En-42
Checklist
9. 3.
Check description
Check method
Criteria
1
High and low pressure values are normal.
Check it with a pressure gauge.
Cooling: low pressure approx. 0.8 MPa
Heating: high pressure approx. 3.0 MPa
2
Drain water is discharged smoothly through
the drain hose.
Check it by pouring water.
―
3
Indoor and outdoor unit fans are operating.
Check them visually.
―
4
Compressor operates after the indoor unit operates.
Check the operating sound.
―
5
Difference between inlet and outlet tempera-
tures is normal.
Measure the inlet and outlet tem-
peratures.
Temperature difference 10 degrees
6
Error is not displayed
Check the 7 segment LED display
Error blinking or no error code display
LED Display
10.
You can determine the operating status by the lighting up and blinking of the 7 segment LED display.
Check the status using the table below.
Normal operation mode
10. 1.
Mode
Code
Description
Operation
C L
Cooling
H
t
Heating
o
r During oil recovery operation
d F During defrosting operation
P C During power saving operation
L n During low noise operation
S n During setting of snowfall mode