INSTALLATION

„

z

Connection Pattern

NOTE:

 Connection pattern is different according to type of Indoor unit.

Indoor unit types

Connection Pattern

All Cassette type

Pattern A

All Duct type

All Ceiling type

Wall Mounted type

Pattern B

„

z

Pattern A

Connect the end of remote controller cable directly to the exclusive terminal block.
Set the DIP switch (SW1) to "3WIRE" on the PC board of the indoor unit.

* Layout of terminal block and 

PC board is varies, depending 
on the type of indoor unit.

Terminal block

Functional earthing 
(If necessary)

Remote controller 
cable 

Set to "3WIRE" the 
DIP switch (SW1)

Indoor unit 
PC board

Y1

 

Y2

 

Y3

Black

White

Red

NOTE:

  The equipment may fail if it is connected to the outdoor unit or the power supply 

terminal block.

„

z

Pattern B

1)  Use a tool to cut off the terminal on the end of the remote controller cable, and then remove 

the insulation from the cut end of the cable as shown in Fig. 1. Connect the remote controller 

cable and connecting cable as shown in Fig. 2. Be sure to insulate the connection between 

the cables.

Remote
controller cable 

Insulated
connection

White

Black

20 mm

Red

Connecting
cable

2

.

g

i

F

1

.

g

i

F

2)  Connect the remote controller cable to the connecting cable, and insert it to the connector. 
    Set the DIP switch (SW1) to "3WIRE" on the PC board of the indoor unit.

Indoor unit 
PC board

Remote controller 
cable 

Connecting cable

Connector CNC01 
(onboard)

Connect to earth 
(ground) screw

Functional earthing 
(If necessary)

Set to "3WIRE" the 
DIP switch (SW1)

*  Layout of Connector and PC board varies, depending on 

the type of indoor unit

Connector
(adapter)

SW1

Indoor unit 
PC board

- (05 - 95) -

C

O

N

TRO

L

SY

ST

EM

C

O

N

TRO

L

SY

ST

EM

Содержание AB* A12GATH

Страница 1: ...DESIGN TECHNICAL MANUAL ...

Страница 2: ...CONTENTS 1 GENERAL INFORMATION 2 MODEL SELECTION 3 OUTDOOR UNITS 4 INDOOR UNITS 5 CONTROL SYSTEM 6 SYSTEM DESIGN 7 FUNCTION SETTING 8 EXTERNAL INPUT OUTPUT 9 NOTES 10 OPTIONAL PARTS ...

Страница 3: ...1 GENERAL INFORMATION DTV_J3LE050E_03 CHAPTER01 2017 10 31 ...

Страница 4: ...L LINE UP 01 01 1 1 OUTDOOR UNIT 01 01 1 2 INDOOR UNIT 01 02 1 3 CONTROLLER 01 06 1 4 ADAPTOR CONVERTOR MAINTENANCE TOOL 01 08 1 5 BRANCH KIT 01 10 1 6 HEADER 01 10 1 7 EV KIT 01 11 1 8 CASSETTE GRILLE 01 11 1 9 OTHERS optional parts 01 12 ...

Страница 5: ...indoor unit 8 22 4 AJ 072LELAH 1 to 20 10 28 0 AJ 090LELAH 1 to 25 12 33 5 AJ 108LELAH 1 to 30 A J Y 0 7 2 L E L A H 1 2 3 4 5 6 7 7 8 9 10 Type AJ Outdoor unit Destination H GENERAL Y FUJITSU Function L Inverter R410A Phase E 3 phase Model change code LA Series name H Model code kW 072 22 4 090 28 0 108 33 5 01 01 GENERAL INFORMATION GENERAL INFORMATION ...

Страница 6: ...ar Flow Cassette Cassette AUXB04GBLH AUXB07GALH AUXB09GALH AUXB12GALH AUXB14GALH AUXB18GALH AUXB24GALH AUXM018GLAH AUXM024GLAH AUXM030GLAH AUXK018GLAH AUXK024GLAH AUXK030GLAH AUXK034GLAH AUXK036GLAH AUXK045GLAH AUXK054GLAH AUXD18GALH AUXD24GALH AUXA30GALH AUXA34GALH AUXA36GALH AUXA45GALH AUXA54GALH Mini Duct Slim Duct Slim Concealed Floor Medium Static Pressure Duct ARXK04GCLH ARXK07GCLH ARXK09GCL...

Страница 7: ... 54 18 0 60 22 4 72 25 0 90 28 0 96 High Static Pressure Duct Large Airflow Duct ARXC36GBTH ARXC45GATH ARXC60GATH ARXC72GBTH ARXC90GBTH ARXC96GATH ARXN018GLBH ARXN024GTBH ARXN030GTBH Compact Floor Compact Floor EEV external AG A004GCAH AG A007GCAH AG A009GCAH AG A012GCAH AG A014GCAH AG E004GCAH AG E007GCAH AG E009GCAH AG E012GCAH AG E014GCAH Floor Ceiling Ceiling AB A12GATH AB A14GATH AB A18GATH A...

Страница 8: ...45 14 0 54 18 0 60 22 4 72 25 0 90 28 0 96 Wall Mounted Wall Mounted EEV external AS A004GTAH AS A007GTAH AS A009GTAH AS A012GCAH AS A014GCAH AS A12GACH AS A14GACH AS A18GBCH AS A24GBCH AS A030GTAH AS A034GTAH AS E004GTAH AS E007GTAH AS E009GTAH AS E012GCAH AS E014GCAH AS E12GACH AS E14GACH EV kit 01 04 GENERAL INFORMATION GENERAL INFORMATION ...

Страница 9: ...2 5 54 14 0 60 18 0 72 22 4 90 25 0 96 28 0 Model change code AC AL AT BC BL BT CL A U X K 5 0 4 G L A H 1 2 3 4 5 6 7 8 9 10 11 Type AU Cassette AR Duct AB Floor Ceiling or Ceiling AG Compact Floor AS Wall Mounted Destination H GENERAL Y FUJITSU X Neutral brand Model A Standard B Compact AU C High Static Pressure AR D Slim AU AR E EEV external AG AS K Mini AR K Standard AU M Slim AU Function G In...

Страница 10: ...out operation mode UTY RHR Simple Remote Controller With operation mode UTY RSK 3 wire type Simple Remote Controller Without operation mode UTY RHK Wireless Remote Controller UTY LNH CENTRAL CONTROL System Controller System Controller Lite Touch Panel Controller Central Remote Controller Group Remote Controller UTY APGXZ1 UTY ALGXZ1 UTY DTG Z1 UTY DCG UTY CGG Network Convertor UTY VGGXZ1 is necess...

Страница 11: ...CG Central Remote Controller CGG Group Remote Controller RNR RLR RNK Wired Remote Controller RSR RSK Simple Remote Controller with operation mode RHR RHK Simple Remote Controller without operation mode LNH Wireless Remote Controller Destination G GENERAL Y FUJITSU X Neutral brand Series name UTY Control unit 01 07 GENERAL INFORMATION GENERAL INFORMATION ...

Страница 12: ...zed BMS Modbus Convertor for VRF Model UTY VMGX For connection between VRF network system and a Modbus open network KNX Convertor for Indoor Unit Model UTY VKSX For connection between Single split indoor unit and a KNX open network Modbus Convertor for Indoor Unit Model UTY VMSX For connection between Single split indoor unit and a Modbus open network BACnet Gateway Hardware Model UTY VBGX For con...

Страница 13: ...tored in real time over the Internet Service Tool Model UTY ASGXZ1 Extensive monitoring and analysis functions for installation and maintenance Operation status and error history can be grasped promptly and adequately External Switch Controller Model UTY TERX UTY TEKX Air conditioner switching can be controlled by connecting other external sensor switches Wireless LAN adapter Model UTY TFSXZ1 Remo...

Страница 14: ...AX090A Liquid Pipe Gas Pipe Separation Tube Model UTP AX180A Liquid Pipe Gas Pipe 1 6 HEADER Header Model UTR H0906L Model UTR H1806L Model UTR H0908L Model UTR H1808L Liquid Pipe Liquid Pipe Liquid Pipe Liquid Pipe Gas Pipe Gas Pipe Gas Pipe Gas Pipe 01 10 GENERAL INFORMATION GENERAL INFORMATION ...

Страница 15: ...nal 1 8 CASSETTE GRILLE Cassette grille Models UTG UFYC W UTG UFGC W Cassette grille Models UTG UGYA W UTG UGGA W For Compact Cassette type For Cassette type Cassette grille Models UTG UKYC W UTG UKGC W UTG UKYA B UTG UKGA B For Circular Flow Cassette type 01 11 GENERAL INFORMATION GENERAL INFORMATION ...

Страница 16: ...A For Medium Static Pressure Duct type For Large Airflow Duct type 18 model For High Static Pressure Duct type x 2 pcs x 2 pcs Long life Filter Model UTD LFNA Drain Pump Unit Model UTZ PX1NBA Drain Pump Unit Model UTR DPB24T For Medium Static Pressure Duct type For Ceiling type Air outlet shutter plate Model UTR YDZK Air outlet shutter plate Model UTR YDZB For Cassette type For Compact Cassette ty...

Страница 17: ... Receiver Unit Model UTY LBHXD For Circular Flow Cassette type Human Sensor Kit Model UTY SHZXC For Circular Flow Cassette type Insulation Kit for High Humidity Models UTZ KXGC 1 UTZ KXRA 2 Insulation Kit 1 For Compact Cassette type 2 For Cassette type For Circular Flow Cassette type Remote Sensor Unit Model UTY XSZX Thermo sensor for sensing the temperature of arbitrary place in the room Install ...

Страница 18: ...te type Fresh air intake kit Model UTZ VXAA For Compact Cassette type Auto louver grille kit Models UTD GXSA W UTD GXSB W UTD GXSC W Auto louver grille kit Models UTD GXTA W UTD GXTB W UTD GXTC W For Slim Duct For Mini Duct Slim Duct 01 14 GENERAL INFORMATION GENERAL INFORMATION ...

Страница 19: ...ntroller For Outdoor unit External connect kit Model UTY XWZXZA External connect kit Model UTY XWZXZB For Touch panel controller Central remote controller For Indoor unit External connect kit Model UTY XWZXZC External connect kit Model UTY XWZXZD For Indoor unit For Indoor unit External connect kit Model UTY XWZXZE For Indoor unit External connect kit Model UTY XWZXZF For Outdoor unit 01 15 GENERA...

Страница 20: ...2 MODEL SELECTION DTV_J3LE050E_03 CHAPTER02 2017 10 31 ...

Страница 21: ... HEATING OUTDOOR UNIT 02 23 6 CAPACITY COMPENSATION COEFFICIENT 02 29 7 CAPACITY TABLE COOLING INDOOR UNIT 02 30 7 1 COMPACT CASSETTE TYPE 02 30 7 2 CIRCULAR FLOW CASSETTE TYPE 02 33 7 3 CASSETTE TYPE 02 37 7 4 MINI DUCT TYPE 02 40 7 5 SLIM DUCT SLIM CONCEALED FLOOR TYPE 02 43 7 6 MEDIUM STATIC PRESSURE DUCT TYPE 02 45 7 7 HIGH STATIC PRESSURE DUCT TYPE 02 46 7 8 LARGE AIRFLOW DUCT TYPE 02 48 7 9 ...

Страница 22: ...PE 02 71 8 5 SLIM DUCT SLIM CONCEALED FLOOR TYPE 02 73 8 6 MEDIUM STATIC PRESSURE DUCT TYPE 02 75 8 7 HIGH STATIC PRESSURE DUCT TYPE 02 76 8 8 LARGE AIRFLOW DUCT TYPE 02 78 8 9 COMPACT FLOOR TYPE 02 79 8 10 COMPACT FLOOR TYPE EEV external model 02 81 8 11 FLOOR CEILING TYPE 02 83 8 12 CEILING TYPE 02 84 8 13 WALL MOUNTED TYPE 02 85 8 14 WALL MOUNTED TYPE EEV external model 02 90 ...

Страница 23: ...de Simple Remote Controller without operation mode Wireless Remote Controller Selection of adaptor convertor Network Convertor Network Convertor for LONWORKS KNX Convertor for VRF KNX Convertor for INDOOR UNIT Modbus Convertor for VRF Modbus Convertor for INDOOR UNIT BACnet Gateway Wireless LAN adapter Signal Amplifier External Switch Controller Selection of branch kit Separation Tube Header END S...

Страница 24: ...name Connectable indoor unit Indoor unit connectable cooling capacity kW Cooling Heating 8 22 4 22 4 AJ 072LELAH 1 to 20 11 2 to 33 6 10 28 0 28 0 AJ 090LELAH 1 to 25 14 0 to 42 0 12 33 5 33 5 AJ 108LELAH 1 to 30 16 8 to 50 2 02 02 MODEL SELECTION MODEL SELECTION ...

Страница 25: ...288 x 840 x 840 10 0 11 2 AUXA34GALH 11 2 12 5 AUXA36GALH 12 5 14 0 AUXA45GALH 14 0 16 0 AUXA54GALH Mini duct 1 1 1 3 ARXK04GCLH 198 x 700 x 450 2 2 2 8 ARXK07GCLH 2 8 3 2 ARXK09GCLH 3 6 4 0 ARXK12GCLH 4 5 5 0 ARXK14GCLH 5 6 6 3 ARXK18GCLH 198 x 900 x 450 7 1 8 0 ARXK24GCLH 198 x1 100 x 450 Slim Duct Slim Concealed Floor 2 2 2 8 ARXD07GALH 198 x 700 x 620 2 8 3 2 ARXD09GALH 3 6 4 0 ARXD12GALH 4 5 ...

Страница 26: ...TR EV09XB 2 2 2 8 AG E007GCAH 2 8 3 2 AG E009GCAH 3 6 4 0 AG E012GCAH UTR EV14XB 4 0 4 5 AG E014GCAH Wall mounted 1 1 1 3 AS A004GTAH 262 x 820 x 206 2 2 2 8 AS A007GTAH 2 8 3 2 AS A009GTAH 3 6 4 0 AS A012GCAH 268 x 840 x 203 4 0 4 5 AS A014GCAH 3 6 4 1 AS A12GACH 275 x 790 x 215 4 5 5 0 AS A14GACH 5 6 6 3 AS A18GBCH 320 x 998 x 238 7 1 8 0 AS A24GBCH 9 0 10 0 AS A030GTAH 340 x 1 150 x 280 10 0 11...

Страница 27: ...Convertor for VRF UTY VKGX KNX Convertor for Indoor Unit UTY VKSX Modbus Convertor for VRF UTY VMGX Modbus Convertor for Indoor Unit UTY VMSX Network Convertor UTY VGGXZ1 Network Convertor for LONWORKS UTY VLGX BACnet Gateway Hardware UTY VBGX BACnet Gateway Software UTY ABGXZ1 Signal Amplifier UTY VSGXZ1 External Switch Controller UTY TERX UTY TEKX Service Tool UTY ASGXZ1 Web Monitoring Tool UTY ...

Страница 28: ...te type Half concealed kit UTR STA For Compact Floor type IR Receiver Unit UTB YWC For all Duct type UTY LRH B1 For Cassette type UTY LBHXD For Circular Flow Cassette type Human Sensor Kit UTY SHZXC Remote Sensor Unit UTY XSZX For all Duct type Insulation Kit for High Humidity UTZ KXRA For Cassette type Circular Flow Cassette type UTZ KXGC For Compact Cassette type Fresh air intake kit UTZ VXAA Fo...

Страница 29: ...h the heat load for each room preliminarily Change to a larger capacity of indoor unit Estimated capacity of indoor unit Heat load Calculate the estimated capacity of each indoor units Refer to 3 2 Find indoor unit capacity at design temperature Calculate the estimated capacity Compensation coefficient of pipe length COOLING Compensation coefficient of pipe length and frosting defrosting HEATING C...

Страница 30: ...city of indoor units at design temperature Change to a larger capacity of outdoor unit Actual capacity of indoor unit Capacity of indoor unit at design temperature A Total capacity of indoor units at design temperature Compensated capacity of outdoor unit Actual capacity of indoor unit Heat load Calculate the compensated capacity of outdoor unit Refer to 3 2 Find outdoor unit capacity at design te...

