2-5 SPECIAL OPERATION
2-5-1 Oil Recovery Operation
(1) Purpose of the operation
The amount of refrigerant lubricant oil which has been transported to the indoor units
and the connection pipe with the refrigerant will become large as the operation time of compressor increases.
It is necessary to recover the oil back into the outdoor unit for a certain time interval
in order to prevent compressors from damaging due to lack of lubrication oil.
During the oil recovery operation, appears on the display of wired and central remote controller,
and appears on the simple remote controller.
The operation indicators (LED) of the indoor units flash slowly.
Others
02-10
Simple oil recovery operation
< Oil recovery from the gas main pipe > (Only cooling mode)
<
Start condition >
< Operation >
Indoor unit : Expansion valve of operating indoor unit gradually opened
< Start condition >
< End condition >
30 seconds have elapsed since the start and "suction temperature - low pressure saturation temperature 5deg"
at all outdoor units or 6 minutes have elapsed since the start.
< Operation >
COMPRESSOR: Performed by all INV compressors and the constant speed compressors operating up until now
INV speed varies depending on the operation state.
EEV Opening (Indoor/Outdoor unit): Controlled pulse (as normal operation mode).
FAN speed (Indoor/Outdoor unit) : Controlled fan speed (as normal operation mode).
< Start condition >
< End condition >
After 4 minutes have elapsed
< Operation >
COMPRESSOR: Performed by all INV compressors and the constant speed compressors operating up until now
INV speed varies depending on the operation state.
EEV Opening (Indoor/Outdoor unit) : Controlled pulse (as normal operation mode)
FAN speed (Indoor/Outdoor unit) : Controlled fan speed (as normal operation mode)
Suction temperature low pressure saturation
temperature
10°C continues for 30 minutes
Cooling oil recovery operation
Compressor accumulated operation time since last cooling oil recovery operation exceeds 3 hours (first time : 1hour)
Heating oil recovery operation
Compressor accumulated operation time since the last heating oil recovery exceeds 8 hours (first time : 1hour)
< End condition >
Suction temperature low pressure saturation
temperature
7°C
Outdoor unit : Normal cooling operation
Содержание AIRSTAGE V-II
Страница 2: ......
Страница 6: ...1 TEST RUN ...
Страница 7: ......
Страница 22: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Страница 23: ......
Страница 39: ...3 INDOOR UNIT OPERATION ...
Страница 40: ......
Страница 59: ...4 TROUBLE SHOOTING ...
Страница 60: ......
Страница 187: ...5 APPENDING DATA UNIT ...
Страница 188: ......
Страница 193: ...MODELS AUXB07 AUXB09 AUXB12 AUXB14 AUXB18 AUXB24 05 05 5 2 WIRING DIAGRAM 5 2 1 Indoor Unit ...
Страница 194: ...MODELS AUXD18 AUXD24 AUXA30 AUXA36 AUXA45 AUXA54 05 06 ...
Страница 195: ...MODELS ARXB07 ARXB09 ARXB12 ARXB14 ARXB18 05 07 ...
Страница 196: ...MODEL ARXB24 MODELS ARXB30 ARXB36 05 08 ...
Страница 197: ...MODEL ARXB45 05 09 ...
Страница 198: ...MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 05 10 ...
Страница 199: ...MODELS ARXC36 ARXC45 ARXC60 MODELS ARXC72 ARXC90 05 11 ...
Страница 200: ...MODELS ARXD07 ARXD09 ARXD12 ARXD14 ARXD18 ARXD24 05 11 1 ...
Страница 201: ...MODELS AB A12 AB A14 AB A18 AB A24 05 12 ...
Страница 202: ...MODELS AB A12LBTH AB A14LBTH 05 12 1 AB A18LBTH AB A24LBTH ...
Страница 203: ...05 13 MODELS AB A30 AB A36 AB A45 AB A54 ...
Страница 204: ...05 13 1 MODELS AB A30LBTH AB A36LBTH AB A45LBTH AB A54LBTH ...
Страница 205: ...MODELS AS A07 AS A09 AS A12 AS A14 05 14 ...
Страница 206: ...MODELS AS E07 AS E09 AS E12 AS E14 05 15 ...
Страница 207: ...MODELS AS A18 AS A24 AS A30 05 16 ...
Страница 208: ...05 16 1 MODELS AS A18LACH AS A24LACH AS A30LACH ...
Страница 216: ...6 DISASSEMBLY PROCESS ...
Страница 217: ......
Страница 218: ......
Страница 219: ......
Страница 220: ......
Страница 221: ......
Страница 222: ......
Страница 223: ......
Страница 225: ......
Страница 226: ......