Trouble shooting 16
INDOOR UNIT
OUTDOOR UNIT Error Method:
Indicate or Display:
Indoor Unit : No LED
Outdoor Unit : No indication
ERROR CODE : E : 19
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 3 : Check Active Filter Module
OK
OK
OK
OK
OK
OK
Active Filter Module (AFM) error
Outdoor Unit Main PCB Circuit
Active Filter Module
1. External cause 2. Connector connection failure 3. Active Filter Module failure
4
. Main PCB failure
Check Point 2 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Active Filter Module.
(PARTS INFORMATION 3)
>>If Active Filter Module is abnormal, replace it.
Check Point 4 : Replace Main PCB
If Check Point 1, 2 do not improve the symptom, change Main PCB.
Check Point 1 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop : Check if there is a large load electric apparatus in the same circuit.
Momentary power failure : Check if there is a defective contact or leak current
in the power supply circuit.
Noise : Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
07-19
When inverter input DC voltage is higher than 467V or
lower than 237V.
When a momentary power cut off occurred on low voltage.
Содержание AO*24LMAKL
Страница 5: ...1 SPECIFICATIONS R410A CASSETTE type INVERTER ...
Страница 11: ...2 DIMENSIONS R410A CASSETTE type INVERTER ...
Страница 15: ...3 REFRIGERANT SYSTEM DIAGRAM R410A CASSETTE type INVERTER ...
Страница 19: ...4 CIRCUIT DIAGRAM R410A CASSETTE type INVERTER ...
Страница 25: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A CASSETTE type INVERTER ...
Страница 47: ...6 REFRIGERANT CAUTION R410A R410A CASSETTE type INVERTER ...
Страница 56: ...7 TROUBLE SHOOTING R410A CASSETTE type INVERTER ...
Страница 91: ...8 APPENDING DATA R410A CASSETTE type INVERTER ...
Страница 110: ...9 INSTALLATION MANUAL R410A CASSETTE type INVERTER ...
Страница 117: ...10 REPLACEMENT PARTS R410A CASSETTE type INVERTER ...
Страница 119: ...Thermistor Heat exchanger temp 2 way valve Liquid 3 way valve Gas 10 02 Thermo Holder Thermistor Outdoor Temp ...
Страница 143: ...2 TOP PANEL removal Remove the 7 mounting screws Remove the TOP PANEL upward FRONT VIEW REAR VIEW 10 26 ...
Страница 158: ...10 41 8 DRAIN PAN removal Remove the DRAIN PAN ASSY DRAIN PAN ASSY ...
Страница 161: ...10 44 11 DRAIN PUMP removal Remove the 2 mounting screws Remove the DRAIN PUMP UNIT DRAIN PUMP UNIT DRAIN HOSE ...
Страница 162: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Apr 2006 Printed in Japan ...