Страница 31: ...ity of outdoor unit 4 Find capacity of outdoor unit at rated condition TCout r From 2 MODEL LINE UP 5 Calculate total rated capacity of indoor units TCin r and ratio to the rated capacity of outdoor unit TCin r TCout r 6 Find capacity of outdoor unit at design temperature TCout d using result of 5 and 4 CAPACITY TABLE OUTDOOR UNIT 7 Calculate the compensated capacity of outdoor unit TCout c COOLIN...

Страница 32: ... See 6 A 6 Estimated capacity of indoor unit TCin e kW 6 9 6 9 6 9 2 7 2 2 A 4 x A 5 A 7 Total rated capacity TCin r kW 26 3 Sum of A 3 A 8 Total capacity at design temperature TCin d kW 28 5 Sum of A 4 z zPreliminary selection of outdoor unit Remark B 1 Outdoor unit model 8HP AJ 072LELAH B 2 Rated capacity TCout r kW 22 4 See 2 B 3 Total rated capacity of indoor unit Rated capacity of outdoor uni...

Страница 33: ...0 CWB 30 CDB 22 CWB 32 CDB 23 CWB CDB TC IP TC IP TC IP TC IP TC IP 26 8 120 15 15 5 2 65 26 9 4 52 29 2 4 89 31 8 5 15 32 5 5 13 35 15 5 3 93 25 4 7 67 25 9 7 73 27 0 7 86 27 6 7 93 46 15 5 5 94 18 4 6 67 18 7 6 67 19 5 6 67 19 9 6 67 24 6 110 15 14 2 2 44 24 6 4 15 26 7 4 49 30 9 5 17 31 6 5 15 35 14 2 3 61 24 6 7 48 25 4 7 67 26 4 7 79 27 0 7 86 46 14 2 5 22 18 2 6 72 18 5 6 72 19 3 6 72 19 7 6...

Страница 34: ...mated capacity of indoor unit TCin e kW 8 7 8 7 8 7 1 1 1 1 A 4 x A 5 A 7 Total rated capacity TCin r kW 29 2 Sum of A 3 A 8 Total capacity at design temperature TCin d kW 31 5 Sum of A 4 z zPreliminary selection of outdoor unit Remark B 1 Outdoor unit model 10HP AJ 090LELAH B 2 Rated capacity TCout r kW 28 0 See 2 B 3 Total rated capacity of indoor unit Rated capacity of outdoor unit TCin r TCout...

Страница 35: ...0 CWB 30 CDB 22 CWB 32 CDB 23 CWB CDB TC IP TC IP TC IP TC IP TC IP 30 8 110 15 17 7 3 88 30 8 6 62 33 4 7 17 35 1 7 17 35 9 7 16 35 17 7 5 07 28 7 8 63 29 3 8 67 30 6 8 74 31 3 8 78 46 17 7 6 67 20 0 6 70 20 5 6 70 21 4 6 70 21 8 6 70 28 0 100 15 16 1 3 54 28 0 6 03 30 4 6 53 34 0 7 18 34 8 7 17 35 16 1 4 63 28 0 8 59 28 6 8 63 29 9 8 70 30 5 8 73 46 16 1 5 92 19 7 6 73 20 2 6 73 21 1 6 73 21 5 6...

Страница 36: ...5 8 00 25 1 8 07 25 6 8 14 26 2 8 21 27 3 8 35 27 9 8 42 40 18 1 5 66 19 9 6 54 20 3 6 54 20 8 6 54 21 2 6 54 21 6 6 54 22 0 6 54 22 9 6 54 23 3 6 54 43 18 1 6 54 18 5 6 55 18 9 6 55 19 3 6 56 19 7 6 56 20 1 6 56 20 5 6 56 21 3 6 55 21 7 6 55 46 16 7 6 57 17 1 6 57 17 5 6 57 17 9 6 57 18 3 6 57 18 7 6 57 19 0 6 57 19 8 6 57 20 2 6 57 29 1 130 15 16 8 2 86 19 2 3 27 21 7 3 67 24 2 4 08 26 7 4 48 29...

Страница 37: ...2 4 6 97 23 7 7 58 24 5 7 59 25 0 7 59 40 12 9 3 75 14 8 4 29 16 7 5 01 18 6 5 92 20 3 6 77 20 6 6 77 21 0 6 77 21 8 6 77 22 2 6 77 43 12 9 4 13 14 8 4 82 16 7 5 78 18 5 6 77 18 9 6 77 19 3 6 77 19 6 6 77 20 4 6 77 20 8 6 77 46 12 9 4 58 14 8 5 55 16 7 6 67 17 2 6 78 17 6 6 78 17 9 6 78 18 3 6 78 19 0 6 78 19 4 6 78 20 1 90 15 11 6 2 02 13 3 2 30 15 0 2 58 16 7 2 86 18 5 3 14 20 2 3 42 21 9 3 70 2...

Страница 38: ... 57 10 0 1 76 11 2 1 94 12 3 2 13 13 4 2 32 14 6 2 50 16 9 2 88 18 0 3 06 15 7 7 1 44 8 9 1 63 10 0 1 83 11 2 2 02 12 3 2 22 13 4 2 41 14 6 2 61 16 9 3 00 18 0 3 19 21 7 7 1 55 8 9 1 76 10 0 1 97 11 2 2 18 12 3 2 39 13 4 2 60 14 6 2 81 16 9 3 24 18 0 3 45 23 7 7 1 59 8 9 1 81 10 0 2 03 11 2 2 25 12 3 2 47 13 4 2 68 14 6 2 90 16 9 3 34 18 0 3 56 25 7 7 1 65 8 9 1 87 10 0 2 10 11 2 2 33 12 3 2 55 13...

Страница 39: ...9 6 8 96 30 2 9 00 31 6 9 08 32 3 9 12 40 20 9 6 59 21 4 6 59 21 9 6 59 22 4 6 59 22 9 6 59 23 4 6 59 23 9 6 59 25 0 6 59 25 5 6 59 43 19 6 6 60 20 0 6 60 20 5 6 60 21 0 6 60 21 5 6 60 22 0 6 60 22 5 6 60 23 5 6 60 24 0 6 59 46 18 3 6 61 18 7 6 61 19 2 6 61 19 7 6 61 20 1 6 60 20 6 6 60 21 1 6 60 22 0 6 60 22 5 6 60 36 4 130 15 21 0 4 56 24 1 5 21 27 1 5 85 30 2 6 50 33 3 7 15 34 3 7 18 35 2 7 17 ...

Страница 40: ...27 4 8 83 28 0 8 87 29 2 8 94 29 8 8 98 40 16 1 5 09 18 5 5 82 20 9 6 72 21 4 6 73 21 8 6 73 22 3 6 73 22 8 6 73 23 8 6 73 24 3 6 73 43 16 1 5 47 18 5 6 34 19 6 6 73 20 1 6 73 20 5 6 73 21 0 6 73 21 5 6 73 22 4 6 73 22 9 6 73 46 16 1 5 92 18 0 6 74 18 4 6 73 18 9 6 73 19 3 6 73 19 7 6 73 20 2 6 73 21 1 6 73 21 5 6 73 25 2 90 15 14 5 3 21 16 7 3 65 18 8 4 10 20 9 4 55 23 1 5 00 25 2 5 45 27 3 5 89 ...

Страница 41: ...9 14 0 3 09 15 4 3 39 16 8 3 68 18 2 3 98 21 1 4 58 22 5 4 88 15 9 7 2 25 11 1 2 55 12 5 2 86 14 0 3 17 15 4 3 48 16 8 3 78 18 2 4 09 21 1 4 70 22 5 5 01 21 9 7 2 36 11 1 2 68 12 5 3 00 14 0 3 33 15 4 3 65 16 8 3 97 18 2 4 30 21 1 4 94 22 5 5 27 23 9 7 2 41 11 1 2 74 12 5 3 07 14 0 3 40 15 4 3 73 16 8 4 06 18 2 4 39 21 1 5 05 22 5 5 38 25 9 7 2 46 11 1 2 80 12 5 3 14 14 0 3 48 15 4 3 81 16 8 4 15 ...

Страница 42: ... 35 4 10 73 36 2 10 77 37 8 10 84 38 7 10 87 40 27 0 9 01 28 3 9 36 29 0 9 36 29 7 9 36 30 3 9 36 31 0 9 36 31 7 9 36 33 0 9 36 33 7 9 36 43 26 1 9 37 26 8 9 37 27 4 9 37 28 0 9 37 28 7 9 37 29 3 9 37 30 0 9 37 31 3 9 36 32 0 9 36 46 24 6 9 37 25 2 9 37 25 8 9 37 26 4 9 37 27 1 9 37 27 7 9 37 28 3 9 37 29 6 9 37 30 2 9 37 43 5 130 15 25 1 5 86 28 8 6 67 32 5 7 49 36 2 8 30 39 9 9 12 41 0 9 17 42 1...

Страница 43: ... 77 32 8 10 62 33 5 10 65 35 0 10 72 35 7 10 75 40 19 3 6 21 22 1 7 07 25 0 8 12 27 8 9 37 28 7 9 50 29 3 9 50 29 9 9 50 31 2 9 50 31 8 9 50 43 19 3 6 61 22 1 7 62 25 0 8 90 26 6 9 50 27 2 9 50 27 8 9 50 28 4 9 50 29 6 9 50 30 2 9 50 46 19 3 7 08 22 1 8 35 24 5 9 50 25 1 9 50 25 7 9 50 26 3 9 50 26 9 9 50 28 0 9 50 28 6 9 50 30 1 90 15 17 4 4 15 19 9 4 72 22 5 5 28 25 0 5 84 27 6 6 41 30 2 6 97 32...

Страница 44: ... 18 4 4 38 20 1 4 75 21 8 5 13 25 2 5 88 26 9 6 26 15 11 6 2 93 13 3 3 32 15 0 3 70 16 7 4 09 18 4 4 47 20 1 4 86 21 8 5 24 25 2 6 01 26 9 6 40 21 11 6 3 05 13 3 3 45 15 0 3 85 16 7 4 25 18 4 4 66 20 1 5 06 21 8 5 46 25 2 6 27 26 9 6 67 23 11 6 3 10 13 3 3 51 15 0 3 92 16 7 4 33 18 4 4 74 20 1 5 15 21 8 5 56 25 2 6 38 26 9 6 79 25 11 6 3 16 13 3 3 57 15 0 3 99 16 7 4 41 18 4 4 83 20 1 5 25 21 8 5 ...

Страница 45: ... 7 6 82 31 2 6 54 29 1 6 03 28 1 5 77 27 0 5 52 25 0 5 03 22 9 4 55 12 0 10 6 33 3 6 59 31 2 6 09 29 1 5 61 28 1 5 37 27 0 5 13 25 0 4 67 22 9 4 23 15 0 13 5 33 3 6 12 31 2 5 65 29 1 5 20 28 1 4 98 27 0 4 76 25 0 4 33 22 9 3 92 26 8 120 19 3 20 0 17 7 4 38 17 6 4 66 17 6 4 94 17 6 5 08 17 6 5 22 17 6 5 49 17 6 5 77 15 0 16 0 19 4 4 83 19 4 5 09 19 3 5 36 19 3 5 49 19 2 5 62 19 2 5 88 19 1 6 14 12 ...

Страница 46: ...4 27 14 6 4 11 13 4 3 78 12 3 3 45 5 0 6 0 17 9 4 89 16 8 4 56 15 7 4 24 15 1 4 08 14 6 3 92 13 4 3 60 12 3 3 29 3 0 4 0 17 9 4 67 16 8 4 35 15 7 4 04 15 1 3 89 14 6 3 73 13 4 3 43 12 3 3 13 1 0 2 0 17 9 4 44 16 8 4 14 15 7 3 85 15 1 3 70 14 6 3 55 13 4 3 26 12 3 2 98 0 0 1 0 17 9 4 33 16 8 4 04 15 7 3 75 15 1 3 61 14 6 3 47 13 4 3 18 12 3 2 91 2 0 1 0 17 9 4 12 16 8 3 84 15 7 3 57 15 1 3 43 14 6 ...

Страница 47: ...36 1 8 44 35 1 8 20 33 8 7 84 31 2 7 13 28 6 6 44 12 0 10 6 39 0 8 31 38 6 8 44 36 4 7 92 35 1 7 58 33 8 7 24 31 2 6 58 28 6 5 95 15 0 13 5 41 2 8 45 39 0 7 94 36 4 7 30 35 1 6 98 33 8 6 67 31 2 6 07 28 6 5 48 33 6 120 19 3 20 0 19 5 6 74 19 3 6 90 19 1 7 06 19 0 7 14 18 9 7 22 18 8 7 38 18 6 7 54 15 0 16 0 21 5 7 00 21 3 7 16 21 0 7 31 20 9 7 39 20 8 7 46 20 6 7 61 20 4 7 77 12 0 13 0 23 1 7 19 2...

Страница 48: ...16 8 5 61 15 4 5 12 5 0 6 0 22 4 7 23 21 0 6 74 19 6 6 25 18 9 6 01 18 2 5 77 16 8 5 30 15 4 4 84 3 0 4 0 22 4 6 84 21 0 6 37 19 6 5 91 18 9 5 68 18 2 5 46 16 8 5 01 15 4 4 57 1 0 2 0 22 4 6 46 21 0 6 02 19 6 5 58 18 9 5 37 18 2 5 15 16 8 4 73 15 4 4 31 0 0 1 0 22 4 6 28 21 0 5 85 19 6 5 42 18 9 5 21 18 2 5 01 16 8 4 60 15 4 4 19 2 0 1 0 22 4 5 93 21 0 5 52 19 6 5 12 18 9 4 92 18 2 4 73 16 8 4 34 ...

Страница 49: ...40 2 9 19 40 0 9 29 39 7 9 39 37 3 8 81 34 2 7 97 12 0 10 6 43 5 8 98 43 0 9 18 42 5 9 38 42 0 9 37 40 4 8 96 37 3 8 16 34 2 7 38 15 0 13 5 46 0 9 17 45 5 9 37 43 5 9 03 42 0 8 65 40 4 8 27 37 3 7 53 34 2 6 81 40 2 120 19 3 20 0 20 9 6 91 20 8 7 13 20 6 7 35 20 6 7 47 20 5 7 58 20 3 7 80 20 2 8 02 15 0 16 0 23 3 7 26 23 1 7 47 22 9 7 69 22 8 7 80 22 7 7 90 22 5 8 11 22 2 8 33 12 0 13 0 25 2 7 51 2...

Страница 50: ...20 1 6 91 18 4 6 32 5 0 6 0 26 8 8 90 25 1 8 30 23 5 7 71 22 6 7 41 21 8 7 12 20 1 6 55 18 4 5 98 3 0 4 0 26 8 8 42 25 1 7 86 23 5 7 29 22 6 7 02 21 8 6 74 20 1 6 20 18 4 5 66 1 0 2 0 26 8 7 97 25 1 7 43 23 5 6 90 22 6 6 64 21 8 6 38 20 1 5 87 18 4 5 36 0 0 1 0 26 8 7 75 25 1 7 23 23 5 6 71 22 6 6 46 21 8 6 20 20 1 5 70 18 4 5 21 2 0 1 0 26 8 7 33 25 1 6 84 23 5 6 35 22 6 6 11 21 8 5 87 20 1 5 40 ...

Страница 51: ...40 50 0 10 20 30 40 50 60 70 80 90 100 110 120 z zHeating 40 30 20 10 0 10 20 30 40 50 0 10 20 30 40 50 60 70 80 90 100 110 120 1 00 0 98 0 96 Height difference H m Outdoor unit Upper Outdoor unit Lower Pipe length L m COMPENSATION COEFFICIENT OF FROSTING DEFROSTING HEATING OPERATION To take the effects of accumulated frost and defrosting operation on heating capacity into consideration the capaci...

