2-6 PROTECTIVE FUNCTION
02-13
2-6-1 Protective Function List
Protective Function
Detect Parts
Operating Condition
Operation
Discharge Temp
Protection 1
Discharge Temp
Thermistor
Discharge Temp
Protection 2
Discharge Temp
Thermistor
Discharge Temp
Protection 3
Discharge Temp
Thermistor
High Pressure
Protection 1
High Pressure
Sensor
High Pressure
Protection 4
High Pressure
Sensor
COOL HEAT
<Starting conditions>
3 minutes have elapsed since the start of operation and
(discharge temperature 100°C or suction SH 10°C accumulated time
30 minutes)
<Reset conditions>
Discharge temperature 95°C and suction 7°C
EEV of operating indoor unit gradually opened
<Starting conditions>
Cooling: Discharge temperature 95°C
Heating: Discharge temperature 102°C
<Reset conditions>
Discharge temperature 90°C
Discharge temperature 97°C
EEV2 + 30pls/30 secs
<Starting conditions>
Discharge temperature 107°C
<Reset conditions>
Discharge temperature 105°C
Outdoor unit rotation execution
* After rotation has been executed once;
it is executed every 15 minutes.
Discharge Temp
Protection 4
Discharge Temp
Thermistor
< starting condition>
Discharge temperature 105°C
<Pattern reset condition>
Discharge temperature 100°C
INV compressor speed -6rps every 30 secs
Speed rise prohibited,
when discharge temperature becomes lower
than 105 , prohibit the rotational speed rise
of the compressor.
Discharge Temp
Protection 5
Discharge Temp
Thermistor
<Starting conditions>
Discharge temperature 95°C and EEV1=500pls
<Reset conditions>
2 minutes have elapsed and
(discharge temperature 90°C or EEV1 400pls)
Expansion valve of stopped indoor unit gradually
opened
(upper limit 200pls)
Discharge Temp
Protection 6
Discharge Temp
Thermistor
<Starting conditions>
Discharge temperature 90°C
<Reset conditions>
Discharge temperature 90°C
EEV1: Forcefully OPEN
Discharge Temp
Protection Stop
Discharge Temp
Thermistor
<Pattern starting condition>
Discharge temperature fixed value (INV: 110°C, constant speed: 115°C)
<Pattern reset condition>
3 minutes have elapsed and discharge temperature 80°C
Corresponding compressor stopped
<Pattern starting condition>
Pattern generated 2 times within 40 minutes
<Pattern reset condition>
Error reset (push button SW) executed after power turned on again
Corresponding compressor stopped
(permanent stop)
Error display
<Starting conditions>
High-pressure 3.94MPa
<Reset conditions>
Fixed time has elapsed and high-pressure 3.70MPa
* Fixed time when SV1: ON 180 secs, when SV2: ON 30 secs
At INV independent operation: SV2 ON
At constant speed independent operation:
SV1 ON
High Pressure
Protection 2
High Pressure
Sensor
<Starting conditions>
High-pressure 3.60MPa
<Reset conditions>
3 minutes have elapsed and high-pressure 2.80MPa
At INV independent operation: SV2 ON
When still insufficient: SV1 ON + SV2 ON
At INV + constant speed operation, constant
speed independent operation: SV1 ON
High Pressure
Protection 3
High Pressure
Sensor
<Starting conditions>
Fixed time has elapsed and high-pressure 3.50MPa
(* Fixed time at start of operation: 10 secs, after operation execution: 20 secs)
<Reset conditions>
Operation (fan speed 1 step increase) complete
Fan speed 1 step increase
<Pattern starting condition>
High-pressure 3.30MPa
<Pattern starting condition>
High-pressure 3.50MPa
<Pattern reset condition>
High-pressure 3.3MPa
<Pattern reset condition>
High-pressure 3.5MPa
Fan speed lowered/every 30 secs
Fan lowest speed (300rpm) fixed
DISPLAY
P1
EA11
(INV)
EA21
(CONST)
High Pressure
Protection 5
High Pressure
Sensor
Abnormal High
Pressure Protection
Control
High Pressure
Sensor
<Starting conditions>
High-pressure 3.20MPa
Compressor capacity lowered/every 15 secs
<Pattern starting condition>
High-pressure 3.78MPa
<Pattern reset condition>
After 25 seconds have elapsed and high-pressure 3.70MPa
Compressor capacity rise prohibited
<Reset conditions>
High-pressure 3.20MPa
<Pattern starting condition>
High-pressure 3.90MPa
<Pattern reset condition>
After 25 seconds have elapsed and high-pressure 3.78MPa
Compressor capacity lowered every 30 secs
Содержание AIRSTAGE V-II
Страница 2: ......
Страница 6: ...1 TEST RUN ...
Страница 7: ......
Страница 22: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Страница 23: ......
Страница 39: ...3 INDOOR UNIT OPERATION ...
Страница 40: ......
Страница 59: ...4 TROUBLE SHOOTING ...
Страница 60: ......
Страница 187: ...5 APPENDING DATA UNIT ...
Страница 188: ......
Страница 193: ...MODELS AUXB07 AUXB09 AUXB12 AUXB14 AUXB18 AUXB24 05 05 5 2 WIRING DIAGRAM 5 2 1 Indoor Unit ...
Страница 194: ...MODELS AUXD18 AUXD24 AUXA30 AUXA36 AUXA45 AUXA54 05 06 ...
Страница 195: ...MODELS ARXB07 ARXB09 ARXB12 ARXB14 ARXB18 05 07 ...
Страница 196: ...MODEL ARXB24 MODELS ARXB30 ARXB36 05 08 ...
Страница 197: ...MODEL ARXB45 05 09 ...
Страница 198: ...MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 05 10 ...
Страница 199: ...MODELS ARXC36 ARXC45 ARXC60 MODELS ARXC72 ARXC90 05 11 ...
Страница 200: ...MODELS ARXD07 ARXD09 ARXD12 ARXD14 ARXD18 ARXD24 05 11 1 ...
Страница 201: ...MODELS AB A12 AB A14 AB A18 AB A24 05 12 ...
Страница 202: ...MODELS AB A12LBTH AB A14LBTH 05 12 1 AB A18LBTH AB A24LBTH ...
Страница 203: ...05 13 MODELS AB A30 AB A36 AB A45 AB A54 ...
Страница 204: ...05 13 1 MODELS AB A30LBTH AB A36LBTH AB A45LBTH AB A54LBTH ...
Страница 205: ...MODELS AS A07 AS A09 AS A12 AS A14 05 14 ...
Страница 206: ...MODELS AS E07 AS E09 AS E12 AS E14 05 15 ...
Страница 207: ...MODELS AS A18 AS A24 AS A30 05 16 ...
Страница 208: ...05 16 1 MODELS AS A18LACH AS A24LACH AS A30LACH ...
Страница 216: ...6 DISASSEMBLY PROCESS ...
Страница 217: ......
Страница 218: ......
Страница 219: ......
Страница 220: ......
Страница 221: ......
Страница 222: ......
Страница 223: ......
Страница 225: ......
Страница 226: ......