Trouble shooting 7
INDOOR UNIT
INDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 :
62.9
103.3
134.2
176.0
233.2
312.3
579.6
1131.9
Resistance Value (k )
Temperature
OK
OK
OK
17.1
25.6
39.6
Resistance Value (k )
Temperature
Indoor unit Heat Ex. Middle temp.
sensor error
Indoor unit Controller PCB
Heat Ex. temperature thermistor
When Heat Ex. Temperature Thermistor open or short-circuit is detected.
1. Connector connection failure 2.Thermistor failure 3. Controller PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of indoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Controller PCB.
02-09
20°C
10°C
5°C
0°C
-5°C
-10°C
-20°C
-30°C
50°C
11.6
60°C
10.4
63°C
40°C
30°C
Outdoor Unit : No indication
Indoor Unit : Operation lamp: 4 times Flash, Timer lamp: 2 times Flash
Economy lamp: Continuous flash.
ERROR CODE : [E : 42]
THERMISTOR
(ROOM TEMP.)
THERMISTOR
(PIPE)
BLACK
CN4
1
2
3
4
1
2
3
4
BLACK
BLACK
BLACK
Содержание AOTG36LATT
Страница 4: ...2008 11 20 3 31 12 330 900 1290 9 21 OUTDOOR UNIT unit mm 650 400 370 air flow ...
Страница 30: ...1204G4067 ...
Страница 34: ...Unit mm 2012 05 29 3 AOTG12LVCC OUTDOOR UNIT AOTG09LVCC 540 290 790 540 540 660 290 450 ...
Страница 60: ...1205G4083 ...
Страница 85: ...1307G4239 ...
Страница 113: ......
Страница 114: ...1 DESCRIPTION OF EACH CONTROL OPERATION WALL MOUNTED type INVERTER ...
Страница 135: ......
Страница 136: ...2 TROUBLE SHOOTING WALL MOUNTED type INVERTER ...
Страница 169: ......
Страница 170: ...3 APPENDING DATA WALL MOUNTED type INVERTER ...
Страница 176: ...4 INSTALLATION WORK WALL MOUNTED type INVERTER ...
Страница 181: ......
Страница 187: ......
Страница 188: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan September 2013 Printed in Japan ...
Страница 190: ...1 INDOOR UNIT WALL MOUNTED TYPE ASTG18KMCA ASTG22KMCA ASTG24KMCA DTR_AS082E_02 2013 09 13 ...
Страница 198: ... 01 07 WALL MOUNTED TYPE ASTG18 24KMCA WALL MOUNTED TYPE ASTG18 24KMCA INSTALLATION PLACE Unit mm ...
Страница 210: ... 01 19 WALL MOUNTED TYPE ASTG18 24KMCA WALL MOUNTED TYPE ASTG18 24KMCA SOUND LEVEL CHECK POINT 88888 ...
Страница 221: ...2 OUTDOOR UNIT SINGLE TYPE AOTG18KMCA AOTG22KMCA AOTG24KMCA DTR_AO144E_02 2013 09 13 ...
Страница 227: ... 02 05 OUTDOOR UNIT AOTG18 24KMCA OUTDOOR UNIT AOTG18 24KMCA WIRING DIAGRAMS 444 MODEL AOTG18KMCA AOTG22KMCA AOTG24KMCA ...
Страница 236: ... 02 14 OUTDOOR UNIT AOTG18 24KMCA OUTDOOR UNIT AOTG18 24KMCA SOUND LEVEL CHECK POINT 88888 ...
Страница 264: ...1208G4097 ...