PROCEDURE IN BRIEF FOR MAKING XIF & REGISTER DATA TO
NETWORK CONVERTOR (UTY-VLGX)
NOTE:
For detailed information, check the Application Manual which is included inside
packaged CD-ROM.
Following are the work items during on line operation. However, making XIF is also
possible during off line operation.
STEP 1: Connect the PC and Network Convertor (UTY-VLGX) .
Connection will be done by the connector cable provided as an accessory item of
UTY-VLGX.
STEP 2: Install Tool for Network Convertor (software) for UTY-VLGX in PC.
Tool for Network Convertor is the accessory item of UTY-VLGX.
STEP 3: Set Network Convertor (UTY-VLGX) to Installation Mode.
STEP 4: Setting ID number of UTY-VLGX on PC screen of Tool for Network Convertor.
(ID number is required to identify UTY-VLGX from BMS. A maximum of four Network
Convertors can be connected to one BMS, and ID number allocation is like 00, 01,
and so on.)
STEP 5: Initial setting of Indoor Unit & Outdoor Unit Addresses by using the Tool for Network
Convertor.
STEP 6: Register the initial setting data to UTY-VLGX. Click ‘Register’ dialog.
STEP 7: Set Configuration Properties.
It is the communication properties of UTY-VLGX. Select the following Communication
items & Communication type if necessary. Otherwise, communication will be taken
place by the Default values.
● Select Communication items
-Event Driven communication or Cyclic communication.
(Default: Cyclic 3minutes)
-Communication Interval Time during turning ON all together.
(Default: 3 minutes)
● Select Communication type (to communicate data with BMS)
- Communicate only when changing network variable or communicate all network
variable. (Default: Only when changing network variable)
- Communicate only when changing room temperature value.
(Default: Room temperature changed value 1°C)
STEP 8: Register the Configuration Properties data to UTY-VLGX. Click ‘Register’ dialog.
STEP 9: Making / Modifying XIF, and transfer XIF data by USB flash drive or floppy disk for
binding.
STEP 10: Reset Network Convertor (UTY-VLGX) to press ‘Reset SW7’.
STEP 11: Turn OFF the power. After that, remove the connection of PC and Network Convertor
(UTR-VLGX) respectively.
In this stage, Network Convertor (UTY-VLGX) is ready for binding and commissioning.
- (05 - 168) -
C
O
N
TRO
L
SY
ST
EM
C
O
N
TRO
L
SY
ST
EM
Содержание AB* A12GATH
Страница 1: ...DESIGN TECHNICAL MANUAL ...
Страница 3: ...1 GENERAL INFORMATION DTV_J3LE050E_03 CHAPTER01 2017 10 31 ...
Страница 20: ...2 MODEL SELECTION DTV_J3LE050E_03 CHAPTER02 2017 10 31 ...
Страница 115: ...3 OUTDOOR UNITS DTV_J3LE050E_02 CHAPTER03 2017 07 21 ...
Страница 119: ... Unit mm Detail B Detail A Detail C 03 03 OUTDOOR UNITS OUTDOOR UNITS ...
Страница 128: ...5 WIRING DIAGRAM MODELS AJ 072LELAH AJ 090LELAH 03 12 OUTDOOR UNITS OUTDOOR UNITS ...
Страница 129: ... MODEL AJ 108LELAH 03 13 OUTDOOR UNITS OUTDOOR UNITS ...
Страница 133: ... SOUND LEVEL CHECK POINT Microphone Airflow 1 m 03 17 OUTDOOR UNITS OUTDOOR UNITS ...
Страница 136: ...4 INDOOR UNITS DTV_VR2E018E_14 CHAPTER04 2017 10 31 ...
Страница 216: ... Unit mm INSTALLATION PLACE 04 77 INDOOR UNITS INDOOR UNITS ...
Страница 231: ...4 7 MEDIUM STATIC PRESSURE DUCT TYPE MODELS ARXA24GBLH ARXA30GBLH ARXA36GBLH ARXA45GBLH 04 92 INDOOR UNITS INDOOR UNITS ...
Страница 232: ...4 8 HIGH STATIC PRESSURE DUCT TYPE MODEL ARXC36GBTH MODELS ARXC45GATH ARXC60GATH 04 93 INDOOR UNITS INDOOR UNITS ...