Страница 52: ...9 0 8 1 0 0 9 1 1 0 9 1 2 0 9 1 4 1 0 1 5 1 0 15 0 6 0 5 0 7 0 6 0 8 0 7 0 9 0 8 1 0 0 9 1 1 0 9 1 2 0 9 1 4 1 0 1 5 1 0 21 0 6 0 5 0 7 0 6 0 8 0 7 0 9 0 8 1 0 0 9 1 1 0 9 1 2 0 9 1 4 1 0 1 4 1 0 23 0 6 0 5 0 7 0 6 0 8 0 7 0 9 0 8 1 0 0 9 1 1 0 9 1 2 0 9 1 4 1 0 1 4 1 0 25 0 6 0 5 0 7 0 6 0 8 0 7 0 9 0 8 1 0 0 9 1 1 0 9 1 2 0 9 1 4 1 0 1 4 1 0 27 0 6 0 5 0 7 0 6 0 8 0 7 0 9 0 8 1 0 0 9 1 1 0 9 1 2...

Страница 53: ... 2 2 3 7 2 3 23 1 8 1 4 2 1 1 7 2 3 1 8 2 6 2 0 2 8 2 1 3 0 2 1 3 5 2 2 3 6 2 3 25 1 8 1 4 2 1 1 7 2 3 1 8 2 6 2 0 2 8 2 1 3 0 2 1 3 5 2 2 3 5 2 3 27 1 8 1 4 2 1 1 7 2 3 1 8 2 6 2 0 2 8 2 1 3 0 2 1 3 4 2 2 3 5 2 3 30 1 8 1 4 2 1 1 7 2 3 1 8 2 6 2 0 2 8 2 1 3 0 2 1 3 4 2 1 3 4 2 2 33 1 8 1 4 2 1 1 7 2 3 1 8 2 6 2 0 2 8 2 1 3 0 2 1 3 3 2 1 3 3 2 2 35 1 8 1 4 2 1 1 7 2 3 1 8 2 6 2 0 2 8 2 1 3 0 2 1 3...

Страница 54: ... 4 2 7 3 4 4 23 3 7 2 6 4 2 3 2 4 6 3 4 5 1 3 7 5 6 3 9 6 1 4 0 7 0 4 2 7 2 4 3 25 3 7 2 6 4 2 3 2 4 6 3 4 5 1 3 7 5 6 3 9 6 1 4 0 7 0 4 1 7 1 4 3 27 3 7 2 6 4 2 3 2 4 6 3 4 5 1 3 7 5 6 3 9 6 1 4 0 6 8 4 1 7 0 4 2 30 3 7 2 6 4 2 3 2 4 6 3 4 5 1 3 7 5 6 3 9 6 1 4 0 6 7 4 0 6 8 4 2 33 3 7 2 6 4 2 3 2 4 6 3 4 5 1 3 7 5 6 3 9 6 1 4 0 6 5 4 0 6 7 4 1 35 3 7 2 6 4 2 3 2 4 6 3 4 5 1 3 7 5 6 3 9 6 1 4 0 6...

Страница 55: ... 5 6 4 4 6 1 4 5 7 0 4 6 7 5 5 0 15 3 2 2 5 3 7 3 0 4 2 3 7 4 6 3 9 5 1 4 3 5 6 4 4 6 1 4 5 7 0 4 6 7 5 5 0 21 3 2 2 5 3 7 3 0 4 2 3 7 4 6 3 9 5 1 4 3 5 6 4 4 6 1 4 5 7 0 4 6 7 3 4 9 23 3 2 2 5 3 7 3 0 4 2 3 7 4 6 3 9 5 1 4 3 5 6 4 4 6 1 4 5 7 0 4 6 7 2 4 9 25 3 2 2 5 3 7 3 0 4 2 3 7 4 6 3 9 5 1 4 3 5 6 4 4 6 1 4 5 7 0 4 6 7 1 4 8 27 3 2 2 5 3 7 3 0 4 2 3 7 4 6 3 9 5 1 4 3 5 6 4 4 6 1 4 5 6 8 4 6 ...

Страница 56: ... 7 0 4 3 7 5 4 6 15 3 2 2 3 3 7 2 7 4 2 3 3 4 6 3 5 5 1 3 9 5 6 4 0 6 1 4 1 7 0 4 3 7 5 4 6 21 3 2 2 3 3 7 2 7 4 2 3 3 4 6 3 5 5 1 3 9 5 6 4 0 6 1 4 1 7 0 4 3 7 3 4 5 23 3 2 2 3 3 7 2 7 4 2 3 3 4 6 3 5 5 1 3 9 5 6 4 0 6 1 4 1 7 0 4 3 7 2 4 5 25 3 2 2 3 3 7 2 7 4 2 3 3 4 6 3 5 5 1 3 9 5 6 4 0 6 1 4 1 7 0 4 2 7 1 4 4 27 3 2 2 3 3 7 2 7 4 2 3 3 4 6 3 5 5 1 3 9 5 6 4 0 6 1 4 1 6 8 4 2 7 0 4 4 30 3 2 2...

Страница 57: ...3 4 8 1 15 5 7 4 1 6 6 4 8 7 4 5 9 8 3 6 1 9 1 6 8 10 0 7 0 10 8 7 2 12 5 7 5 13 4 8 1 21 5 7 4 1 6 6 4 8 7 4 5 9 8 3 6 1 9 1 6 8 10 0 7 0 10 8 7 2 12 5 7 5 13 0 7 9 23 5 7 4 1 6 6 4 8 7 4 5 9 8 3 6 1 9 1 6 8 10 0 7 0 10 8 7 2 12 5 7 5 12 8 7 8 25 5 7 4 1 6 6 4 8 7 4 5 9 8 3 6 1 9 1 6 8 10 0 7 0 10 8 7 2 12 4 7 5 12 6 7 8 27 5 7 4 1 6 6 4 8 7 4 5 9 8 3 6 1 9 1 6 8 10 0 7 0 10 8 7 2 12 2 7 4 12 5 7...

Страница 58: ...0 4 8 7 11 6 9 0 12 8 10 0 14 0 10 2 15 2 10 5 17 6 10 9 18 8 11 7 21 8 0 6 0 9 2 7 0 10 4 8 7 11 6 9 0 12 8 10 0 14 0 10 2 15 2 10 5 17 6 10 9 18 3 11 5 23 8 0 6 0 9 2 7 0 10 4 8 7 11 6 9 0 12 8 10 0 14 0 10 2 15 2 10 5 17 6 10 9 18 0 11 4 25 8 0 6 0 9 2 7 0 10 4 8 7 11 6 9 0 12 8 10 0 14 0 10 2 15 2 10 5 17 4 10 9 17 7 11 3 27 8 0 6 0 9 2 7 0 10 4 8 7 11 6 9 0 12 8 10 0 14 0 10 2 15 2 10 5 17 1 ...

Страница 59: ...1 4 2 3 9 4 6 4 1 5 1 4 5 5 6 4 6 5 8 4 6 6 0 4 5 6 1 4 8 46 3 7 3 1 4 2 3 9 4 6 4 1 5 1 4 5 5 5 4 6 5 6 4 5 5 8 4 4 5 9 4 7 MODEL AUXD24GALH Outdoor temperature Indoor temperature 20 CDB 15 CWB 23 CDB 16 CWB 24 CDB 17 CWB 26 CDB 18 CWB 27 CDB 19 CWB 28 CDB 20 CWB 30 CDB 22 CWB 32 CDB 23 CWB CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 10 4 7 3 8 5 3 4 8 5 9 4 9 6 5 5 5 7 1 5 6 7 7 ...

Страница 60: ... 6 2 8 2 6 9 9 0 7 1 9 3 7 0 9 6 6 9 9 8 7 3 46 5 9 4 8 6 7 6 0 7 5 6 2 8 2 6 9 8 8 6 9 9 0 7 0 9 4 6 8 9 5 7 2 Outdoor temperature Indoor temperature 20 CDB 15 CWB 23 CDB 16 CWB 24 CDB 17 CWB 26 CDB 18 CWB 27 CDB 19 CWB 28 CDB 20 CWB 30 CDB 22 CWB 32 CDB 23 CWB CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 10 7 4 5 7 8 3 7 1 9 3 7 4 10 2 8 2 11 2 8 4 12 1 8 6 14 0 8 9 15 0 9 6 15 7 ...

Страница 61: ... 0 10 0 15 2 10 2 17 6 10 7 18 0 11 1 25 9 2 6 8 10 4 8 4 11 6 8 8 12 8 9 7 14 0 10 0 15 2 10 2 17 4 10 6 17 7 11 0 27 9 2 6 8 10 4 8 4 11 6 8 8 12 8 9 7 14 0 10 0 15 2 10 2 17 1 10 5 17 5 10 9 30 9 2 6 8 10 4 8 4 11 6 8 8 12 8 9 7 14 0 10 0 15 2 10 2 16 8 10 4 17 1 10 8 33 9 2 6 8 10 4 8 4 11 6 8 8 12 8 9 7 14 0 10 0 15 2 10 2 16 4 10 2 16 7 10 6 35 9 2 6 8 10 4 8 4 11 6 8 8 12 8 9 7 14 0 10 0 15...

Страница 62: ...1 2 0 9 1 4 0 9 1 5 1 0 15 0 6 0 5 0 7 0 6 0 8 0 7 0 9 0 8 1 0 0 9 1 1 0 9 1 2 0 9 1 4 0 9 1 5 1 0 21 0 6 0 5 0 7 0 6 0 8 0 7 0 9 0 8 1 0 0 9 1 1 0 9 1 2 0 9 1 4 0 9 1 4 1 0 23 0 6 0 5 0 7 0 6 0 8 0 7 0 9 0 8 1 0 0 9 1 1 0 9 1 2 0 9 1 4 0 9 1 4 1 0 25 0 6 0 5 0 7 0 6 0 8 0 7 0 9 0 8 1 0 0 9 1 1 0 9 1 2 0 9 1 4 0 9 1 4 1 0 27 0 6 0 5 0 7 0 6 0 8 0 7 0 9 0 8 1 0 0 9 1 1 0 9 1 2 0 9 1 3 0 9 1 4 1 0 3...

Страница 63: ... 2 1 3 5 2 1 3 7 2 3 23 1 8 1 4 2 1 1 7 2 3 1 8 2 6 1 9 2 8 2 0 3 0 2 1 3 5 2 1 3 6 2 2 25 1 8 1 4 2 1 1 7 2 3 1 8 2 6 1 9 2 8 2 0 3 0 2 1 3 5 2 1 3 5 2 2 27 1 8 1 4 2 1 1 7 2 3 1 8 2 6 1 9 2 8 2 0 3 0 2 1 3 4 2 1 3 5 2 2 30 1 8 1 4 2 1 1 7 2 3 1 8 2 6 1 9 2 8 2 0 3 0 2 1 3 4 2 1 3 4 2 2 33 1 8 1 4 2 1 1 7 2 3 1 8 2 6 1 9 2 8 2 0 3 0 2 1 3 3 2 1 3 3 2 1 35 1 8 1 4 2 1 1 7 2 3 1 8 2 6 1 9 2 8 2 0 3...

Страница 64: ... 4 4 7 3 4 6 23 3 7 2 8 4 2 3 5 4 6 3 6 5 1 4 0 5 6 4 1 6 1 4 2 7 0 4 4 7 2 4 6 25 3 7 2 8 4 2 3 5 4 6 3 6 5 1 4 0 5 6 4 1 6 1 4 2 7 0 4 4 7 1 4 5 27 3 7 2 8 4 2 3 5 4 6 3 6 5 1 4 0 5 6 4 1 6 1 4 2 6 8 4 3 7 0 4 5 30 3 7 2 8 4 2 3 5 4 6 3 6 5 1 4 0 5 6 4 1 6 1 4 2 6 7 4 3 6 8 4 5 33 3 7 2 8 4 2 3 5 4 6 3 6 5 1 4 0 5 6 4 1 6 1 4 2 6 5 4 2 6 7 4 4 35 3 7 2 8 4 2 3 5 4 6 3 6 5 1 4 0 5 6 4 1 6 1 4 2 6...

Страница 65: ...2 43 1 8 1 5 2 1 1 8 2 3 1 9 2 6 2 1 2 8 2 1 2 9 2 1 3 0 2 1 3 1 2 2 46 1 8 1 5 2 1 1 8 2 3 1 9 2 6 2 1 2 8 2 1 2 8 2 1 2 9 2 1 3 0 2 2 MODEL ARXD12GALH Outdoor temperature Indoor temperature 20 CDB 15 CWB 23 CDB 16 CWB 24 CDB 17 CWB 26 CDB 18 CWB 27 CDB 19 CWB 28 CDB 20 CWB 30 CDB 22 CWB 32 CDB 23 CWB CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 10 2 4 1 8 2 7 2 3 3 0 2 4 3 3 2 6 3...

Страница 66: ... 4 6 3 7 5 1 4 1 5 6 4 2 5 8 4 2 6 0 4 1 6 1 4 3 46 3 7 2 9 4 2 3 5 4 6 3 7 5 1 4 1 5 5 4 2 5 6 4 1 5 8 4 0 5 9 4 2 MODEL ARXD24GALH Outdoor temperature Indoor temperature 20 CDB 15 CWB 23 CDB 16 CWB 24 CDB 17 CWB 26 CDB 18 CWB 27 CDB 19 CWB 28 CDB 20 CWB 30 CDB 22 CWB 32 CDB 23 CWB CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 10 4 7 3 9 5 3 4 9 5 9 5 0 6 5 5 6 7 1 5 7 7 7 5 8 8 9 6...

Страница 67: ... 9 3 14 4 9 7 40 8 2 6 4 9 3 7 9 10 4 8 2 11 4 9 0 12 5 9 3 13 2 9 4 13 8 9 2 14 0 9 6 43 8 2 6 4 9 3 7 9 10 4 8 2 11 4 9 0 12 5 9 3 12 9 9 3 13 4 9 0 13 7 9 5 46 8 2 6 4 9 3 7 9 10 4 8 2 11 4 9 0 12 3 9 2 12 5 9 1 13 0 8 9 13 3 9 4 Outdoor temperature Indoor temperature 20 CDB 15 CWB 23 CDB 16 CWB 24 CDB 17 CWB 26 CDB 18 CWB 27 CDB 19 CWB 28 CDB 20 CWB 30 CDB 22 CWB 32 CDB 23 CWB CDB TC SHC TC SH...

Страница 68: ... 4 9 5 11 4 10 5 12 5 10 8 13 5 10 9 15 7 11 3 16 3 12 0 23 8 2 7 3 9 3 9 2 10 4 9 5 11 4 10 5 12 5 10 8 13 5 10 9 15 7 11 3 16 0 11 9 25 8 2 7 3 9 3 9 2 10 4 9 5 11 4 10 5 12 5 10 8 13 5 10 9 15 5 11 2 15 8 11 8 27 8 2 7 3 9 3 9 2 10 4 9 5 11 4 10 5 12 5 10 8 13 5 10 9 15 3 11 1 15 6 11 8 30 8 2 7 3 9 3 9 2 10 4 9 5 11 4 10 5 12 5 10 8 13 5 10 9 15 0 11 0 15 2 11 6 33 8 2 7 3 9 3 9 2 10 4 9 5 11 ...

Страница 69: ... 8 31 3 19 6 32 1 20 5 25 16 4 12 6 18 6 15 6 20 7 16 2 22 9 17 9 25 0 18 4 27 1 18 8 31 1 19 5 31 6 20 3 27 16 4 12 6 18 6 15 6 20 7 16 2 22 9 17 9 25 0 18 4 27 1 18 8 30 5 19 3 31 2 20 2 30 16 4 12 6 18 6 15 6 20 7 16 2 22 9 17 9 25 0 18 4 27 1 18 8 29 9 19 0 30 4 19 9 33 16 4 12 6 18 6 15 6 20 7 16 2 22 9 17 9 25 0 18 4 27 1 18 8 29 2 18 8 29 7 19 6 35 16 4 12 6 18 6 15 6 20 7 16 2 22 9 17 9 25...

