5-18. DRAIN PUMP OPERATION
1. When the compressor starts, the drain pump starts simultaneously.
2. The drain pump operates continuously for 3 minutes after the compressor is turned off.
3. When the compressor stops by the "Indoor heat exchanger de-icing function", the drain pump is turned off in 1 hour
after the compressor stops.
4.When the water level in the drain pan rises up and then the float switch functions:
The compressor, indoor and outdoor fan motor operation are stopped.
Drain pump operates continuously for 3 minutes after the float switch is turned off.
(Almost condensing water may be drained)
5. When the float switch turns ON continuously for 3 min., "FAILURE INDICATION" operates.
6. When the float switch turns OFF within 3 min., the unit starts cooling operation.
1
2
1.When the water level in the drain pan rises up and then the float switch functions:
Drain pump operates continuously for 3 minutes after the float switch is turned off.
(Almost condensing water may be drained)
2. When the float switch turns ON continuously for 3 min., "FAILURE INDICATION" operates.
1
During Cooling / Dry operation
During Heating / Fan / Stop operation
5-19. ENERGY SAVE FUNCTION
1. During Cooling / Dry operation:
The thermostat temperature setting increases by 1 degC as soon as the ENERGY SAVE button is pressed,
and then increases by 1 degC after 1 hour later.
Afterwards, energy consumption is saved by continuing to cool or dry at a thermostat temperature of 2 degC
higher than setting temperature.
2. During Heating operation:
The thermostat temperature setting decreases by 1 degC as soon as the ENERGY SAVE button is pressed,
and then decreases by another 1 degC every 30 minutes.
Afterwards, energy consumption is saved by continuing to heat at a thermostat temperature of 4 degC
lower than setting temperature.
1hour.
1 degC
2
degC
ENERGY
SAVE ON
Setting
temperature
1
degC
2
degC
3
degC
4
degC
30min.
1 hour.
1 hour
30 min.
ENERGY
SAVE ON
Setting
temperature
05-18
Содержание AO*24LMAKL
Страница 5: ...1 SPECIFICATIONS R410A CASSETTE type INVERTER ...
Страница 11: ...2 DIMENSIONS R410A CASSETTE type INVERTER ...
Страница 15: ...3 REFRIGERANT SYSTEM DIAGRAM R410A CASSETTE type INVERTER ...
Страница 19: ...4 CIRCUIT DIAGRAM R410A CASSETTE type INVERTER ...
Страница 25: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A CASSETTE type INVERTER ...
Страница 47: ...6 REFRIGERANT CAUTION R410A R410A CASSETTE type INVERTER ...
Страница 56: ...7 TROUBLE SHOOTING R410A CASSETTE type INVERTER ...
Страница 91: ...8 APPENDING DATA R410A CASSETTE type INVERTER ...
Страница 110: ...9 INSTALLATION MANUAL R410A CASSETTE type INVERTER ...
Страница 117: ...10 REPLACEMENT PARTS R410A CASSETTE type INVERTER ...
Страница 119: ...Thermistor Heat exchanger temp 2 way valve Liquid 3 way valve Gas 10 02 Thermo Holder Thermistor Outdoor Temp ...
Страница 143: ...2 TOP PANEL removal Remove the 7 mounting screws Remove the TOP PANEL upward FRONT VIEW REAR VIEW 10 26 ...
Страница 158: ...10 41 8 DRAIN PAN removal Remove the DRAIN PAN ASSY DRAIN PAN ASSY ...
Страница 161: ...10 44 11 DRAIN PUMP removal Remove the 2 mounting screws Remove the DRAIN PUMP UNIT DRAIN PUMP UNIT DRAIN HOSE ...
Страница 162: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Apr 2006 Printed in Japan ...