If the amount of recovered refrigerant is available that was pulled out of outdoor unit
which compressor was replaced.
(When the refrigerant is recovered by refrigerant recovery machine, and its weight is measured.)
If the amount of recovered refrigerant from outdoor unit that compressor was replaced is not sure.
>>> Once recover all units' refrigerant, and then recharge the calculated amount of
refrigerant again after vacuuming.
>>> Perform vacuuming of repaired outdoor unit thoroughly ,
and add the refrigerant with the recovered amount.
4-4-2 Work procedure after the backup operation
1. Refrigerant shortage at the backup operation
1. On Cooling operation
<How to judge, when refrigerant is deficient>
Refrigerant shortage is judged by the information from "Service tool" during backup operation.
<How to respond, when refrigerant is deficient>
When excessive refrigerant accumulates in the defective outdoor unit during the backup operation,
it becomes capacity shortage by refrigerant shortage.
2. Refrigerant charging after the compressor replacement.
When the refrigerant leaks at the time of replacing the defective compressor,
charge the refrigerant as follows depending on the situation.
Running indoor unit's EEV is fully open condition.
>>> It displays corresponding indoor unit's EEV on the chart at the bottom of the monitor.
If there is no sign of closing the EEV from fully opened condition.
It often creates "Low pressure protection stop" at start up or after oil recovery operation.
>>> When LPS < 0.1MPa at start up, the compressor stops.
2. On Heating operation
EEV1 of outdoor unit is open at 500 pulse. (full admission).
Suction superheat is too high.
>>> When both TH5 TH4 and TH4 TH3.
Reuse the refrigerant of the broken master unit.
Connect the high pressure service port of the broken master unit and the low pressure service port of the
substitutional master unit by charging hose, placing the valve on the way.
>>> Refrigerant release from the heat exchanger of the broken master unit.
(Refrigerant is removed until refrigerant shortage is resolved)
Not available to reuse.
>>> New refrigerant is encapsulated.
* substitutional master unit, and encapsulating amount is recorded.
It often creates "Low pressure protection stop" at start up or after oil recovery operation.
>>> When LPS < 0.1MPa at start up, the compressor stops.
LPS : Low pressure sensor detection value
EEV1 : Expansion valve #1
TH3 : Outdoor thermistor detection value
TH4 : Suction thermistor detection value
TH5 : Outdoor heat EX. temperature sensor detection value
The meaning of the sign
Broken
master unit
Substitutional
master unit
Slave
unit #1
04-97
Содержание AIRSTAGE V-II
Страница 2: ......
Страница 6: ...1 TEST RUN ...
Страница 7: ......
Страница 22: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Страница 23: ......
Страница 39: ...3 INDOOR UNIT OPERATION ...
Страница 40: ......
Страница 59: ...4 TROUBLE SHOOTING ...
Страница 60: ......
Страница 187: ...5 APPENDING DATA UNIT ...
Страница 188: ......
Страница 193: ...MODELS AUXB07 AUXB09 AUXB12 AUXB14 AUXB18 AUXB24 05 05 5 2 WIRING DIAGRAM 5 2 1 Indoor Unit ...
Страница 194: ...MODELS AUXD18 AUXD24 AUXA30 AUXA36 AUXA45 AUXA54 05 06 ...
Страница 195: ...MODELS ARXB07 ARXB09 ARXB12 ARXB14 ARXB18 05 07 ...
Страница 196: ...MODEL ARXB24 MODELS ARXB30 ARXB36 05 08 ...
Страница 197: ...MODEL ARXB45 05 09 ...
Страница 198: ...MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 05 10 ...
Страница 199: ...MODELS ARXC36 ARXC45 ARXC60 MODELS ARXC72 ARXC90 05 11 ...
Страница 200: ...MODELS ARXD07 ARXD09 ARXD12 ARXD14 ARXD18 ARXD24 05 11 1 ...
Страница 201: ...MODELS AB A12 AB A14 AB A18 AB A24 05 12 ...
Страница 202: ...MODELS AB A12LBTH AB A14LBTH 05 12 1 AB A18LBTH AB A24LBTH ...
Страница 203: ...05 13 MODELS AB A30 AB A36 AB A45 AB A54 ...
Страница 204: ...05 13 1 MODELS AB A30LBTH AB A36LBTH AB A45LBTH AB A54LBTH ...
Страница 205: ...MODELS AS A07 AS A09 AS A12 AS A14 05 14 ...
Страница 206: ...MODELS AS E07 AS E09 AS E12 AS E14 05 15 ...
Страница 207: ...MODELS AS A18 AS A24 AS A30 05 16 ...
Страница 208: ...05 16 1 MODELS AS A18LACH AS A24LACH AS A30LACH ...
Страница 216: ...6 DISASSEMBLY PROCESS ...
Страница 217: ......
Страница 218: ......
Страница 219: ......
Страница 220: ......
Страница 221: ......
Страница 222: ......
Страница 223: ......
Страница 225: ......
Страница 226: ......