Страница 70: ...23 3 2 2 4 3 7 2 8 4 2 3 5 4 6 3 6 5 1 4 0 5 6 4 1 6 1 4 2 7 0 4 4 7 2 4 6 25 3 2 2 4 3 7 2 8 4 2 3 5 4 6 3 6 5 1 4 0 5 6 4 1 6 1 4 2 7 0 4 4 7 1 4 6 27 3 2 2 4 3 7 2 8 4 2 3 5 4 6 3 6 5 1 4 0 5 6 4 1 6 1 4 2 6 8 4 3 7 0 4 5 30 3 2 2 4 3 7 2 8 4 2 3 5 4 6 3 6 5 1 4 0 5 6 4 1 6 1 4 2 6 7 4 3 6 8 4 5 33 3 2 2 4 3 7 2 8 4 2 3 5 4 6 3 6 5 1 4 0 5 6 4 1 6 1 4 2 6 5 4 2 6 7 4 4 35 3 2 2 4 3 7 2 8 4 2 3 ...

Страница 71: ...0 8 1 0 0 8 1 1 0 9 1 2 0 9 1 4 0 9 1 5 1 0 15 0 6 0 5 0 7 0 6 0 8 0 7 0 9 0 8 1 0 0 8 1 1 0 9 1 2 0 9 1 4 0 9 1 5 1 0 21 0 6 0 5 0 7 0 6 0 8 0 7 0 9 0 8 1 0 0 8 1 1 0 9 1 2 0 9 1 4 0 9 1 4 1 0 23 0 6 0 5 0 7 0 6 0 8 0 7 0 9 0 8 1 0 0 8 1 1 0 9 1 2 0 9 1 4 0 9 1 4 1 0 25 0 6 0 5 0 7 0 6 0 8 0 7 0 9 0 8 1 0 0 8 1 1 0 9 1 2 0 9 1 4 0 9 1 4 0 9 27 0 6 0 5 0 7 0 6 0 8 0 7 0 9 0 8 1 0 0 8 1 1 0 9 1 2 0...

Страница 72: ... 1 3 0 2 5 3 3 2 7 3 7 3 0 4 0 3 0 4 1 3 0 4 3 3 0 4 4 3 1 46 2 3 1 8 2 6 2 1 3 0 2 5 3 3 2 7 3 7 3 0 3 9 3 0 4 0 3 0 4 2 2 9 4 2 3 1 Outdoor temperature Indoor temperature 18 CDB 14 CWB 20 CDB 15 CWB 23 CDB 16 CWB 24 CDB 17 CWB 26 CDB 18 CWB 27 CDB 19 CWB 28 CDB 20 CWB 30 CDB 22 CWB 32 CDB 23 CWB CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 15 2 1 1 6 2 4 1 8 2 7 2 3 3 0 2 4...

Страница 73: ...8 0 7 0 9 0 8 1 0 0 8 1 1 0 9 1 2 0 9 1 4 0 9 1 5 1 0 15 0 6 0 5 0 7 0 6 0 8 0 7 0 9 0 8 1 0 0 8 1 1 0 9 1 2 0 9 1 4 0 9 1 5 1 0 21 0 6 0 5 0 7 0 6 0 8 0 7 0 9 0 8 1 0 0 8 1 1 0 9 1 2 0 9 1 4 0 9 1 4 1 0 23 0 6 0 5 0 7 0 6 0 8 0 7 0 9 0 8 1 0 0 8 1 1 0 9 1 2 0 9 1 4 0 9 1 4 1 0 25 0 6 0 5 0 7 0 6 0 8 0 7 0 9 0 8 1 0 0 8 1 1 0 9 1 2 0 9 1 4 0 9 1 4 0 9 27 0 6 0 5 0 7 0 6 0 8 0 7 0 9 0 8 1 0 0 8 1 1...

Страница 74: ... 1 3 0 2 5 3 3 2 7 3 7 3 0 4 0 3 0 4 1 3 0 4 3 3 0 4 4 3 1 46 2 3 1 8 2 6 2 1 3 0 2 5 3 3 2 7 3 7 3 0 3 9 3 0 4 0 3 0 4 2 2 9 4 2 3 1 Outdoor temperature Indoor temperature 18 CDB 14 CWB 20 CDB 15 CWB 23 CDB 16 CWB 24 CDB 17 CWB 26 CDB 18 CWB 27 CDB 19 CWB 28 CDB 20 CWB 30 CDB 22 CWB 32 CDB 23 CWB CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 15 2 1 1 6 2 4 1 8 2 7 2 3 3 0 2 4...

Страница 75: ...4 4 5 9 4 4 6 2 4 4 6 3 4 6 43 3 7 3 0 4 2 3 8 4 6 3 9 5 1 4 3 5 6 4 4 5 8 4 4 6 0 4 3 6 1 4 5 46 3 7 3 0 4 2 3 8 4 6 3 9 5 1 4 3 5 5 4 4 5 6 4 3 5 8 4 2 5 9 4 5 Outdoor temperature Indoor temperature 20 CDB 15 CWB 23 CDB 16 CWB 24 CDB 17 CWB 26 CDB 18 CWB 27 CDB 19 CWB 28 CDB 20 CWB 30 CDB 22 CWB 32 CDB 23 CWB CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 10 3 0 2 4 3 3 3 0 3 7 3 1 ...

Страница 76: ...6 14 1 9 4 14 4 9 8 40 8 2 6 4 9 3 7 9 10 4 8 2 11 4 9 1 12 5 9 4 13 2 9 5 13 8 9 3 14 0 9 7 43 8 2 6 4 9 3 7 9 10 4 8 2 11 4 9 1 12 5 9 4 12 9 9 3 13 4 9 1 13 7 9 6 46 8 2 6 4 9 3 7 9 10 4 8 2 11 4 9 1 12 3 9 3 12 5 9 2 13 0 9 0 13 3 9 5 Outdoor temperature Indoor temperature 20 CDB 15 CWB 23 CDB 16 CWB 24 CDB 17 CWB 26 CDB 18 CWB 27 CDB 19 CWB 28 CDB 20 CWB 30 CDB 22 CWB 32 CDB 23 CWB CDB TC SHC...

Страница 77: ...0 7 1 0 0 8 1 1 0 8 1 2 0 9 1 4 0 9 1 5 1 0 15 0 6 0 5 0 7 0 6 0 8 0 7 0 9 0 7 1 0 0 8 1 1 0 8 1 2 0 9 1 4 0 9 1 5 1 0 21 0 6 0 5 0 7 0 6 0 8 0 7 0 9 0 7 1 0 0 8 1 1 0 8 1 2 0 9 1 4 0 9 1 4 1 0 23 0 6 0 5 0 7 0 6 0 8 0 7 0 9 0 7 1 0 0 8 1 1 0 8 1 2 0 9 1 4 0 9 1 4 0 9 25 0 6 0 5 0 7 0 6 0 8 0 7 0 9 0 7 1 0 0 8 1 1 0 8 1 2 0 9 1 4 0 9 1 4 0 9 27 0 6 0 5 0 7 0 6 0 8 0 7 0 9 0 7 1 0 0 8 1 1 0 8 1 2 0...

Страница 78: ... 2 3 0 2 7 3 3 2 8 3 7 3 1 4 0 3 2 4 1 3 1 4 3 3 1 4 4 3 3 46 2 3 1 8 2 6 2 2 3 0 2 7 3 3 2 8 3 7 3 1 3 9 3 1 4 0 3 1 4 2 3 0 4 2 3 2 Outdoor temperature Indoor temperature 18 CDB 14 CWB 20 CDB 15 CWB 23 CDB 16 CWB 24 CDB 17 CWB 26 CDB 18 CWB 27 CDB 19 CWB 28 CDB 20 CWB 30 CDB 22 CWB 32 CDB 23 CWB CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 10 2 1 1 6 2 4 1 9 2 7 2 3 3 0 2 4...

Страница 79: ... 3 0 2 3 3 3 2 6 3 6 2 7 3 7 2 6 3 9 2 6 3 9 2 7 46 2 4 1 8 2 7 2 3 3 0 2 3 3 3 2 6 3 5 2 6 3 6 2 6 3 8 2 6 3 8 2 7 MODEL AS A14GACH Outdoor temperature Indoor temperature 20 CDB 15 CWB 23 CDB 16 CWB 24 CDB 17 CWB 26 CDB 18 CWB 27 CDB 19 CWB 28 CDB 20 CWB 30 CDB 22 CWB 32 CDB 23 CWB CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 10 3 0 2 2 3 3 2 8 3 7 2 9 4 1 3 2 4 5 3 3 4 9 3 3 5 6 3...

Страница 80: ...7 5 3 4 6 5 9 4 7 6 5 5 2 7 1 5 4 7 3 5 3 7 6 5 2 7 8 5 5 46 4 1 3 1 4 7 3 7 5 3 4 6 5 9 4 7 6 5 5 2 7 0 5 3 7 1 5 3 7 4 5 2 7 5 5 4 Outdoor temperature Indoor temperature 18 CDB 14 CWB 20 CDB 15 CWB 23 CDB 16 CWB 24 CDB 17 CWB 26 CDB 18 CWB 27 CDB 19 CWB 28 CDB 20 CWB 30 CDB 22 CWB 32 CDB 23 CWB CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 15 3 2 2 4 3 7 2 9 4 2 3 5 4 6 3 7 ...

Страница 81: ... 7 4 4 6 6 5 2 7 4 6 5 8 3 6 7 9 1 7 4 10 0 7 6 10 3 7 5 10 7 7 4 10 9 7 8 46 5 7 4 4 6 6 5 2 7 4 6 5 8 3 6 7 9 1 7 4 9 8 7 5 10 0 7 4 10 4 7 3 10 6 7 7 Outdoor temperature Indoor temperature 18 CDB 14 CWB 20 CDB 15 CWB 23 CDB 16 CWB 24 CDB 17 CWB 26 CDB 18 CWB 27 CDB 19 CWB 28 CDB 20 CWB 30 CDB 22 CWB 32 CDB 23 CWB CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 15 5 2 3 9 5 9 ...

Страница 82: ...8 0 7 0 9 0 7 1 0 0 8 1 1 0 8 1 2 0 9 1 4 0 9 1 5 1 0 15 0 6 0 5 0 7 0 6 0 8 0 7 0 9 0 7 1 0 0 8 1 1 0 8 1 2 0 9 1 4 0 9 1 5 1 0 21 0 6 0 5 0 7 0 6 0 8 0 7 0 9 0 7 1 0 0 8 1 1 0 8 1 2 0 9 1 4 0 9 1 4 1 0 23 0 6 0 5 0 7 0 6 0 8 0 7 0 9 0 7 1 0 0 8 1 1 0 8 1 2 0 9 1 4 0 9 1 4 0 9 25 0 6 0 5 0 7 0 6 0 8 0 7 0 9 0 7 1 0 0 8 1 1 0 8 1 2 0 9 1 4 0 9 1 4 0 9 27 0 6 0 5 0 7 0 6 0 8 0 7 0 9 0 7 1 0 0 8 1 1...

Страница 83: ... 2 3 0 2 7 3 3 2 8 3 7 3 1 4 0 3 2 4 1 3 1 4 3 3 1 4 4 3 3 46 2 3 1 8 2 6 2 2 3 0 2 7 3 3 2 8 3 7 3 1 3 9 3 1 4 0 3 1 4 2 3 0 4 2 3 2 Outdoor temperature Indoor temperature 18 CDB 14 CWB 20 CDB 15 CWB 23 CDB 16 CWB 24 CDB 17 CWB 26 CDB 18 CWB 27 CDB 19 CWB 28 CDB 20 CWB 30 CDB 22 CWB 32 CDB 23 CWB CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 10 2 1 1 6 2 4 1 9 2 7 2 3 3 0 2 4...

Страница 84: ... 3 0 2 4 3 3 2 7 3 6 2 7 3 7 2 7 3 9 2 7 3 9 2 8 46 2 4 1 9 2 7 2 3 3 0 2 4 3 3 2 7 3 5 2 7 3 6 2 7 3 8 2 6 3 8 2 8 MODEL AS E14GACH Outdoor temperature Indoor temperature 20 CDB 15 CWB 23 CDB 16 CWB 24 CDB 17 CWB 26 CDB 18 CWB 27 CDB 19 CWB 28 CDB 20 CWB 30 CDB 22 CWB 32 CDB 23 CWB CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 10 3 0 2 3 3 3 2 8 3 7 3 0 4 1 3 3 4 5 3 4 4 9 3 4 5 6 3...

Страница 85: ... 2 8 2 7 2 6 2 4 2 2 9 0 7 8 3 2 3 0 2 8 2 7 2 6 2 4 2 2 12 0 10 6 3 2 3 0 2 8 2 7 2 6 2 4 2 2 15 0 13 5 3 2 3 0 2 8 2 7 2 6 2 4 2 2 MODEL AUXB09GALH Outdoor Temperature Indoor temperature 16 CDB 18 CDB 20 CDB 21 CDB 22 CDB 24 CDB 26 CDB CDB CWB TC TC TC TC TC TC TC 19 3 20 0 1 7 1 7 1 7 1 7 1 6 1 6 1 6 15 0 16 0 1 9 1 9 1 9 1 9 1 9 1 9 1 9 12 0 13 0 2 1 2 1 2 1 2 1 2 1 2 1 2 1 9 0 10 0 2 4 2 3 2 ...

Страница 86: ...4 2 4 2 4 2 4 2 4 1 4 1 9 0 10 0 4 6 4 6 4 6 4 6 4 6 4 5 4 5 7 0 8 0 4 9 4 9 4 9 4 9 4 8 4 8 4 8 5 0 6 0 5 2 5 2 5 2 5 1 5 1 5 1 5 0 3 0 4 0 5 5 5 5 5 4 5 4 5 4 5 4 5 0 1 0 2 0 5 8 5 8 5 7 5 7 5 7 5 4 5 0 0 0 1 0 5 9 5 9 5 9 5 8 5 8 5 4 5 0 2 0 1 0 6 2 6 2 6 2 6 0 5 8 5 4 5 0 5 0 4 0 6 7 6 7 6 3 6 1 5 9 5 5 5 0 7 0 6 0 7 0 6 7 6 3 6 1 5 9 5 5 5 0 9 0 7 8 7 1 6 7 6 3 6 1 5 9 5 5 5 0 12 0 10 6 7 1 6...

Страница 87: ... 8 4 7 4 7 12 0 13 0 5 4 5 3 5 3 5 3 5 3 5 3 5 2 9 0 10 0 5 9 5 9 5 8 5 8 5 8 5 8 5 7 7 0 8 0 6 2 6 2 6 2 6 2 6 1 6 1 6 1 5 0 6 0 6 6 6 6 6 6 6 5 6 5 6 5 6 3 3 0 4 0 7 0 6 9 6 9 6 9 6 9 6 8 6 3 1 0 2 0 7 4 7 3 7 3 7 2 7 2 6 9 6 3 0 0 1 0 7 5 7 5 7 4 7 4 7 4 6 9 6 3 2 0 1 0 7 9 7 9 7 8 7 7 7 4 6 9 6 3 5 0 4 0 8 5 8 5 8 0 7 7 7 5 6 9 6 4 7 0 6 0 8 9 8 5 8 0 7 7 7 5 6 9 6 4 9 0 7 8 9 1 8 5 8 0 7 7 7 ...

Страница 88: ... 0 13 5 9 1 8 5 8 0 7 7 7 5 6 9 6 4 MODEL AUXK030GLAH Outdoor Temperature Indoor temperature 16 CDB 18 CDB 20 CDB 21 CDB 22 CDB 24 CDB 26 CDB CDB CWB TC TC TC TC TC TC TC 19 3 20 0 5 2 5 2 5 2 5 2 5 1 5 1 5 1 15 0 16 0 6 0 6 0 6 0 6 0 6 0 5 9 5 9 12 0 13 0 6 7 6 7 6 6 6 6 6 6 6 6 6 5 9 0 10 0 7 4 7 3 7 3 7 3 7 2 7 2 7 2 7 0 8 0 7 8 7 8 7 7 7 7 7 7 7 7 7 6 5 0 6 0 8 3 8 2 8 2 8 2 8 1 8 1 7 9 3 0 4 ...

