: ...4 INSTALLATION WORK WALL MOUNTED type INVERTER ...
Страница 181: ......
Страница 187: ......
Страница 188: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan September 2013 Printed in Japan ...
Страница 190: ...1 INDOOR UNIT WALL MOUNTED TYPE ASTG18KMCA ASTG22KMCA ASTG24KMCA DTR_AS082E_02 2013 09 13 ...
Страница 198: ... 01 07 WALL MOUNTED TYPE ASTG18 24KMCA WALL MOUNTED TYPE ASTG18 24KMCA INSTALLATION PLACE Unit mm ...
Страница 210: ... 01 19 WALL MOUNTED TYPE ASTG18 24KMCA WALL MOUNTED TYPE ASTG18 24KMCA SOUND LEVEL CHECK POINT 88888 ...
Страница 221: ...2 OUTDOOR UNIT SINGLE TYPE AOTG18KMCA AOTG22KMCA AOTG24KMCA DTR_AO144E_02 2013 09 13 ...
Страница 227: ... 02 05 OUTDOOR UNIT AOTG18 24KMCA OUTDOOR UNIT AOTG18 24KMCA WIRING DIAGRAMS 444 MODEL AOTG18KMCA AOTG22KMCA AOTG24KMCA ...
Страница 236: ... 02 14 OUTDOOR UNIT AOTG18 24KMCA OUTDOOR UNIT AOTG18 24KMCA SOUND LEVEL CHECK POINT 88888 ...
Страница 264: ...1208G4097 ...