![Fujitsu AJ*108LALH Series Скачать руководство пользователя страница 28](http://html.mh-extra.com/html/fujitsu/aj-108lalh-series/aj-108lalh-series_installation-manual_118219028.webp)
En-28
Number o
(3) f
outdoor
units
installed
The number of outdoor units installed in 1 refrigerant system must be set.
Set for all outdoor units.
SET5
Number of out-
door units
Remarks
1
2
OFF
OFF
1
(Factory setting)
OFF
ON
2
-
ON
OFF
3
-
ON
ON
-
Forbidden
Terminating resistor setting
7. 2. 3.
Caution
Be sure to set the terminal resistor according to speci
fi
cations.
Set the terminal resistor for every network segment (NS).
If terminal resistor is set in multiple devices, the overall communication system may be damaged.
If terminal resistor is not set in a device, abnormal communication may occur.
Be sure to
•
set 1 terminal resistor in a network segment. You can set the terminal resistor at the outdoor unit or
signal ampli
fi
er.
When settin
•
g the terminal resistor of a signal ampli
fi
er, refer to the installation manual of the signal ampli
fi
er.
When settin
• g
multiple
terminal
resistors,
take note of the following items.
How many network segments are there in a VRF system?
①
Where will you set the terminal resistors in a network segment? (Condition for 1 segment: Total number of
②
outdoor and indoor units and signal ampli
fi
ers is less than 64, or the total length of the transmission cable is
less than 500m)
How many outdoor units are connected to 1 refrigerant system?
③
Con
fi
gure the setting (DIP switch SET5) of the terminal resistor of the outdoor units as shown below from con-
ditions
1
to
3
.
SET5
Terminal resistor
Remarks
4
OFF
Disable
(Factory setting)
ON
Enable
-
Figure: Terminal resistor setting
NS2 (Network segment 2)
NS3 (Network segment 3)
NS4 (Network segment 4)
NS1 (Network segment 1)
(Set terminal resistor at outdoor units)
Master unit
Master unit
Master unit
Refrigerant system1
Refrigerant system2
Refrigerant system3
Terminal resistor: off
Terminal resistor: on
Terminal resister: on
About the setting of terminal resistor
Outdoor unit (Master unit)
Install
Do not install
:on