Trouble shooting 20
INDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
OK
OK
OK
OK
4-way valve error
Indoor unit Controller PCB
Heat Ex. temperature thermistor
Room temperature thermistor
4-way valve
When the indoor heat exchanger temperature is compared with
the room temperature, and either following condition is detected
continuously 2 times, the compressor stops.
1. Connector connection failure 2. Thermistor failure 3. Coil failure 4. 4-way valve failure
5. Controller PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 3 : Check the solenoid coil and 4-way valve
Remove CN30 from PCB and check the resistance value of coil.
Resistance value is 2.085
>> If it is Open or abnormal resistance value, replace Solenoid Coil.
02-22
Cooling or Dry operation
[Indoor heat exchanger temp.] - [Room temp.] > 10degC
Heating operation
[Indoor heat exchanger temp.] - [room temp.] < -10degC
If the same operation is repeated 5 times,
the compressor stops permanently.
[ Solenoid coil ]
Check each piping temperature,
and the location of the valve by the temperature difference.
>> If the value location is not proper, replace 4-way valve.
[ 4-way valve ]
OK
OK
Check Point 4 : Replace Controller PCB
If Check Point 1- 3 do not improve the symptom, replace Controller PCB.
Check Point 2 : Check each thermistor
Isn’t it fallen off the holder?
Is there a cable pinched?
>> Check characteristics of thermistor (Refer to Trouble shooting 5, 6),
If defective, replace the thermistor
Outdoor Unit : No indication
Indoor Unit : Operation lamp: 9 times Flash, Timer lamp: 9 times Flash
Economy lamp: Continuous flash.
ERROR CODE : [E : 99]
Содержание AOTG36LATT
Страница 4: ...2008 11 20 3 31 12 330 900 1290 9 21 OUTDOOR UNIT unit mm 650 400 370 air flow ...
Страница 30: ...1204G4067 ...
Страница 34: ...Unit mm 2012 05 29 3 AOTG12LVCC OUTDOOR UNIT AOTG09LVCC 540 290 790 540 540 660 290 450 ...
Страница 60: ...1205G4083 ...
Страница 85: ...1307G4239 ...
Страница 113: ......
Страница 114: ...1 DESCRIPTION OF EACH CONTROL OPERATION WALL MOUNTED type INVERTER ...
Страница 135: ......
Страница 136: ...2 TROUBLE SHOOTING WALL MOUNTED type INVERTER ...
Страница 169: ......
Страница 170: ...3 APPENDING DATA WALL MOUNTED type INVERTER ...
Страница 176: ...4 INSTALLATION WORK WALL MOUNTED type INVERTER ...
Страница 181: ......
Страница 187: ......
Страница 188: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan September 2013 Printed in Japan ...
Страница 190: ...1 INDOOR UNIT WALL MOUNTED TYPE ASTG18KMCA ASTG22KMCA ASTG24KMCA DTR_AS082E_02 2013 09 13 ...
Страница 198: ... 01 07 WALL MOUNTED TYPE ASTG18 24KMCA WALL MOUNTED TYPE ASTG18 24KMCA INSTALLATION PLACE Unit mm ...
Страница 210: ... 01 19 WALL MOUNTED TYPE ASTG18 24KMCA WALL MOUNTED TYPE ASTG18 24KMCA SOUND LEVEL CHECK POINT 88888 ...
Страница 221: ...2 OUTDOOR UNIT SINGLE TYPE AOTG18KMCA AOTG22KMCA AOTG24KMCA DTR_AO144E_02 2013 09 13 ...
Страница 227: ... 02 05 OUTDOOR UNIT AOTG18 24KMCA OUTDOOR UNIT AOTG18 24KMCA WIRING DIAGRAMS 444 MODEL AOTG18KMCA AOTG22KMCA AOTG24KMCA ...
Страница 236: ... 02 14 OUTDOOR UNIT AOTG18 24KMCA OUTDOOR UNIT AOTG18 24KMCA SOUND LEVEL CHECK POINT 88888 ...
Страница 264: ...1208G4097 ...