25. VARIOUS PROTECTIONS
1. DISCHARGE GAS TEMPERATURE OVERRISE PREVENSION CONTROL
The discharge gas thermosensor (discharge thermistor : Outdoor side) will detect discharge gas
temperature.
104°C
101°C
110°C
When the discharge temperature becomes higher than Temperature ,the compressor frequency
is decreased 20rps, and it continues to decrease the frequency for 20rps every 120 seconds until
the temperature becomes lower than Temperature .
When the discharge temperature becomes lower than Temperature , the control of the control of
the compressor frequency is released.
When the discharge temperature becomes higher than Temperature ,the compressor is stopped
and the indoor unit LED starts blinking.
(Table 21 : Discharge Temperature Over Rise Prevension Control / Release Temperature)
Temperature
Temperature
Temperature
2. CURRENT RELEASE CONTROL
The compressor frequency is controlled so that the outdoor unit input current does not exceeds
the current limit velue that was set up with the outdoor temperature.
The compressor frequency returns to the designated frequency of the indoor unit at the time
when the frequency becomes lower than the release value.
(Table 22 : Current Release Operation Value / Release Value)
01-18
[ Heating ]
10.5A/ 10.0A
13.0A/ 12.5A
15.0A/ 14.5A
15.0A/ 14.5A
OT (Control / Release)
OT :Outdoor Temperature
AOTG22/ 24KMCA
7.0A/ 6.5A
9.5A/ 9.0A
12.0A/ 11.5A
OT (Control / Release)
OT :Outdoor Temperature
AOTG22/ 24KMCA
[ Cooling ]
17°C
12°C
5°C
46°C
40°C
7.0A/ 6.5A
9.0A/ 8.5A
11.0A/ 10.5A
13.0A/ 12.5A
OT (Control / Release)
OT :Outdoor Temperature
AOTG18KMCA
4.5A/ 4.0A
6.0A/ 5.5A
9.0A/ 8.5A
OT (Control / Release)
OT :Outdoor Temperature
AOTG18KMCA
17°C
12°C
5°C
46°C
40°C
Содержание AOTG36LATT
Страница 4: ...2008 11 20 3 31 12 330 900 1290 9 21 OUTDOOR UNIT unit mm 650 400 370 air flow ...
Страница 30: ...1204G4067 ...
Страница 34: ...Unit mm 2012 05 29 3 AOTG12LVCC OUTDOOR UNIT AOTG09LVCC 540 290 790 540 540 660 290 450 ...
Страница 60: ...1205G4083 ...
Страница 85: ...1307G4239 ...
Страница 113: ......
Страница 114: ...1 DESCRIPTION OF EACH CONTROL OPERATION WALL MOUNTED type INVERTER ...
Страница 135: ......
Страница 136: ...2 TROUBLE SHOOTING WALL MOUNTED type INVERTER ...
Страница 169: ......
Страница 170: ...3 APPENDING DATA WALL MOUNTED type INVERTER ...
Страница 176: ...4 INSTALLATION WORK WALL MOUNTED type INVERTER ...
Страница 181: ......
Страница 187: ......
Страница 188: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan September 2013 Printed in Japan ...
Страница 190: ...1 INDOOR UNIT WALL MOUNTED TYPE ASTG18KMCA ASTG22KMCA ASTG24KMCA DTR_AS082E_02 2013 09 13 ...
Страница 198: ... 01 07 WALL MOUNTED TYPE ASTG18 24KMCA WALL MOUNTED TYPE ASTG18 24KMCA INSTALLATION PLACE Unit mm ...
Страница 210: ... 01 19 WALL MOUNTED TYPE ASTG18 24KMCA WALL MOUNTED TYPE ASTG18 24KMCA SOUND LEVEL CHECK POINT 88888 ...
Страница 221: ...2 OUTDOOR UNIT SINGLE TYPE AOTG18KMCA AOTG22KMCA AOTG24KMCA DTR_AO144E_02 2013 09 13 ...
Страница 227: ... 02 05 OUTDOOR UNIT AOTG18 24KMCA OUTDOOR UNIT AOTG18 24KMCA WIRING DIAGRAMS 444 MODEL AOTG18KMCA AOTG22KMCA AOTG24KMCA ...
Страница 236: ... 02 14 OUTDOOR UNIT AOTG18 24KMCA OUTDOOR UNIT AOTG18 24KMCA SOUND LEVEL CHECK POINT 88888 ...
Страница 264: ...1208G4097 ...