Страница 89: ...7 5 0 6 0 11 6 11 5 11 5 11 4 11 4 11 3 11 0 3 0 4 0 12 2 12 1 12 1 12 0 12 0 12 0 11 1 1 0 2 0 12 9 12 8 12 7 12 7 12 6 12 0 11 1 0 0 1 0 13 2 13 1 13 0 13 0 12 9 12 0 11 1 2 0 1 0 13 9 13 8 13 7 13 4 13 0 12 0 11 1 5 0 4 0 14 9 14 8 14 0 13 5 13 1 12 1 11 2 7 0 6 0 15 5 14 9 14 0 13 5 13 1 12 1 11 2 9 0 7 8 15 9 14 9 14 0 13 5 13 1 12 1 11 2 12 0 10 6 15 9 14 9 14 0 13 5 13 1 12 1 11 2 15 0 13 5...

Страница 90: ... 7 7 5 6 9 6 4 9 0 7 8 9 1 8 5 8 0 7 7 7 5 6 9 6 4 12 0 10 6 9 1 8 5 8 0 7 7 7 5 6 9 6 4 15 0 13 5 9 1 8 5 8 0 7 7 7 5 6 9 6 4 Outdoor Temperature Indoor temperature 16 CDB 18 CDB 20 CDB 21 CDB 22 CDB 24 CDB 26 CDB CDB CWB TC TC TC TC TC TC TC 19 3 20 0 3 3 3 3 3 3 3 3 3 2 3 2 3 2 15 0 16 0 3 8 3 8 3 8 3 8 3 8 3 7 3 7 12 0 13 0 4 2 4 2 4 2 4 2 4 2 4 1 4 1 9 0 10 0 4 6 4 6 4 6 4 6 4 6 4 5 4 5 7 0 8...

Страница 91: ...0 9 10 5 9 7 9 0 MODEL AUXA36GALH Outdoor Temperature Indoor temperature 16 CDB 18 CDB 20 CDB 21 CDB 22 CDB 24 CDB 26 CDB CDB CWB TC TC TC TC TC TC TC 19 3 20 0 6 5 6 5 6 5 6 5 6 4 6 4 6 4 15 0 16 0 7 5 7 5 7 5 7 5 7 5 7 4 7 4 12 0 13 0 8 4 8 3 8 3 8 3 8 3 8 2 8 2 9 0 10 0 9 2 9 2 9 1 9 1 9 0 9 0 9 0 7 0 8 0 9 8 9 7 9 6 9 6 9 6 9 6 9 5 5 0 6 0 10 3 10 3 10 2 10 2 10 2 10 1 9 8 3 0 4 0 10 9 10 8 10...

Страница 92: ...6 11 5 11 5 7 0 8 0 12 5 12 4 12 3 12 3 12 3 12 2 12 2 5 0 6 0 13 2 13 2 13 1 13 1 13 0 13 0 12 6 3 0 4 0 14 0 13 9 13 8 13 8 13 7 13 7 12 6 1 0 2 0 14 7 14 6 14 5 14 5 14 4 13 7 12 6 0 0 1 0 15 1 15 0 14 9 14 8 14 8 13 7 12 6 2 0 1 0 15 8 15 7 15 6 15 3 14 8 13 8 12 7 5 0 4 0 17 0 16 9 16 0 15 4 14 9 13 9 12 8 7 0 6 0 17 7 17 0 16 0 15 4 14 9 13 9 12 8 9 0 7 8 18 1 17 0 16 0 15 4 14 9 13 9 12 8 1...

Страница 93: ...0 10 6 3 2 3 0 2 8 2 7 2 6 2 4 2 2 15 0 13 5 3 2 3 0 2 8 2 7 2 6 2 4 2 2 MODEL ARXK09GCLH Outdoor Temperature Indoor temperature 16 CDB 18 CDB 20 CDB 21 CDB 22 CDB 24 CDB 26 CDB CDB CWB TC TC TC TC TC TC TC 19 3 20 0 1 7 1 7 1 7 1 7 1 6 1 6 1 6 15 0 16 0 1 9 1 9 1 9 1 9 1 9 1 9 1 9 12 0 13 0 2 1 2 1 2 1 2 1 2 1 2 1 2 1 9 0 10 0 2 4 2 3 2 3 2 3 2 3 2 3 2 3 7 0 8 0 2 5 2 5 2 5 2 5 2 5 2 4 2 4 5 0 6 ...

Страница 94: ...5 4 5 7 0 8 0 4 9 4 9 4 9 4 9 4 8 4 8 4 8 5 0 6 0 5 2 5 2 5 2 5 1 5 1 5 1 5 0 3 0 4 0 5 5 5 5 5 4 5 4 5 4 5 4 5 0 1 0 2 0 5 8 5 8 5 7 5 7 5 7 5 4 5 0 0 0 1 0 5 9 5 9 5 9 5 8 5 8 5 4 5 0 2 0 1 0 6 2 6 2 6 2 6 0 5 8 5 4 5 0 5 0 4 0 6 7 6 7 6 3 6 1 5 9 5 5 5 0 7 0 6 0 7 0 6 7 6 3 6 1 5 9 5 5 5 0 9 0 7 8 7 1 6 7 6 3 6 1 5 9 5 5 5 0 12 0 10 6 7 1 6 7 6 3 6 1 5 9 5 5 5 0 15 0 13 5 7 1 6 7 6 3 6 1 5 9 5 ...

Страница 95: ... 2 8 2 6 9 0 7 8 3 6 3 4 3 2 3 1 3 0 2 8 2 6 12 0 10 6 3 6 3 4 3 2 3 1 3 0 2 8 2 6 15 0 13 5 3 6 3 4 3 2 3 1 3 0 2 8 2 6 MODEL ARXD12GALH Outdoor Temperature Indoor temperature 16 CDB 18 CDB 20 CDB 21 CDB 22 CDB 24 CDB 26 CDB CDB CWB TC TC TC TC TC TC TC 19 3 20 0 2 1 2 1 2 1 2 1 2 1 2 1 2 0 15 0 16 0 2 4 2 4 2 4 2 4 2 4 2 4 2 4 12 0 13 0 2 7 2 7 2 7 2 6 2 6 2 6 2 6 9 0 10 0 2 9 2 9 2 9 2 9 2 9 2 ...

Страница 96: ... 6 7 6 3 6 1 5 9 5 5 5 0 12 0 10 6 7 1 6 7 6 3 6 1 5 9 5 5 5 0 15 0 13 5 7 1 6 7 6 3 6 1 5 9 5 5 5 0 MODEL ARXD24GALH Outdoor Temperature Indoor temperature 16 CDB 18 CDB 20 CDB 21 CDB 22 CDB 24 CDB 26 CDB CDB CWB TC TC TC TC TC TC TC 19 3 20 0 4 2 4 1 4 1 4 1 4 1 4 1 4 1 15 0 16 0 4 8 4 8 4 8 4 8 4 8 4 7 4 7 12 0 13 0 5 4 5 3 5 3 5 3 5 3 5 3 5 2 9 0 10 0 5 9 5 9 5 8 5 8 5 8 5 8 5 7 7 0 8 0 6 2 6 ...

Страница 97: ... 3 8 7 8 0 7 0 6 0 11 1 10 6 10 0 9 7 9 3 8 7 8 0 9 0 7 8 11 3 10 6 10 0 9 7 9 3 8 7 8 0 12 0 10 6 11 3 10 7 10 0 9 7 9 3 8 7 8 0 15 0 13 5 11 3 10 7 10 0 9 7 9 3 8 7 8 0 Outdoor Temperature Indoor temperature 16 CDB 18 CDB 20 CDB 21 CDB 22 CDB 24 CDB 26 CDB CDB CWB TC TC TC TC TC TC TC 19 3 20 0 6 5 6 5 6 5 6 5 6 4 6 4 6 4 15 0 16 0 7 5 7 5 7 5 7 5 7 5 7 4 7 4 12 0 13 0 8 4 8 3 8 3 8 3 8 3 8 2 8 ...

Страница 98: ... 3 9 2 9 2 9 2 9 2 9 0 10 0 10 3 10 3 10 2 10 2 10 1 10 1 10 0 7 0 8 0 10 9 10 9 10 8 10 8 10 8 10 7 10 7 5 0 6 0 11 6 11 5 11 5 11 4 11 4 11 3 11 0 3 0 4 0 12 2 12 1 12 1 12 0 12 0 12 0 11 1 1 0 2 0 12 9 12 8 12 7 12 7 12 6 12 0 11 1 0 0 1 0 13 2 13 1 13 0 13 0 12 9 12 0 11 1 2 0 1 0 13 9 13 8 13 7 13 4 13 0 12 0 11 1 5 0 4 0 14 9 14 8 14 0 13 5 13 1 12 1 11 2 7 0 6 0 15 5 14 9 14 0 13 5 13 1 12 ...

Страница 99: ... 20 6 20 5 20 4 20 4 20 3 20 2 20 1 7 0 8 0 21 9 21 8 21 6 21 6 21 5 21 4 21 3 5 0 6 0 23 1 23 0 22 9 22 8 22 8 22 7 22 0 3 0 4 0 24 4 24 3 24 2 24 1 24 0 23 9 22 1 1 0 2 0 25 8 25 6 25 4 25 3 25 2 24 0 22 1 0 0 1 0 26 4 26 2 26 0 26 0 25 9 24 0 22 1 2 0 1 0 27 7 27 6 27 4 26 8 26 0 24 1 22 2 5 0 4 0 29 8 29 6 28 0 27 0 26 1 24 3 22 4 7 0 6 0 31 0 29 8 28 0 27 0 26 1 24 3 22 4 9 0 7 8 31 7 29 8 28...

Страница 100: ... 4 7 4 7 12 0 13 0 5 4 5 3 5 3 5 3 5 3 5 3 5 2 9 0 10 0 5 9 5 9 5 8 5 8 5 8 5 8 5 7 7 0 8 0 6 2 6 2 6 2 6 2 6 1 6 1 6 1 5 0 6 0 6 6 6 6 6 6 6 5 6 5 6 5 6 3 3 0 4 0 7 0 6 9 6 9 6 9 6 9 6 8 6 3 1 0 2 0 7 4 7 3 7 3 7 2 7 2 6 9 6 3 0 0 1 0 7 5 7 5 7 4 7 4 7 4 6 9 6 3 2 0 1 0 7 9 7 9 7 8 7 7 7 4 6 9 6 3 5 0 4 0 8 5 8 5 8 0 7 7 7 5 6 9 6 4 7 0 6 0 8 9 8 5 8 0 7 7 7 5 6 9 6 4 9 0 7 8 9 1 8 5 8 0 7 7 7 5 ...

Страница 101: ... 7 0 6 0 3 5 3 4 3 2 3 1 3 0 2 8 2 6 9 0 7 8 3 6 3 4 3 2 3 1 3 0 2 8 2 6 12 0 10 6 3 6 3 4 3 2 3 1 3 0 2 8 2 6 15 0 13 5 3 6 3 4 3 2 3 1 3 0 2 8 2 6 Outdoor Temperature Indoor temperature 16 CDB 18 CDB 20 CDB 21 CDB 22 CDB 24 CDB 26 CDB CDB CWB TC TC TC TC TC TC TC 19 3 20 0 1 5 1 4 1 4 1 4 1 4 1 4 1 4 15 0 16 0 1 7 1 7 1 7 1 7 1 7 1 7 1 7 12 0 13 0 1 9 1 9 1 9 1 8 1 8 1 8 1 8 9 0 10 0 2 1 2 1 2 0...

Страница 102: ... 0 2 9 9 0 10 0 3 3 3 3 3 3 3 3 3 3 3 2 3 2 7 0 8 0 3 5 3 5 3 5 3 5 3 5 3 4 3 4 5 0 6 0 3 7 3 7 3 7 3 7 3 7 3 6 3 5 3 0 4 0 3 9 3 9 3 9 3 9 3 9 3 8 3 6 1 0 2 0 4 1 4 1 4 1 4 1 4 1 3 9 3 6 0 0 1 0 4 2 4 2 4 2 4 2 4 2 3 9 3 6 2 0 1 0 4 5 4 4 4 4 4 3 4 2 3 9 3 6 5 0 4 0 4 8 4 8 4 5 4 3 4 2 3 9 3 6 7 0 6 0 5 0 4 8 4 5 4 3 4 2 3 9 3 6 9 0 7 8 5 1 4 8 4 5 4 3 4 2 3 9 3 6 12 0 10 6 5 1 4 8 4 5 4 3 4 2 3 ...

Страница 103: ... 0 2 8 2 6 7 0 6 0 3 5 3 4 3 2 3 1 3 0 2 8 2 6 9 0 7 8 3 6 3 4 3 2 3 1 3 0 2 8 2 6 12 0 10 6 3 6 3 4 3 2 3 1 3 0 2 8 2 6 15 0 13 5 3 6 3 4 3 2 3 1 3 0 2 8 2 6 Outdoor Temperature Indoor temperature 16 CDB 18 CDB 20 CDB 21 CDB 22 CDB 24 CDB 26 CDB CDB CWB TC TC TC TC TC TC TC 19 3 20 0 1 5 1 4 1 4 1 4 1 4 1 4 1 4 15 0 16 0 1 7 1 7 1 7 1 7 1 7 1 7 1 7 12 0 13 0 1 9 1 9 1 9 1 8 1 8 1 8 1 8 9 0 10 0 2...

Страница 104: ... 0 2 9 9 0 10 0 3 3 3 3 3 3 3 3 3 3 3 2 3 2 7 0 8 0 3 5 3 5 3 5 3 5 3 5 3 4 3 4 5 0 6 0 3 7 3 7 3 7 3 7 3 7 3 6 3 5 3 0 4 0 3 9 3 9 3 9 3 9 3 9 3 8 3 6 1 0 2 0 4 1 4 1 4 1 4 1 4 1 3 9 3 6 0 0 1 0 4 2 4 2 4 2 4 2 4 2 3 9 3 6 2 0 1 0 4 5 4 4 4 4 4 3 4 2 3 9 3 6 5 0 4 0 4 8 4 8 4 5 4 3 4 2 3 9 3 6 7 0 6 0 5 0 4 8 4 5 4 3 4 2 3 9 3 6 9 0 7 8 5 1 4 8 4 5 4 3 4 2 3 9 3 6 12 0 10 6 5 1 4 8 4 5 4 3 4 2 3 ...

Страница 105: ... 0 6 0 7 0 6 7 6 3 6 1 5 9 5 5 5 0 9 0 7 8 7 1 6 7 6 3 6 1 5 9 5 5 5 0 12 0 10 6 7 1 6 7 6 3 6 1 5 9 5 5 5 0 15 0 13 5 7 1 6 7 6 3 6 1 5 9 5 5 5 0 Outdoor Temperature Indoor temperature 16 CDB 18 CDB 20 CDB 21 CDB 22 CDB 24 CDB 26 CDB CDB CWB TC TC TC TC TC TC TC 19 3 20 0 2 6 2 6 2 6 2 6 2 6 2 6 2 6 15 0 16 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0 12 0 13 0 3 3 3 3 3 3 3 3 3 3 3 3 3 3 9 0 10 0 3 7 3 7 3 6 3...

Страница 106: ... 13 1 12 1 11 2 7 0 6 0 15 5 14 9 14 0 13 5 13 1 12 1 11 2 9 0 7 8 15 9 14 9 14 0 13 5 13 1 12 1 11 2 12 0 10 6 15 9 14 9 14 0 13 5 13 1 12 1 11 2 15 0 13 5 15 9 14 9 14 0 13 5 13 1 12 1 11 2 Outdoor Temperature Indoor temperature 16 CDB 18 CDB 20 CDB 21 CDB 22 CDB 24 CDB 26 CDB CDB CWB TC TC TC TC TC TC TC 19 3 20 0 6 5 6 5 6 5 6 5 6 4 6 4 6 4 15 0 16 0 7 5 7 5 7 5 7 5 7 5 7 4 7 4 12 0 13 0 8 4 8...

