02-14
Protective Function Detect Parts
Operating Condition
Operation
Low Pressure
Protection 4
Low Pressure
Sensor
COOL HEAT
High Pressure
Protection Stop 1
High Pressure
Sensor
<Pattern starting condition>
High-pressure 4.00MPa
<Pattern reset condition>
5 minutes have elapsed and high-pressure 3.50MPa
All compressors in outdoor unit stopped
<Pattern starting condition>
Pattern generated 3 times within 60 minutes.
<Pattern reset condition>
10 minutes have elapsed and high-pressure 3.50MPa
Pressure Switch
<Pattern starting condition>
Pressure SW operated (Operated by high-pressure 4.20MPa)
<Pattern reset condition>
5 minutes have elapsed and pressure SW operation reset
(Reset by high-pressure 3.2MPa)
Corresponding compressor stopped
High Pressure
Protection Stop 2
<Pattern starting condition>
Pattern generated 3 times within 60 minutes.
<Pattern reset condition>
10 minutes have elapsed and pressure SW operation reset
(Reset by high-pressure 3.2MPa)
Corresponding compressor stopped
Error display
<Starting conditions>
Low-pressure 0.20MPa
<Reset conditions>
5 minutes have elapsed and low-pressure 0.30MPa
SV1 ON
Low Pressure
Protection 1
Low Pressure
Sensor
<Starting conditions>
Low-pressure 0.10MPa
<Reset conditions>
3 minutes have elapsed and low-pressure 0.17MPa
SV1 ON
SV1 ON
<Starting conditions>
One operating outdoor unit and INV compressor operating at 30rps and
low-pressure 0.65MPa
<Reset conditions>
5 minutes have elapsed and INV compressor operating at 40rps or faster
<Starting conditions>
3 minutes have elapsed and low-pressure 0.18MPa
<Reset conditions>
3 minutes have elapsed and low-pressure 0.22MPa
EEV of stopped indoor unit opened quickly
(450pls)
Abnormal Low
Pressure Protection
Control
Low Pressure
Sensor
<starting condition>
Low-pressure 0.16MPa
Compressor capacity lowered every 180 secs,
Low Pressure
Protection Stop
Low Pressure
Sensor
<Pattern starting condition>
Low-pressure 0.05MPa or low-pressure 0.10MPa continues for 10 mins
<Pattern reset condition>
3 minutes have elapsed and low-pressure 0.17MPa
<Pattern starting condition>
Pattern generated 5 times within 180 minutes.
<Pattern reset condition>
Error reset (push button SW) executed after power turned on again.
All compressors in outdoor unit stopped
(permanent stop)
Error display
All compressors in outdoor unit stopped
Error display
Low Pressure
Sensor
Low Pressure
Protection 2
Low Pressure
Protection 3
Low Pressure
Sensor
<reset condition>
3 minutes have elapsed and
low-pressure 0.18MPa
All compressors in outdoor unit stopped
DISPLAY
Compressor Temp
Protection Stop
Compressor
Temp
Thermistor
<Pattern starting condition>
Compressor temperature fixed value (INV: 112°C, Constant speed: 120°C)
<Pattern reset condition>
3 minutes have elapsed and discharge temperature 80°C
Corresponding compressor stopped
Corresponding compressor stopped
(permanent stop)
Error display
<Pattern starting condition>
Pattern generated 2 times within 40 minutes
<Pattern reset condition>
Error reset (push button SW) executed after power turned on again
P2
EA41
EA31
(INV)
EA32
(CONST)
EA42
(INV)
EA43
(CONST)
P4
P3
EA51
when the Low-pressure becomes more than
0.17MPa, prohibit compressor capacity rise.
P2
Содержание AIRSTAGE V-II
Страница 2: ......
Страница 6: ...1 TEST RUN ...
Страница 7: ......
Страница 22: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Страница 23: ......
Страница 39: ...3 INDOOR UNIT OPERATION ...
Страница 40: ......
Страница 59: ...4 TROUBLE SHOOTING ...
Страница 60: ......
Страница 187: ...5 APPENDING DATA UNIT ...
Страница 188: ......
Страница 193: ...MODELS AUXB07 AUXB09 AUXB12 AUXB14 AUXB18 AUXB24 05 05 5 2 WIRING DIAGRAM 5 2 1 Indoor Unit ...
Страница 194: ...MODELS AUXD18 AUXD24 AUXA30 AUXA36 AUXA45 AUXA54 05 06 ...
Страница 195: ...MODELS ARXB07 ARXB09 ARXB12 ARXB14 ARXB18 05 07 ...
Страница 196: ...MODEL ARXB24 MODELS ARXB30 ARXB36 05 08 ...
Страница 197: ...MODEL ARXB45 05 09 ...
Страница 198: ...MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 05 10 ...
Страница 199: ...MODELS ARXC36 ARXC45 ARXC60 MODELS ARXC72 ARXC90 05 11 ...
Страница 200: ...MODELS ARXD07 ARXD09 ARXD12 ARXD14 ARXD18 ARXD24 05 11 1 ...
Страница 201: ...MODELS AB A12 AB A14 AB A18 AB A24 05 12 ...
Страница 202: ...MODELS AB A12LBTH AB A14LBTH 05 12 1 AB A18LBTH AB A24LBTH ...
Страница 203: ...05 13 MODELS AB A30 AB A36 AB A45 AB A54 ...
Страница 204: ...05 13 1 MODELS AB A30LBTH AB A36LBTH AB A45LBTH AB A54LBTH ...
Страница 205: ...MODELS AS A07 AS A09 AS A12 AS A14 05 14 ...
Страница 206: ...MODELS AS E07 AS E09 AS E12 AS E14 05 15 ...
Страница 207: ...MODELS AS A18 AS A24 AS A30 05 16 ...
Страница 208: ...05 16 1 MODELS AS A18LACH AS A24LACH AS A30LACH ...
Страница 216: ...6 DISASSEMBLY PROCESS ...
Страница 217: ......
Страница 218: ......
Страница 219: ......
Страница 220: ......
Страница 221: ......
Страница 222: ......
Страница 223: ......
Страница 225: ......
Страница 226: ......