2-4. SELECTION OF PIPE HEAT INSULATING MATERIAL
●
Always insulate the refrigerant pipe to prevent condensation and water droplets by the
refrigerant pipe.
●
Decide the thickness of the heat insulating material by referring to the recommended
minimum thickness in Table 1. (For installation condition T=32°C(DB),humidity≤70%,
humidity≤75%, humidity≤80%, humidity≤85%)
● When the outdoor unit is installed in a higher position than the indoor unit, fill the connecting
part gap with putty, etc. to prevent the dew condensation water of the valve of the outdoor
unit from flowing to the indoors from the gap between the pipe and the heat insulating
material.
● Liquid pipe and gas pipe should be completely insulated with same specification.
●
In case not to insulate and not to seal refrigerant pipe completely, it will become the cause of
water leak.
●
Table1 Size of refrigerant pipe and recommended minimum thickness of heat insulating
material
(In case a heat insulating material which thermal conductivity is equal to or less than 0.040 W/(m·k)
is used. )
Recommended minimum thickness for heat
insulating material (mm)
Relative humidity
≤70%
≤75%
≤80%
≤85%
Refrigerant
pipe
Outside
diameter mm
(in.)
6.35 (1/4")
8
10
13
17
9.52 (3/8")
9
11
14
18
12.70 (1/2")
10
12
15
19
15.88 (5/8")
10
12
16
20
19.05 (3/4")
10
13
16
21
22.22 (7/8")
11
13
17
22
28.58 (1-1/8")
11
14
18
23
● When an ambient temperature and relative humidity exceed 32°C (DB)and 85% respectively,
please strengthen heat insulation of refrigerant pipe. If necessary put a heat insulation on
indoor unit casing. When not strengthening heat insulation of refrigerant pipe, the surface
of the heat insulation may be dewed.
●
Since gas pipe becomes high temperature at heating operation for heatpump type, please
select the heat insulating material which heat-resistant temperature is 120°C or more.
Gas pipe
Gas pipe
Connection cable
Finishing tape
Heat insulation
Heat insulation
Liquid pipe
Liquid pipe
●
Make sure that pipe is covered completely by the heat insulation,not expoding to air.
Inadequate heat insulation may cause condensation.
● Do not cover heat insulation gas and liquid pipes together as above figure. It may cause
condensation and capacity drop by heat loss.
- (06 - 20) -
SY
ST
EM
DE
SIGN
SY
ST
EM
DE
SIGN
Содержание AB* A12GATH
Страница 1: ...DESIGN TECHNICAL MANUAL ...
Страница 3: ...1 GENERAL INFORMATION DTV_J3LE050E_03 CHAPTER01 2017 10 31 ...
Страница 20: ...2 MODEL SELECTION DTV_J3LE050E_03 CHAPTER02 2017 10 31 ...
Страница 115: ...3 OUTDOOR UNITS DTV_J3LE050E_02 CHAPTER03 2017 07 21 ...
Страница 119: ... Unit mm Detail B Detail A Detail C 03 03 OUTDOOR UNITS OUTDOOR UNITS ...
Страница 128: ...5 WIRING DIAGRAM MODELS AJ 072LELAH AJ 090LELAH 03 12 OUTDOOR UNITS OUTDOOR UNITS ...
Страница 129: ... MODEL AJ 108LELAH 03 13 OUTDOOR UNITS OUTDOOR UNITS ...
Страница 133: ... SOUND LEVEL CHECK POINT Microphone Airflow 1 m 03 17 OUTDOOR UNITS OUTDOOR UNITS ...
Страница 136: ...4 INDOOR UNITS DTV_VR2E018E_14 CHAPTER04 2017 10 31 ...
Страница 216: ... Unit mm INSTALLATION PLACE 04 77 INDOOR UNITS INDOOR UNITS ...
Страница 231: ...4 7 MEDIUM STATIC PRESSURE DUCT TYPE MODELS ARXA24GBLH ARXA30GBLH ARXA36GBLH ARXA45GBLH 04 92 INDOOR UNITS INDOOR UNITS ...
Страница 232: ...4 8 HIGH STATIC PRESSURE DUCT TYPE MODEL ARXC36GBTH MODELS ARXC45GATH ARXC60GATH 04 93 INDOOR UNITS INDOOR UNITS ...