Страница 233: ... MODELS ARXC72GBTH ARXC90GBTH ARXC96GATH 04 94 INDOOR UNITS INDOOR UNITS ...
Страница 234: ...4 9 LARGE AIRFLOW DUCT TYPE MODEL ARXN018GLBH 04 95 INDOOR UNITS INDOOR UNITS ...
Страница 235: ... MODELS ARXN024GTBH ARXN030GTBH 04 96 INDOOR UNITS INDOOR UNITS ...
Страница 236: ... MODELS ARXN18GATH ARXN24GATH ARXN30GATH ARXN34GATH ARXN36GATH ARXN45GATH 04 97 INDOOR UNITS INDOOR UNITS ...
Страница 237: ...4 10 FLOOR CEILING TYPE MODELS AB A12GATH AB A14GATH AB A18GATH AB A24GATH 04 98 INDOOR UNITS INDOOR UNITS ...
Страница 238: ...4 11 CEILING TYPE MODELS AB A30GATH AB A36GATH AB A45GATH AB A54GATH 04 99 INDOOR UNITS INDOOR UNITS ...
Страница 241: ...4 14 WALL MOUNTED TYPE MODELS AS A004GTAH AS A007GTAH AS A009GTAH 04 102 INDOOR UNITS INDOOR UNITS ...
Страница 242: ... MODELS AS A012GCAH AS A014GCAH 04 103 INDOOR UNITS INDOOR UNITS ...
Страница 243: ... MODELS AS A04GACH AS A07GACH AS A09GACH AS A12GACH AS A14GACH 04 104 INDOOR UNITS INDOOR UNITS ...
Страница 244: ... MODELS AS A18GBCH AS A24GBCH AS A18GACH AS A24GACH AS A30GACH 04 105 INDOOR UNITS INDOOR UNITS ...
Страница 245: ... MODELS AS A030GTAH AS A034GTAH 04 106 INDOOR UNITS INDOOR UNITS ...
Страница 246: ...4 15 WALL MOUNTED TYPE EEV external model MODELS AS E004GTAH AS E007GTAH AS E009GTAH 04 107 INDOOR UNITS INDOOR UNITS ...
Страница 247: ... MODELS AS E012GCAH AS E014GCAH 04 108 INDOOR UNITS INDOOR UNITS ...
Страница 248: ... MODELS AS E04GACH AS E07GACH AS E09GACH AS E12GACH AS E14GACH 04 109 INDOOR UNITS INDOOR UNITS ...
Страница 466: ...5 CONTROL SYSTEM DTV_VR2E018E_12 CHAPTER05 2017 10 31 ...
Страница 690: ...6 SYSTEM DESIGN DTV_J3LE050E_03 CHAPTER06 2017 10 31 ...
Страница 779: ...7 FUNCTION SETTING DTV_VR2E018E_14 CHAPTER07 2017 10 31 ...
Страница 975: ...8 EXTERNAL INPUT OUTPUT DTV_VR2E018E_11 CHAPTER08 2017 10 31 ...
Страница 1016: ...9 NOTES DTV_VR2E018E_11 CHAPTER09 2017 07 21 ...
Страница 1034: ...10 OPTIONAL PARTS DTV_VR2E018E_13 CHAPTER10 2017 10 31 ...
Страница 1046: ... 10 11 OPTIONAL PARTS OPTIONAL PARTS z zDimensions Liquid pipe Discharge gas pipe Suction gas pipe 130 15 REDUCER 95 15 REDUCER ...
Страница 1058: ... 10 23 OPTIONAL PARTS OPTIONAL PARTS z zDimensions Liquid pipe Dis charge gas pipe Suction gas pipe ...
Страница 1060: ... 10 25 OPTIONAL PARTS OPTIONAL PARTS z zDimensions Liquid pipe Dis charge gas pipe Suction gas pipe ...
Страница 1068: ... 10 33 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX04BH Unit mm ...
Страница 1073: ... 10 38 OPTIONAL PARTS OPTIONAL PARTS 5 5 WIRING DIAGRAMS MODEL UTP RX01AH MODEL UTP RX01BH ...
Страница 1074: ... 10 39 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX01CH ...
Страница 1075: ... 10 40 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX04BH ...