5-4. AUTO CHANGEOVER OPERATION
When the air conditioner is set to the AUTO mode by remote control, operation starts in the optimum
mode from among the HEATING, COOLING and MONITORING modes. During operation, the
optimum mode is automatically swiched in accordance with temperature changes. The temperature
can be set between 18°C and 30°C in 1 degC steps.
When operation starts, only the indoor fan is operated for 1 minute. (Air flow mode: S- Lo)
After 1 minute, depends on the room temperature and outdoor unit's operarion mode,
the operation mode is selected in accordance with the table below.
( Table 4 : Operation mode selection table )
When COOLING was selected at , the same operation as COOLING OPERATION is performed.
When HEATING was selected at , the same operation as HEATING OPERATION is performed.
When the compressor was stopped for 6 consecutive minutes by the temperature control function
after the COOLING or HEATING operation mode was selected at above, operation is switched
to MONITORING and the operation mode is selected again.
1
1
2
3
1
4
1
05-04
Room temperature :TR
Operation mode
TR > Ts +2 degC
Ts +2 degC > TR
=
=
Ts +2 degC > TR > Ts -2 degC
Cooling
Monitoring
Heating
Ts : Setting temperature
( Table 4 : Operation mode selection table )
Room
temperature :TR
Room
temperature :TR
Operation
mode
TR > Ts +3.6°F
(2°C)
Ts +3.6°F > TR
(2°C)
=
=
=
Ts +3.6°F > TR > Ts-3.6°F
(2°C) (2°C)
Cooling
Monitoring
Heating
Operation
mode
Room
temperature :TR
Operation
mode
Monitoring
Heating
TR > Ts
=
Monitoring
Ts > TR
Cooling
TR > Ts
Ts > TR
Outdoor unit's
operation mode : Stop
Outdoor unit's
operation mode : Heating
Outdoor unit's
operation mode : Cooling
Ts : Setting temperature
マルチ用
Содержание AO*24LMAKL
Страница 5: ...1 SPECIFICATIONS R410A CASSETTE type INVERTER ...
Страница 11: ...2 DIMENSIONS R410A CASSETTE type INVERTER ...
Страница 15: ...3 REFRIGERANT SYSTEM DIAGRAM R410A CASSETTE type INVERTER ...
Страница 19: ...4 CIRCUIT DIAGRAM R410A CASSETTE type INVERTER ...
Страница 25: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A CASSETTE type INVERTER ...
Страница 47: ...6 REFRIGERANT CAUTION R410A R410A CASSETTE type INVERTER ...
Страница 56: ...7 TROUBLE SHOOTING R410A CASSETTE type INVERTER ...
Страница 91: ...8 APPENDING DATA R410A CASSETTE type INVERTER ...
Страница 110: ...9 INSTALLATION MANUAL R410A CASSETTE type INVERTER ...
Страница 117: ...10 REPLACEMENT PARTS R410A CASSETTE type INVERTER ...
Страница 119: ...Thermistor Heat exchanger temp 2 way valve Liquid 3 way valve Gas 10 02 Thermo Holder Thermistor Outdoor Temp ...
Страница 143: ...2 TOP PANEL removal Remove the 7 mounting screws Remove the TOP PANEL upward FRONT VIEW REAR VIEW 10 26 ...
Страница 158: ...10 41 8 DRAIN PAN removal Remove the DRAIN PAN ASSY DRAIN PAN ASSY ...
Страница 161: ...10 44 11 DRAIN PUMP removal Remove the 2 mounting screws Remove the DRAIN PUMP UNIT DRAIN PUMP UNIT DRAIN HOSE ...
Страница 162: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Apr 2006 Printed in Japan ...