Страница 233: ... MODELS ARXC72GBTH ARXC90GBTH ARXC96GATH 04 94 INDOOR UNITS INDOOR UNITS ...
Страница 234: ...4 9 LARGE AIRFLOW DUCT TYPE MODEL ARXN018GLBH 04 95 INDOOR UNITS INDOOR UNITS ...
Страница 235: ... MODELS ARXN024GTBH ARXN030GTBH 04 96 INDOOR UNITS INDOOR UNITS ...
Страница 236: ... MODELS ARXN18GATH ARXN24GATH ARXN30GATH ARXN34GATH ARXN36GATH ARXN45GATH 04 97 INDOOR UNITS INDOOR UNITS ...
Страница 237: ...4 10 FLOOR CEILING TYPE MODELS AB A12GATH AB A14GATH AB A18GATH AB A24GATH 04 98 INDOOR UNITS INDOOR UNITS ...
Страница 238: ...4 11 CEILING TYPE MODELS AB A30GATH AB A36GATH AB A45GATH AB A54GATH 04 99 INDOOR UNITS INDOOR UNITS ...
Страница 241: ...4 14 WALL MOUNTED TYPE MODELS AS A004GTAH AS A007GTAH AS A009GTAH 04 102 INDOOR UNITS INDOOR UNITS ...
Страница 242: ... MODELS AS A012GCAH AS A014GCAH 04 103 INDOOR UNITS INDOOR UNITS ...
Страница 243: ... MODELS AS A04GACH AS A07GACH AS A09GACH AS A12GACH AS A14GACH 04 104 INDOOR UNITS INDOOR UNITS ...
Страница 244: ... MODELS AS A18GBCH AS A24GBCH AS A18GACH AS A24GACH AS A30GACH 04 105 INDOOR UNITS INDOOR UNITS ...
Страница 245: ... MODELS AS A030GTAH AS A034GTAH 04 106 INDOOR UNITS INDOOR UNITS ...
Страница 246: ...4 15 WALL MOUNTED TYPE EEV external model MODELS AS E004GTAH AS E007GTAH AS E009GTAH 04 107 INDOOR UNITS INDOOR UNITS ...
Страница 247: ... MODELS AS E012GCAH AS E014GCAH 04 108 INDOOR UNITS INDOOR UNITS ...
Страница 248: ... MODELS AS E04GACH AS E07GACH AS E09GACH AS E12GACH AS E14GACH 04 109 INDOOR UNITS INDOOR UNITS ...
Страница 466: ...5 CONTROL SYSTEM DTV_VR2E018E_12 CHAPTER05 2017 10 31 ...
Страница 690: ...6 SYSTEM DESIGN DTV_J3LE050E_03 CHAPTER06 2017 10 31 ...
Страница 779: ...7 FUNCTION SETTING DTV_VR2E018E_14 CHAPTER07 2017 10 31 ...
Страница 975: ...8 EXTERNAL INPUT OUTPUT DTV_VR2E018E_11 CHAPTER08 2017 10 31 ...
Страница 1016: ...9 NOTES DTV_VR2E018E_11 CHAPTER09 2017 07 21 ...
Страница 1034: ...10 OPTIONAL PARTS DTV_VR2E018E_13 CHAPTER10 2017 10 31 ...
Страница 1046: ... 10 11 OPTIONAL PARTS OPTIONAL PARTS z zDimensions Liquid pipe Discharge gas pipe Suction gas pipe 130 15 REDUCER 95 15 REDUCER ...
Страница 1058: ... 10 23 OPTIONAL PARTS OPTIONAL PARTS z zDimensions Liquid pipe Dis charge gas pipe Suction gas pipe ...
Страница 1060: ... 10 25 OPTIONAL PARTS OPTIONAL PARTS z zDimensions Liquid pipe Dis charge gas pipe Suction gas pipe ...
Страница 1068: ... 10 33 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX04BH Unit mm ...
Страница 1073: ... 10 38 OPTIONAL PARTS OPTIONAL PARTS 5 5 WIRING DIAGRAMS MODEL UTP RX01AH MODEL UTP RX01BH ...
Страница 1074: ... 10 39 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX01CH ...
Страница 1075: ... 10 40 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX04BH ...