![Fujitsu AJ*108LALH Series Скачать руководство пользователя страница 20](http://html.mh-extra.com/html/fujitsu/aj-108lalh-series/aj-108lalh-series_installation-manual_118219020.webp)
En-20
Selecting power supply cable and breaker
6. 3.
CAUTION
Obtain the distribution network operator's agreement about the power capacity of the power supply system,
•
speci
fi
cation of the cable and the harmonic current, and etc. when you connect the outdoor unit with the power
supply.
Regulation of wire size and circuit breaker differs from each locality, please refer in accordance with local rules.
•
Refer to the table for the wiring and breaker speci
fi
cations of each installation condition.
Selecting power supply cable and breaker when connecting 1 outdoor unit
(1)
MODEL
Breaker (Time delay fuse or circuit capacity)
Outdoor unit power supply cable
Capacity (A)
Leakage
current
Power supply
cable (mm
2
)
Ground wire (mm
2
)
Critical wiring
length (m)
AJ A72LALH
30
100mA
0.1sec or less
4
4
30
AJ A90LALH
30
4
4
30
AJ 108LALH
50
10
6
42
AJ 126LALH
50
10
6
42
AJ 144LALH
50
10
6
42
These values are recommended data.
1)
Speci
fi
cation: Use conformed cord with Type 60245 IEC66
2)
Max. wire length: Set a length so that the voltage drop is less than 2%.
3)
Increase the wire diameter when the wire length is long.
In case of connected outdoor unit (breaker: earth leakage breaker)
Fig.
Selecting main breaker and main pow
(2)
er supply cable when connecting multiple outdoor units
Main breaker: Main breaker
>
=
Total Sub breaker (
Refer to the table in item (1) for the sub breaker capacity)
In case of connected 3 outdoor unit (breaker: earth leakage breaker)
Fig.
OK
Transmission cable
230 V 1ø 50 Hz
Sub
breaker
Outdoor unit Power supply cable
Remote controller cable
400 V 3ø
50 Hz
Breaker
Indoor unit
Power supply cable
Main breaker
Example of bad breaker wiring
(3)
No Good
Transmission cable
230 V 1ø 50 Hz
400 V 3ø 50 Hz
Breaker
Indoor unit
Power supply cable
Remote controller cable
Outdoor unit
Power supply cable
No Good: crossover power
supply wiring prohibited
Breaker
No Good: install a breaker
for each outdoor unit
OK
Transmission cable
Remote controller cable
Breaker
400 V 3ø 50 Hz
Breaker
230 V 1ø 50 Hz
Outdoor unit
Power supply cable
Indoor unit
Power supply cable
9378945029-03_IM_EN.indb 20
9378945029-03_IM_EN.indb 20
2011-9-20 16:25:54
2011-9-20 16:25:54