Страница 107: ...2 0 13 0 1 9 1 9 1 9 1 8 1 8 1 8 1 8 9 0 10 0 2 1 2 1 2 0 2 0 2 0 2 0 2 0 7 0 8 0 2 2 2 2 2 2 2 2 2 2 2 1 2 1 5 0 6 0 2 3 2 3 2 3 2 3 2 3 2 3 2 2 3 0 4 0 2 4 2 4 2 4 2 4 2 4 2 4 2 2 1 0 2 0 2 6 2 6 2 5 2 5 2 5 2 4 2 2 0 0 1 0 2 6 2 6 2 6 2 6 2 6 2 4 2 2 2 0 1 0 2 8 2 8 2 7 2 7 2 6 2 4 2 2 5 0 4 0 3 0 3 0 2 8 2 7 2 6 2 4 2 2 7 0 6 0 3 1 3 0 2 8 2 7 2 6 2 4 2 2 9 0 7 8 3 2 3 0 2 8 2 7 2 6 2 4 2 2 12...

Страница 108: ... 9 3 6 9 0 7 8 5 1 4 8 4 5 4 3 4 2 3 9 3 6 12 0 10 6 5 1 4 8 4 5 4 3 4 2 3 9 3 6 15 0 13 5 5 1 4 8 4 5 4 3 4 2 3 9 3 6 Outdoor Temperature Indoor temperature 16 CDB 18 CDB 20 CDB 21 CDB 22 CDB 24 CDB 26 CDB CDB CWB TC TC TC TC TC TC TC 19 3 20 0 2 1 2 1 2 1 2 1 2 1 2 1 2 0 15 0 16 0 2 4 2 4 2 4 2 4 2 4 2 4 2 4 12 0 13 0 2 7 2 7 2 7 2 6 2 6 2 6 2 6 9 0 10 0 2 9 2 9 2 9 2 9 2 9 2 9 2 9 7 0 8 0 3 1 3...

Страница 109: ... 4 4 4 1 4 0 3 8 3 6 3 3 12 0 10 6 4 6 4 4 4 1 4 0 3 8 3 6 3 3 15 0 13 5 4 6 4 4 4 1 4 0 3 8 3 6 3 3 MODEL AS A14GACH Outdoor Temperature Indoor temperature 16 CDB 18 CDB 20 CDB 21 CDB 22 CDB 24 CDB 26 CDB CDB CWB TC TC TC TC TC TC TC 19 3 20 0 2 6 2 6 2 6 2 6 2 6 2 6 2 6 15 0 16 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0 12 0 13 0 3 3 3 3 3 3 3 3 3 3 3 3 3 3 9 0 10 0 3 7 3 7 3 6 3 6 3 6 3 6 3 6 7 0 8 0 3 9 3 ...

Страница 110: ...9 6 4 9 0 7 8 9 1 8 5 8 0 7 7 7 5 6 9 6 4 12 0 10 6 9 1 8 5 8 0 7 7 7 5 6 9 6 4 15 0 13 5 9 1 8 5 8 0 7 7 7 5 6 9 6 4 Outdoor Temperature Indoor temperature 16 CDB 18 CDB 20 CDB 21 CDB 22 CDB 24 CDB 26 CDB CDB CWB TC TC TC TC TC TC TC 19 3 20 0 3 3 3 3 3 3 3 3 3 2 3 2 3 2 15 0 16 0 3 8 3 8 3 8 3 8 3 8 3 7 3 7 12 0 13 0 4 2 4 2 4 2 4 2 4 2 4 1 4 1 9 0 10 0 4 6 4 6 4 6 4 6 4 6 4 5 4 5 7 0 8 0 4 9 4 ...

Страница 111: ... 9 0 9 0 7 8 12 7 11 9 11 2 10 8 10 5 9 7 9 0 12 0 10 6 12 7 11 9 11 2 10 8 10 5 9 7 9 0 15 0 13 5 12 7 11 9 11 2 10 8 10 5 9 7 9 0 Outdoor Temperature Indoor temperature 16 CDB 18 CDB 20 CDB 21 CDB 22 CDB 24 CDB 26 CDB CDB CWB TC TC TC TC TC TC TC 19 3 20 0 5 2 5 2 5 2 5 2 5 1 5 1 5 1 15 0 16 0 6 0 6 0 6 0 6 0 6 0 5 9 5 9 12 0 13 0 6 7 6 7 6 6 6 6 6 6 6 6 6 5 9 0 10 0 7 4 7 3 7 3 7 3 7 2 7 2 7 2 ...

Страница 112: ...1 7 1 7 12 0 13 0 1 9 1 9 1 9 1 8 1 8 1 8 1 8 9 0 10 0 2 1 2 1 2 0 2 0 2 0 2 0 2 0 7 0 8 0 2 2 2 2 2 2 2 2 2 2 2 1 2 1 5 0 6 0 2 3 2 3 2 3 2 3 2 3 2 3 2 2 3 0 4 0 2 4 2 4 2 4 2 4 2 4 2 4 2 2 1 0 2 0 2 6 2 6 2 5 2 5 2 5 2 4 2 2 0 0 1 0 2 6 2 6 2 6 2 6 2 6 2 4 2 2 2 0 1 0 2 8 2 8 2 7 2 7 2 6 2 4 2 2 5 0 4 0 3 0 3 0 2 8 2 7 2 6 2 4 2 2 7 0 6 0 3 1 3 0 2 8 2 7 2 6 2 4 2 2 9 0 7 8 3 2 3 0 2 8 2 7 2 6 2...

Страница 113: ... 9 3 6 9 0 7 8 5 1 4 8 4 5 4 3 4 2 3 9 3 6 12 0 10 6 5 1 4 8 4 5 4 3 4 2 3 9 3 6 15 0 13 5 5 1 4 8 4 5 4 3 4 2 3 9 3 6 Outdoor Temperature Indoor temperature 16 CDB 18 CDB 20 CDB 21 CDB 22 CDB 24 CDB 26 CDB CDB CWB TC TC TC TC TC TC TC 19 3 20 0 2 1 2 1 2 1 2 1 2 1 2 1 2 0 15 0 16 0 2 4 2 4 2 4 2 4 2 4 2 4 2 4 12 0 13 0 2 7 2 7 2 7 2 6 2 6 2 6 2 6 9 0 10 0 2 9 2 9 2 9 2 9 2 9 2 9 2 9 7 0 8 0 3 1 3...

Страница 114: ... 4 4 4 1 4 0 3 8 3 6 3 3 12 0 10 6 4 6 4 4 4 1 4 0 3 8 3 6 3 3 15 0 13 5 4 6 4 4 4 1 4 0 3 8 3 6 3 3 MODEL AS E14GACH Outdoor Temperature Indoor temperature 16 CDB 18 CDB 20 CDB 21 CDB 22 CDB 24 CDB 26 CDB CDB CWB TC TC TC TC TC TC TC 19 3 20 0 2 6 2 6 2 6 2 6 2 6 2 6 2 6 15 0 16 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0 12 0 13 0 3 3 3 3 3 3 3 3 3 3 3 3 3 3 9 0 10 0 3 7 3 7 3 6 3 6 3 6 3 6 3 6 7 0 8 0 3 9 3 ...

Страница 115: ...3 OUTDOOR UNITS DTV_J3LE050E_02 CHAPTER03 2017 07 21 ...

Страница 116: ...TDOOR UNIT INSTALLATION 03 05 3 2 MULTIPLE OUTDOOR UNIT INSTALLATION 03 06 3 3 OUTDOOR UNITS INSTALLATION IN MULTI ROW 03 06 3 4 DUCT INSTALLATION 03 08 4 REFRIGERANT CIRCUIT 03 10 5 WIRING DIAGRAM 03 12 6 OPERATION RANGE 03 14 7 NOISE LEVEL CURVE 03 15 8 ELECTRIC CHARACTERISTICS 03 18 9 SAFETY DEVICES 03 19 ...

Страница 117: ...20 30 30 Motor Type Quantity DC motor 2 Output W 111 x 2 200 x 2 Sound power level Cooling dB A 66 69 73 Heating Sound pressure level Cooling dB A 52 54 59 Heating 54 57 61 Heat exchanger Length mm 1 293 Fin pitch 1 45 Rows Stages 2 x 66 2 6 x 66 Pipe type Material Grooved H pin Copper Fin Type Material Corrugate Aluminium Surface treatment Corrosion Resistance Blue Fin Compressor Type Quantity Sc...

Страница 118: ... Unit mm 2 DIMENSIONS MODELS AJ 072LELAH AJ 090LELAH AJ 108LELAH Top view Front view Rear view Side view Bottom view 03 02 OUTDOOR UNITS OUTDOOR UNITS ...

Страница 119: ... Unit mm Detail B Detail A Detail C 03 03 OUTDOOR UNITS OUTDOOR UNITS ...

Страница 120: ... Unit mm CENTER OF GRAVITY POSITION z zModel AJ 072LELAH Center of gravity z zModels AJ 090LELAH AJ 108LELAH Center of gravity 03 04 OUTDOOR UNITS OUTDOOR UNITS ...

Страница 121: ...ould cause a short circuit and result in a lack of operating performance As a result the outdoor unit might easily be stopped by high pressure protection When there is a wall at the right side of the unit provide a space of 100mm or more Air intake Rear Front Installation methods not shown in the following examples are not recommended Performance may drop significantly 3 1 SINGLE OUTDOOR UNIT INST...

Страница 122: ...PWARD AREA IS OPEN z z Obstacles at rear only Obstacles at front only Obstacles at front and rear only 300 or more 1500 or more 500 or more 1500 or more WHEN AN OBSTRUCTION IS PRESENT ALSO IN THE UPWARD AREA z zObstacles at rear and above only 1500 or more 500 or more Max 300 1500 or more 3 3 OUTDOOR UNITS INSTALLATION IN MULTI ROW The following settings are not recommended in case of cooling by a...

Страница 123: ... may freeze in extremely cold climate For reverse cycle model only In area with heavy snowfall if the inlet and outlet of the outdoor unit is blocked with snow it might become difficult to get warm and it is likely to cause product malfunction Construct a canopy and a pedestal or place the unit on a high stand that is locally installed 03 07 OUTDOOR UNITS OUTDOOR UNITS ...

Страница 124: ...b ABOUT THE DUCT The duct needs to be purchased locally When installing the duct be careful of the followings Do not cover the service panel If covered the panel cannot be opened for servicing Screw holes for installing the duct are placed on the front panel Fix the duct by using a ø5 tapping screw See the following diagram for the location Front panel Top panel Servis panel X1 Remove the screw se...

Страница 125: ... DUCT INSTALLATION EXAMPLE Detail A Front panel Detail A Service panel Service panel Do not cover the Service panel 03 09 OUTDOOR UNITS OUTDOOR UNITS ...

Страница 126: ...INE FAN21 FAN21 Indoor unit1 HEX21 HEX21 Indoor unit2 GAS LINE TH21 TH22 TH23 TH23 TH21 TH22 CMP INV OS HEX SCHEX HPS FAN1 LPS EEV1 EEV2 TH1 TH3 TH4 TH5 TH7 TH9 TH10 HPSW FAN2 ACM Check valve Capillary Strainer 3 way valve Service port Pressure regulation valve 4WV 03 10 OUTDOOR UNITS OUTDOOR UNITS ...

Страница 127: ... Marking Tube TH 1 Discharge temperature thermistor Blue TH 3 Outdoor temperature thermistor TH 4 Suction temperature thermistor Red TH 5 Heat exchanger outlet thermistor Brown TH 7 Liquid temperature thermistor Green TH 9 Sub cool heat exchanger outlet thermistor White TH 10 Compressor temperature thermistor z zIndoor unit MARK DESCRIPTION HEX 21 Heat exchanger FAN 21 Fan EEV 21 Electric expansio...

Страница 128: ...5 WIRING DIAGRAM MODELS AJ 072LELAH AJ 090LELAH 03 12 OUTDOOR UNITS OUTDOOR UNITS ...

Страница 129: ... MODEL AJ 108LELAH 03 13 OUTDOOR UNITS OUTDOOR UNITS ...

Страница 130: ...ON RANGE Operation mode Operation range Indoor unit Outdoor unit Cooling Dry 18 to 32 C DB R H 80 or less 15 to 46 C DB Heating 10 to 30 C DB 20 to 21 C DB R H Relative Humidity 03 14 OUTDOOR UNITS OUTDOOR UNITS ...

Страница 131: ...0 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 Rated Low noise mode 1 Low noise mode 2 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 Rated Low noise mode 1 Low noise mode 2 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC...

Страница 132: ...r frequency Hz 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 Rated Low noise mode 1 Low noise mode 2 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 Rated Low noise mode 1 Low noise mode 2 03 16 OUTDOOR UNITS OUTDOOR UNITS ...

Страница 133: ... SOUND LEVEL CHECK POINT Microphone Airflow 1 m 03 17 OUTDOOR UNITS OUTDOOR UNITS ...

Страница 134: ... of the table above Select the wire diameter based on the larger value of MCA or TOCA of the table above and select a wire diameter which withstands the breaker capacity 1 Wiring Spec These values are recommended data Please select the wiring spec in accordance with the regional cable standard 2 Limited Wiring Length This wiring length is in case voltage drop less than 2 When wiring length extend ...

Страница 135: ...0V 45A Protector Fan Motor DC 750V 10A Compressor Protector Overcurrent protection Discharge Pipe Temperature protection Off 120 C On 85 C Compressor Temperature protection Off 130 C On 90 C High Pressure Protection Off 4 2 MPa On 3 2 MPa Low Pressure Protection Off 0 05 MPa 03 19 OUTDOOR UNITS OUTDOOR UNITS ...

Страница 136: ...4 INDOOR UNITS DTV_VR2E018E_14 CHAPTER04 2017 10 31 ...

Страница 137: ...3 COMPACT FLOOR TYPE EEV external model 04 21 1 14 WALL MOUNTED TYPE 04 22 1 15 WALL MOUNTED TYPE EEV external model 04 27 2 ELECTRIC CHARACTERISTICS 04 30 3 DIMENSIONS 04 33 3 1 COMPACT CASSETTE TYPE 04 33 3 2 CASSETTE TYPE 04 35 3 3 CIRCULAR FLOW CASSETTE TYPE 04 38 3 4 LOW STATIC PRESSURE DUCT CONCEALED FLOOR TYPE 04 42 3 5 MINI DUCT TYPE 04 46 3 6 SLIM DUCT SLIM CONCEALED FLOOR TYPE 04 50 3 7 ...

Страница 138: ...4 7 MEDIUM STATIC PRESSURE DUCT TYPE 04 92 4 8 HIGH STATIC PRESSURE DUCT TYPE 04 93 4 9 LARGE AIRFLOW DUCT TYPE 04 95 4 10 FLOOR CEILING TYPE 04 98 4 11 CEILING TYPE 04 99 4 12 COMPACT FLOOR TYPE 04 100 4 13 COMPACT FLOOR TYPE EEV external model 04 101 4 14 WALL MOUNTED TYPE 04 102 4 15 WALL MOUNTED TYPE EEV external model 04 106 5 AIR VELOCITY AND TEMPERATURE DISTRIBUTIONS 04 110 5 1 COMPACT CASS...

Страница 139: ...285 8 NOISE LEVEL CURVE 04 289 8 1 COMPACT CASSETTE TYPE 04 289 8 2 CASSETTE TYPE 04 291 8 3 CIRCULAR FLOW CASSETTE TYPE 04 293 8 4 LOW STATIC PRESSURE DUCT CONCEALED FLOOR TYPE 04 295 8 5 MINI DUCT TYPE 04 297 8 6 SLIM DUCT SLIM CONCEALED FLOOR TYPE 04 299 8 7 MEDIUM STATIC PRESSURE DUCT TYPE 04 301 8 8 HIGH STATIC PRESSURE DUCT TYPE 04 302 8 9 LARGE AIRFLOW DUCT TYPE 04 304 8 10 FLOOR CEILING TY...

Страница 140: ...W 54 Sound pressure level High dB A 34 34 34 35 Med 30 28 1 30 28 1 30 30 Low 25 21 1 25 21 1 25 25 Heat exchanger Length mm 1 280 Fin pitch 1 20 Rows x Stages 2 10 Face Area m2 0 27 Pipe type Material Grooved H pin Copper Fin Type Material Slit Aluminium Surface treatment Hydrophilic coating Air filter Type Anti mold Net material PP honeycomb Enclosure Material galvanized sheet iron Colour Dimens...

