En-7
Installation dimensions
3. 3.
CAUTION
When installing the outdoor unit, pay attention to the following items.
Provide suf
fi
cient installation space, such as transportation route, maintenance space, ventilation space, refriger-
•
ant piping space, and passageways.
Pay attention to the speci
fi
cations of the installation space as shown in the
fi
gure. If the unit is not installed ac-
•
cording to speci
fi
cations, it may cause short circuit or poor performance. The unit may be prone to lapse into non-
operation due to high pressure protection.
Do not place obstructions in the air
fl
ow outlet direction. If there is an obstruction in the outlet direction, install an outlet duct.
•
When there is a wall in front of the unit, provide a space of 500mm or more as maintenance space.
•
When there is a wall at the left side of the unit, provide a space of 30mm or more as maintenance space.
•
An outdoor temperature of 35 degrees in air-conditioned operation is assumed for the installation space in this item. If the outdoor
•
temperature exceeds 35 degrees and the outdoor unit is operating at a load exceeding its rated ability, provide a larger inlet space.
If you are installing more outdoor units than indicated here, please ensure suf
fi
cient space or consult your distrib-
•
uting agent as it may affect the performance due to short circuit and other problems.
When install near by limited height wall
3. 3. 1.
Single and multiple installations
(1)
There are no restrictions on the height of the side wall.
•
Provide installation spaces L1 and L2 in accordance with the table below according to the wall height (front side, rear
•
side) conditions.
Provide installation spaces other than L1 and L2 in accordance with the conditions shown in the
fi
gure below.
•
Ventilation resistance can be ignorable when the distance from a wall or product, etc. is larger than 2m.
•
Wall height condition
Necessary installation space
When H1 is 1500 (mm) or less
L1
>
=
500 (mm)
When H1 is 1500 (mm) or more
L1
>
=
500+h1÷2 (mm)
When H2 is 500 (mm) or less
L2
>
=
100 (mm)
When H2 is 500 (mm) or more
L2
>
=
100+h2÷2 (mm)
1
Fig.
J
.
.
J
*
*
<Side view>
<Front>
<Rear>
Wall
Wall
2 Single installation
Fig.
.
.
30mm or more 10mm or more
<Top view>
<Front>
<Rear>
3 Multiple installations
Fig.
.
.
<Top view>
30mm or
more
20mm or
more
10mm or
more
<Front>
<Rear>
20mm or
more
Concentrated installation
(2)
Provide installation spaces L3, L4, and L5 in accordance with the table below according to the wall height (front
•
side, rear side) conditions.
Provide installation spaces other than L3, L4, and L5 in accordance with the conditions shown in the
fi
gure below.
•
Ventilation resistance can be ignorable when the distance from a wall or product, etc. is larger than 2m.
•
Wall height condition
Necessary installation space
When H3 is 1500 (mm) or less
L3
>
=
500 (mm)
When H3 is 1500 (mm) or more
L3
>
=
500+h3÷2 (mm)
When H4 is 500 (mm) or less
L4
>
=
200 (mm)
When H4 is 500 (mm) or more
L4
>
=
200+h4÷2 (mm)
When H5 is 500 (mm) or less
L5
>
=
200 (mm)
When H5 is 500 (mm) or more
L5
>
=
200+h5÷2 (mm)