Страница 141: ...tor output W 54 Sound pressure level High dB A 37 38 41 50 Med 34 34 35 44 Low 27 27 27 30 Heat exchanger Length mm 1 280 1 295 Fin pitch 1 20 1 30 Rows x Stages 2 10 3 10 Face Area m2 0 27 0 28 Pipe type Material Grooved H pin Copper Fin Type Material Slit Aluminium Surface treatment Hydrophilic coating Air filter Type Anti mold Net material PP honeycomb Enclosure Material galvanized sheet iron C...

Страница 142: ...put W 80 Sound pressure level High dB A 36 38 Med 30 33 Low 29 29 Heat exchanger Length mm 2 054 Fin pitch 1 20 Rows x Stages 2 10 Face Area m2 0 42 Pipe type Material Grooved H pin Copper Fin Type Material Slit Aluminium Surface treatment Hydrophilic coating Air filter Type Anti mold Net material PP honeycomb Enclosure Material galvanized sheet iron Colour Dimensions H x W x D Net Main body mm 24...

Страница 143: ...ty Turbo 1 Motor output W 80 Sound pressure level High dB A 40 40 40 43 Med 36 36 38 38 Low 33 31 1 33 31 1 33 33 Heat exchanger Length mm 2 087 Fin pitch 1 30 Rows x Stages 3 12 Face Area m2 0 52 Pipe type Material Grooved H pin Copper Fin Type Material Slit Aluminium Surface treatment Hydrophilic coating Air filter Type Anti mold Net material PP honeycomb Enclosure Material galvanized sheet iron...

Страница 144: ...y Turbo 1 Motor output W 80 Sound pressure level High dB A 44 46 47 Med 38 39 39 Low 33 33 33 Heat exchanger Length mm 2 087 Fin pitch 1 30 Rows x Stages 3 12 Face Area m2 0 52 Pipe type Material Grooved H pin Copper Fin Type Material Slit Aluminium Surface treatment Hydrophilic coating Air filter Type Anti mold Net material PP honeycomb Enclosure Material galvanized sheet iron Colour Dimensions H...

Страница 145: ...780 217 Type Quantity Turbo 1 Motor output W 81 Sound pressure level High dB A 33 35 40 Me Hi 32 33 36 Med 31 32 34 Lo Hi 30 31 32 Low 29 30 31 Quiet 28 28 28 Heat exchanger Dimensions H x W x D mm 210 2 127 13 3 210 2 061 13 3 Fin pitch 1 2 Rows Stages 2 10 Pipe type Material Grooved H pin Copper Fin Type Material Slit Aluminium Surface treatment Hydrophilic coating Air filter Type Anti mold Net ...

Страница 146: ...r output W 81 Sound pressure level High dB A 38 38 Me Hi 37 37 Med 36 36 Lo Hi 35 35 Low 34 34 Quiet 33 33 Heat exchanger Dimensions H x W x D mm 252 2 127 13 3 252 2 061 13 3 Fin pitch 1 2 Rows Stages 2 12 Pipe type Material Grooved H pin Copper Fin Type Material Slit Aluminium Surface treatment Hydrophilic coating Air filter Type Anti mold Net material PP honeycomb Enclosure Material galvanized ...

Страница 147: ... 1 300 361 1 300 361 Quiet 1 150 319 1 150 319 1 150 319 1 150 319 1 150 319 Type Quantity Turbo 1 Motor output W 81 Sound pressure level High dB A 39 39 41 44 47 Me Hi 38 38 40 42 45 Med 37 37 38 40 42 Lo Hi 36 36 37 38 39 Low 35 35 35 36 36 Quiet 33 33 33 33 33 Heat exchanger Dimensions H x W x D mm 252 2 124 13 3 252 2 062 13 3 252 1 999 13 3 Fin pitch 1 3 Rows Stages 3 12 Pipe type Material Gr...

Страница 148: ... High m3 h l s 370 103 440 122 590 164 800 222 890 247 Med 310 86 370 103 500 139 750 208 810 225 Low 280 78 340 94 450 125 700 194 730 203 Type x Quantity Sirocco 1 Sirocco 2 Motor output W 20 18 23 36 42 Sound pressure level High dB A 29 31 30 33 36 Med 26 29 28 32 34 Low 24 27 25 30 30 Heat exchanger Length mm 410 700 Fin pitch 1 30 Rows x Stages 2 14 Face Area m2 0 12 0 21 Pipe type Material G...

Страница 149: ...440 122 520 144 Med 420 117 420 117 420 117 480 133 Lo Hi 400 111 400 111 400 111 450 125 Low 370 103 370 103 370 103 410 114 Quiet 340 94 340 94 340 94 340 94 Type x Quantity Sirocco 2 Motor output W 80 Sound pressure level High dB A 25 26 26 29 Me Hi 24 25 25 27 Med 23 24 24 26 Lo Hi 22 23 23 25 Low 21 22 22 24 Quiet 20 21 21 22 Heat exchanger Length mm 490 Fin pitch 1 30 Rows x Stages 1 16 2 16...

Страница 150: ...Hi 490 136 640 178 860 239 Low 410 114 540 150 750 208 Quiet 340 94 470 131 610 169 Type Quantity Sirocco 2 Sirocco 3 Sirocco 4 Motor output W 80 81 Sound pressure level High dB A 34 33 32 Me Hi 31 30 30 Med 28 28 28 Lo Hi 26 26 27 Low 24 24 25 Quiet 22 22 22 Heat exchanger Length mm 490 690 890 Fin pitch 1 30 Rows Stages 2 16 Face Area m2 0 16 0 23 0 30 Pipe type Material Grooved H pin Copper Fin...

Страница 151: ... 510 142 550 153 600 167 600 167 800 222 Med 470 400 1 131 111 490 136 550 153 510 142 710 197 Low 440 320 1 122 89 440 122 480 133 450 125 610 169 Type x Quantity Sirocco 2 Motor output W 80 81 Sound pressure level High dB A 26 28 29 30 34 Med 25 21 1 25 26 27 32 Low 22 20 1 22 24 24 28 Heat exchanger Length mm 500 Fin pitch 1 30 Rows x Stages 2 14 3 14 Face Area m2 0 15 Pipe type Material Groove...

Страница 152: ...rate High m3 h l s 940 261 1 330 369 Med 840 233 1 240 344 Low 750 208 1 100 306 Type x Quantity Sirocco 3 Sirocco 4 Motor output W 96 Sound pressure level High dB A 34 35 Med 32 32 Low 28 29 Heat exchanger Length mm 700 900 Fin pitch 1 30 Rows x Stages 3 14 Face Area m2 0 21 0 26 Pipe type Material Grooved H pin Copper Fin Type Material Slit Aluminium Surface treatment Hydrophilic coating Air fil...

Страница 153: ...ow rate High m3 h l s 1 280 356 1 410 392 1 840 511 1 970 547 Med 990 275 1 280 356 1 600 444 1 860 517 Low 840 233 1 150 319 1 470 408 1 640 456 Type x Quantity Sirocco 2 Motor output W 106 197 Sound pressure level High dB A 31 34 37 41 Med 27 32 35 38 Low 23 29 33 36 Heat exchanger Length mm 1 000 Fin pitch 1 40 Rows x Stages 3 14 4 14 Face Area m2 0 29 Pipe type Material Grooved H pin Copper Fi...

Страница 154: ...00 833 3 300 917 4 000 1 111 4 250 1 181 Low 1 330 369 2 460 683 2 460 683 3 000 833 3 500 972 3 600 1 000 Type x Quantity Sirocco 2 Motor output W 197 540 700 2 Sound pressure level High dB A 42 49 49 47 48 48 Med 36 45 45 43 46 45 Low 32 42 42 40 44 42 Heat exchanger Length mm 890 1 250 Fin pitch 1 30 1 45 1 60 Rows x Stages 4 16 4 18 4 20 Face Area m2 0 30 0 50 0 64 Pipe type Material Grooved H...

Страница 155: ...00 583 2700 750 Me Hi 2050 569 2390 664 Med 1470 408 1860 517 2080 578 Lo Hi 1660 461 1770 492 Low 1360 378 1470 408 1470 408 Quiet 1260 350 1260 350 Type x Quantity Sirocco 2 Sirocco 3 Motor output W 197 385 Sound pressure level High dB A 36 37 41 Me Hi 35 38 Med 33 33 34 Lo Hi 31 31 Low 30 28 28 Quiet 26 26 Heat exchanger Length mm 1 000 1158 Fin pitch 1 40 Rows x Stages 4 14 3 20 Face Area 0 29...

Страница 156: ...50 to 150 50 to 250 50 to 300 Standard static pressure Pa 50 60 Fan Airflow rate m3 h l s 2 280 633 2 640 733 3 200 889 3 720 1 033 4 120 1 145 Type x Quantity Sirocco 2 Motor output W 700 2 Sound pressure level dB A 35 37 40 43 45 Heat exchanger Length mm 1 250 Fin pitch 1 45 Rows x Stages 4 18 Face Area m2 0 50 Pipe type Material Grooved H pin Copper Fin Type Material Slit Aluminium Surface trea...

Страница 157: ... 1 000 277 Med 570 158 640 177 720 199 820 227 Low 490 136 550 152 580 161 680 188 Type x Quantity Sirocco 2 Motor output W 80 Sound pressure level High dB A 36 40 46 47 Med 32 36 39 42 Low 28 34 35 37 Heat exchanger Length mm 800 Fin pitch 1 20 1 30 Rows x Stages 2 12 3 12 4 12 Face Area m2 0 20 Pipe type Material Grooved H pin Copper Fin Type Material Slit Aluminium Surface treatment Hydrophilic...

Страница 158: ... 2 270 629 Med 1 370 379 1 400 389 1 600 444 1 780 493 Low 1 140 316 1 170 325 1 230 342 1 280 355 Type x Quantity Sirocco 4 Motor output W 130 Sound pressure level High dB A 42 45 48 51 Med 38 38 42 45 Low 33 34 35 36 Heat exchanger Length mm 1 350 Fin pitch 1 45 Rows x Stages 3 12 3 12 1 8 Face Area m2 0 34 0 34 Pipe type Material Grooved H pin Copper Fin Type Material Slit Aluminium Surface tre...

Страница 159: ...90 108 400 111 470 131 520 144 Lo Hi 310 86 360 100 360 100 420 117 450 125 Low 280 78 330 92 330 92 390 108 390 108 Quiet 210 58 270 75 270 75 340 94 340 94 Type x Quantity Cross flow 2 Motor output W 16 2 Sound pressure level High dB A 35 36 37 38 42 46 Me Hi 33 35 36 39 42 Med 31 33 34 37 39 Lo Hi 30 31 31 35 36 Low 28 29 29 33 33 Quiet 22 22 22 30 30 Heat exchanger Length mm 550 Fin pitch 1 2 ...

Страница 160: ... 111 470 131 520 144 Lo Hi 310 86 360 100 360 100 420 117 450 125 Low 280 78 330 92 330 92 390 108 390 108 Quiet 210 58 270 75 270 75 340 94 340 94 Type x Quantity Cross flow 2 Motor output W 16 2 Sound pressure level High dB A 35 36 37 38 42 46 Me Hi 33 35 36 39 42 Med 31 33 34 37 39 Lo Hi 30 31 31 35 36 Low 28 29 29 33 33 Quiet 22 22 22 30 30 Heat exchanger Length mm 550 Fin pitch 1 2 Rows x Sta...

Страница 161: ...i 380 106 390 108 410 114 Low 360 100 360 100 360 100 Quiet 330 92 330 92 330 92 Type x Quantity Cross flow 1 Motor output W 30 Sound pressure level High dB A 31 35 43 Me Hi 30 32 38 Med 28 30 34 Lo Hi 26 27 29 Low 24 24 24 Quiet 22 22 22 Heat exchanger Dimensions H x W x D mm 256 630 20 Fin pitch 1 1 Rows x Stages 2 16 Pipe type Material Grooved H pin Copper Fin Type Material Slit Aluminium Surfa...

Страница 162: ...w 420 320 1 117 89 420 370 1 117 103 420 370 1 117 103 420 117 420 117 Type x Quantity Cross flow 1 Motor output W 42 Sound pressure level High dB A 33 35 36 39 44 Med 32 27 1 33 33 35 37 Low 31 22 1 31 27 1 31 27 1 31 32 Heat exchanger Length mm 600 Fin pitch 1 20 Rows x Stages 2 16 Face Area m2 0 20 Pipe type Material Grooved H pin Copper Fin Type Material Slit Aluminium Surface treatment Hydrop...

Страница 163: ...69 Low 470 131 550 153 Quiet 330 92 330 92 Type x Quantity Cross flow 1 Motor output W 30 Sound pressure level High dB A 40 44 Me Hi 37 42 Med 35 40 Lo Hi 33 37 Low 30 34 Quiet 24 24 Heat exchanger Dimensions H x W x D mm Main 320 630 20 Sub 84 630 13 3 Fin pitch Main 1 1 Sub 1 4 Rows x Stages Main 2 20 Sub 1 4 Pipe type Material Grooved H pin Copper Fin Type Material Slit Aluminium Surface treatm...

Страница 164: ...71 770 214 910 253 Low 690 191 730 202 770 213 690 192 730 203 Type x Quantity Cross flow 1 Motor output W 42 65 42 Sound pressure level High dB A 41 48 52 41 48 Med 39 43 45 39 43 Low 35 35 35 35 35 Heat exchanger Length mm 817 Fin pitch 1 20 1 40 Rows x Stages 2 18 1 4 2 pieces Face Area m2 0 31 Pipe type Material Grooved H pin Copper Fin Type Material Slit Aluminium Surface treatment Hydrophili...

Страница 165: ...47 890 247 Quiet 700 194 700 194 Type x Quantity Cross flow x 1 Motor output W 61 Sound pressure level High dB A 53 55 54 Me Hi 49 51 Med 45 47 Lo Hi 42 43 Low 39 39 Quiet 33 33 Heat exchanger Dimensions H x W x D mm Main 462 900 26 6 Sub1 126 900 13 3 Sub2 84 900 13 3 Fin pitch Main 1 2 Sub1 2 1 4 Rows x Stages Main 2 x 22 Sub 1 1 6 Sub2 1 4 Pipe type Material Grooved H pin Copper Fin Type Materi...

Страница 166: ...114 Low 360 100 360 100 360 100 Quiet 330 92 330 92 330 92 Type x Quantity Cross flow 1 Motor output W 30 Sound pressure level High dB A 31 35 43 Me Hi 30 32 38 Med 28 30 34 Lo Hi 26 27 29 Low 24 24 24 Quiet 22 22 22 Heat exchanger Dimensions H x W x D mm 256 630 20 Fin pitch 1 1 Rows x Stages 2 16 Pipe type Material Grooved H pin Copper Fin Type Material Slit Aluminium Surface treatment Hydrophil...

Страница 167: ...69 Low 470 131 550 153 Quiet 330 92 330 92 Type x Quantity Cross flow 1 Motor output W 30 Sound pressure level High dB A 40 44 Me Hi 37 42 Med 35 40 Lo Hi 33 37 Low 30 34 Quiet 24 24 Heat exchanger Dimensions H x W x D mm Main 320 630 20 Sub 84 630 13 3 Fin pitch Main 1 1 Sub 1 4 Rows x Stages Main 2 20 Sub 1 4 Pipe type Material Grooved H pin Copper Fin Type Material Slit Aluminium Surface treatm...

Страница 168: ... 420 370 1 117 103 420 370 1 117 103 420 117 420 117 Type x Quantity Cross flow 1 Motor output W 42 Sound pressure level High dB A 32 34 35 38 43 Med 31 26 1 32 32 34 35 Low 30 19 1 30 26 1 30 26 1 30 30 Heat exchanger Length mm 635 Fin pitch 1 20 Rows x Stages 2 16 Face Area m2 0 21 Pipe type Material Grooved H pin Copper Fin Type Material Slit Aluminium Surface treatment Hydrophilic coating Air ...

Страница 169: ...e AUXD18GALH 230 50 0 32 20 0 039 0 27 AUXD24GALH 0 38 0 046 0 32 AUXA18GALH 0 46 0 051 0 38 AUXA24GALH 0 46 0 051 0 38 AUXA30GALH 0 51 0 059 0 42 AUXA34GALH 0 61 0 077 0 51 AUXA36GALH 0 64 0 080 0 53 AUXA45GALH 0 83 0 099 0 69 AUXA54GALH 0 94 0 119 0 78 AUXM018GLAH 0 24 0 020 0 20 AUXM024GLAH 0 29 0 025 0 24 AUXM030GLAH 0 50 0 049 0 41 AUXK018GLAH 0 41 0 040 0 34 AUXK024GLAH 0 41 0 040 0 34 AUXK0...

Страница 170: ... 40 0 840 4 89 Large airflow duct ARXN018GLBH 230 50 1 34 20 0 173 1 05 ARXN024GTBH 1 50 0 180 1 10 ARXN030GTBH 2 28 0 273 1 64 ARXN18GATH 230 50 1 86 20 0 154 1 09 ARXN24GATH 2 76 0 205 1 39 ARXN30GATH 4 91 0 306 1 99 ARXN34GATH 6 14 0 432 2 71 ARXN36GATH 6 83 0 572 3 50 ARXN45GATH 6 83 0 572 3 50 Floor Ceiling AB A12GATH 230 50 0 30 20 0 030 0 25 AB A14GATH 0 41 0 042 0 34 AB A18GATH 0 69 0 074 ...

Страница 171: ... A09GACH 0 22 0 018 0 18 AS A12GACH 0 24 0 022 0 20 AS A14GACH 0 36 0 034 0 30 AS A18GACH 0 40 0 032 0 33 AS A24GACH 0 63 0 060 0 52 AS A30GACH 0 82 0 091 0 69 AS A18GBCH 0 40 0 032 0 33 AS A24GBCH 0 63 0 060 0 52 AS A030GTAH 0 66 0 074 0 55 AS A034GTAH 0 87 0 103 0 72 Wall mounted EEV external model AS E004GTAH 230 50 0 16 20 0 013 0 13 AS E007GTAH 0 23 0 019 0 19 AS E009GTAH 0 38 0 034 0 31 AS E...

Страница 172: ...UXB24 Refrigerant pipe flare connection Liquid ø 6 35 mm ø 9 52 mm Gas ø 9 52 mm ø 12 70 mm ø 15 88 mm Drain hose VP25 ø 25mm I D ø 32mm O D 285 285 Ceiling 114 114 B 700 700 View A IR receiver 570 Indoor unit 370 540 Hanging bolt position 580 to 660 Ceiling openings 530 530 Hanging bolt position Drain hose A View B View C 215 19 30 123 30 262 183 Control Box 146 40 C 04 33 INDOOR UNITS INDOOR UNI...

Страница 173: ...mm Model name AUXB04 07 09 AUXB12 14 18 24 Standard mode 2 700 2 700 High Ceiling mode 3 000 100 or more 4 directions 3 directions Piping position NOTE Use the Insulation kit for high humidity option when the condition under the roof is over 80 in humidity and over 30 C in temperature Otherwise there is a risk of condensation on the ceiling 04 34 INDOOR UNITS INDOOR UNITS ...

Страница 174: ... I D ø 32mm O D 796 Hanging bolt position Drain hose 358 840 Indoor unit 607 420 699 Hanging bolt position 860 to 910 Ceiling opening 250 31 31 143 Fresh air inlet cut out 70 A View B 142 142 Ceiling B 950 IR receiver Option 950 View A Control Box 109 90 352 83 83 100 100 View C 143 200 10 358 278 60 44 40 Wire hole 140 C 256 04 35 INDOOR UNITS INDOOR UNITS ...

Страница 175: ...15 88 mm ø 19 05 mm Drain hose VP25 ø 25mm I D ø 32mm O D 796 Hanging bolt position Drain hose 358 840 Indoor unit 607 420 699 Hanging bolt position 860 to 910 Ceiling opening 250 31 31 185 Fresh air inlet cut out 70 A View B 109 185 90 352 83 83 100 100 View C 142 142 Ceiling B 950 IR receiver Option 950 View A Control Box 200 10 358 278 60 44 40 Wire hole 140 C 298 04 36 INDOOR UNITS INDOOR UNIT...

Страница 176: ...XD24 AUXA18 AUXA24 AUXA30 AUXA34 AUXA36 AUXA45 AUXA54 Standard mode 3 000 3 000 3 200 3 200 3 200 3 200 3 200 3 200 3 200 High Ceiling mode 3 500 3 500 3 600 3 600 3 600 3 600 4 200 4 200 4 200 4 Direction 3 Direction 100 or more NOTE Use the Insulation kit for high humidity option when the condition under the roof is over 80 in humidity and over 30 C in temperature Otherwise there is a risk of co...

Страница 177: ...0 Refrigerant pipe flare connection Liquid ø 6 35 mm ø 9 52 mm Gas ø 12 70 mm ø 15 88 mm Drain hose VP25 ø 25mm I D ø 32mm O D 3 3 CIRCULAR FLOW CASSETTE TYPE MODELS AUXM018GLAH AUXM024GLAH AUXM030GLAH 04 38 INDOOR UNITS INDOOR UNITS ...

Страница 178: ...eight from floor to ceiling mm Model name AUXM018 024 030 Standard mode 3 000 High Ceiling mode 3 500 4 direction 3 direction 100 mm or more 1 1 Please ensure sufficient service access during installation NOTE Use the Insulation kit for high humidity option when the condition under the roof is over 80 in humidity and over 30 C in temperature Otherwise there is a risk of condensation on the ceiling...

Страница 179: ... AUXK036GLAH AUXK045GLAH AUXK054GLAH Unit mm AUXK018 AUXK024 AUXK030 AUXK034 AUXK036 AUXK045 AUXK054 Refrigerant pipe flare connection Liquid ø 6 35 mm ø 9 52 mm Gas ø 12 70 mm ø 15 88 mm Drain hose VP25 ø 25mm I D ø 32mm O D 04 40 INDOOR UNITS INDOOR UNITS ...

Страница 180: ... to ceiling mm Model name AUXK018 024 030 034 AUXK036 045 054 Standard mode 3 200 3 200 High Ceiling mode 3 600 4 200 4 direction 3 direction 100 mm or more 1 1 Please ensure sufficient service access during installation NOTE Use the Insulation kit for high humidity option when the condition under the roof is over 80 in humidity and over 30 C in temperature Otherwise there is a risk of condensatio...

Страница 181: ...ARXB07 ARXB09 Refrigerant pipe flare connection Liquid ø 6 35 mm Gas ø 12 70 mm Drain hose VP25 ø 25mm I D ø 32mm O D Rear view Ceiling concealed Rear view Floor concealed View A Top view Side view Front view Bottom view Drain hose 170 Drain port Drain port 04 42 INDOOR UNITS INDOOR UNITS ...

Страница 182: ...pipe flare connection Liquid ø 6 35 mm ø 9 52 mm Gas ø 12 70 mm ø 15 88 mm Drain hose VP25 ø 25mm I D ø 32mm O D Top view Front view Bottom view Side view View A Drain hose 170 Rear view Ceiling concealed Rear view Floor concealed Drain port Drain port 04 43 INDOOR UNITS INDOOR UNITS ...

Страница 183: ... or more 400 or more Right side PIPE side Strong and durable floor 30 or more 30 or more Duct Wall Grille Left 10 or less 10 or less side 150 or more 400 or more Right side PIPE side Strong and durable floor 30 or more 30 or more Wall Grille 1 When drain pump is used leave the space required for service and maintenance Refer to 6 10 1 DRAIN PUMP UNIT 2 When drain hose is connected the required dim...

Страница 184: ...0 or more 192 or more 100 or more Service space 400 or more Service access Control box Air Air Top view Provide a service access for inspection purposes as shown below Do not place any wiring or illumination in the service space as they will impede service Unit mm 04 45 INDOOR UNITS INDOOR UNITS ...

Страница 185: ...GCLH ARXK04 ARXK07 ARXK09 ARXK12 ARXK14 Refrigerant pipe flare connection Liquid ø 6 35 mm Gas ø 9 52 mm ø 12 70 mm Drain hose connection Drain hose I D 25 mm O D 32 mm Drain hose Rear view Top view Front view Bottom view Side view View A Unit mm 04 46 INDOOR UNITS INDOOR UNITS ...

Страница 186: ...efrigerant pipe flare connection Liquid ø 9 52 mm Gas ø 15 88 mm Drain hose connection Drain hose I D 25 mm O D 32 mm Rear view View A Top view Side view Front view Bottom view Drain hose Unit mm 04 47 INDOOR UNITS INDOOR UNITS ...

Страница 187: ...efrigerant pipe flare connection Liquid ø 9 52 mm Gas ø 15 88 mm Drain hose connection Drain hose I D 25 mm O D 32 mm Rear view View A Top view Side view Front view Bottom view Drain hose Unit mm 04 48 INDOOR UNITS INDOOR UNITS ...

Страница 188: ...or more Air When intaking air from bottom 100 mm or more Air 1 400mm or more when drain from drain pipe MAINTENANCE SPACE Provide a service access for inspection purposes as shown below Do not place any wiring or illumination in the service space as they will impede service Service access Air Air Control box Top view 400 mm or more 100 mm or more 300 mm or more Service space Above 100mm when intak...

Страница 189: ...XD09GALH ARXD12GALH ARXD14GALH ARXD04 ARXD07 ARXD09 ARXD12 ARXD14 Refrigerant pipe flare connection Liquid ø 6 35 mm Gas ø 12 70 mm Drain hose VP25 ø 25mm I D ø 32mm O D Rear view View A Top view Side view Front view Bottom view Drain hose Drain port 04 50 INDOOR UNITS INDOOR UNITS ...

Страница 190: ...H ARXD18 Refrigerant pipe flare connection Liquid ø 9 52 mm Gas ø 15 88 mm Drain hose VP25 ø 25mm I D ø 32mm O D Rear view View A Top view Side view Front view Bottom view Drain hose Drain port 04 51 INDOOR UNITS INDOOR UNITS ...

Страница 191: ...H ARXD24 Refrigerant pipe flare connection Liquid ø 9 52 mm Gas ø 15 88 mm Drain hose VP25 ø 25mm I D ø 32mm O D Rear view View A Top view Side view Front view Bottom view Drain hose Drain port 04 52 INDOOR UNITS INDOOR UNITS ...

Страница 192: ...re 10mm or less 10mm or less Left side 150 mm or more 150 mm or more 400 mm or more Strong and durable floor Right side PIPE side Grille Inlet air Strong and durable floor 20 mm or more 20 mm or more 150 mm or more Left side 150 mm or more 150 mm or more 400 mm or more Strong and durable floor Right side PIPE side Duct Grille Inlet air Strong and durable floor 20 mm or more 20 mm or more 150 mm or mor...

Страница 193: ...ection purposes as shown below Do not place any wiring or illumination in the service space as they will impede service 300 or more Service space 100 or more 400 or more Service access Air Indoor unit Air Top view Unit mm 04 54 INDOOR UNITS INDOOR UNITS ...

Страница 194: ...XA36 ARXA45 Refrigerant pipe flare connection Liquid ø 9 52 mm ø 9 52 mm Gas ø 15 88 mm ø 19 05 mm Drain hose VP25 ø 25mm I D ø 32mm O D Knock out hole fresh air 200 mm Hole for power cable 23 mm Rear view Front view Top view Side view R Side view L Drain hose Drain port Drain port 04 55 INDOOR UNITS INDOOR UNITS ...

Страница 195: ... view 1078 28 23 109 219 46 P174 x 6 1044 Ø 3 2 16 hole 400 or more 150 or more 20 or more Strong and durable ceiling For accessibility to install and remove the control box For accessibility to install and remove the control box fan units and filter 1 When drain pump is used leave the space required for service and maintenance 2 When drain hose is connected the required dimension is 400mm or more...

Страница 196: ...GBTH ARXC45GATH ARXC60GATH ARXC36 ARXC45 ARXC60 Refrigerant pipe flare connection Liquid ø 9 52 mm Gas ø 19 05 mm Drain hose VP25 ø 25mm I D ø 32mm O D Front view Top view Side view L Side view R Rear view Drain hose Drain port 04 57 INDOOR UNITS INDOOR UNITS ...

Страница 197: ...ice access Top view Service space 500 300 or more 300 or more Air Air 500 or more 30 or more Indoor unit Provide a service access for inspection purposes as shown below Do not place any wiring or illumination in the service space as they will impede service 04 58 INDOOR UNITS INDOOR UNITS ...

Страница 198: ...ion Liquid ø 12 70 mm Gas ø 22 22 mm Drain hose VP25 ø 25mm I D ø 32mm O D Drain hose 60 49 81 450 370 15 65 P160x2 320 350 35 15 1587 1410 BOLT PITCH 1250 150x7 1050 1200 1450 75 125 117 149 Φ3 38 42 227 311 404 427 700 653 BOLT PITCH 25 25 50 50 8 29 04 59 INDOOR UNITS INDOOR UNITS ...

Страница 199: ...25 15 35 P160x2 320 350 700 653 BOLT PITCH 29 1250 1410 BOLT PITCH 1587 81 42 149 75 125 117 P150x7 1050 1200 1450 38 60 49 8 ARXC96 Refrigerant pipe flare connection Liquid ø 12 70 mm Gas ø 22 22 mm Drain hose VP25 ø 25mm I D ø 32mm O D 04 60 INDOOR UNITS INDOOR UNITS ...

Страница 200: ...ll impede service b Installation by which service is carried out from the bottom of the unit 450 or more 450 Service space e l o h e c n a n e t n i a M or more a When service access will be carried out above the indoor unit a recommended installation space of 450mm is required Service access Service space Top view 890 or more 700 or more 30 or more 1490 500 or more 200 or more Control box Air Air...

Страница 201: ...18GLBH ARXN018 Refrigerant pipe flare connection Liquid ø 6 35 mm Gas ø 12 7 mm Drain hose VP25 ø 25 I D ø 32 O D Unit mm Rear view Front view Top view Side view R Side view L Drain hose Drain port Drain port 04 62 INDOOR UNITS INDOOR UNITS ...

Страница 202: ... view 1078 28 23 109 219 46 P174 x 6 1044 Ø 3 2 16 hole 400 or more 150 or more 20 or more Strong and durable ceiling For accessibility to install and remove the control box For accessibility to install and remove the control box fan units and filter 1 When drain pump is used leave the space required for service and maintenance 2 When drain hose is connected the required dimension is 400mm or more...

Страница 203: ...030 Refrigerant pipe flare connection Liquid ø 9 52 mm Gas ø 15 88 mm Drain hose VP25 ø 25 I D ø 32 O D Drain hose Unit mm Air Side view L Side view R Top view Front view Rear view Drain port Drain port Control box 04 64 INDOOR UNITS INDOOR UNITS ...

Страница 204: ...Provide a service access for maintenance purposes The service access necessary for fan units and filter maintenance Bottom view AIR Unit mm Control box 300 or more 500 or more 500 or more Service access AIR Service access Fan unit side 300 or more 500 or more 1400 or more 100 Bottom view Unit mm 04 65 INDOOR UNITS INDOOR UNITS ...

Страница 205: ...5GATH ARXN18 ARXN24 ARXN30 ARXN34 ARXN36 ARXN45 Refrigerant pipe flare connection Liquid ø 9 52 mm ø 9 52 mm Gas ø 15 88 mm ø 19 05 mm Drain hose VP25 ø 25mm I D ø 32mm O D Front view Top view Side view L Side view R Rear view Drain hose 04 66 INDOOR UNITS INDOOR UNITS ...

Страница 206: ...ll impede service b Installation by which service is carried out from the bottom of the unit 450 or more 450 Service space e l o h e c n a n e t n i a M or more a When service access will be carried out above the indoor unit a recommended installation space of 450mm is required Service access Service space Top view 890 or more 700 or more 30 or more 1490 500 or more 200 or more Control box Air Air...

Страница 207: ...A12 AB A14 AB A18 AB A24 Refrigerant pipe flare connection Liquid ø 6 35 mm ø 9 52 mm Gas ø 12 70 mm ø 15 88 mm Drain hose VP25 ø 25mm I D ø 32mm O D Knock out hole Drain outlet ø 45 mm Hole for lifting bolt Use M10 screw bolt 4 5 5 5 7 6 1 2 1 2 Drain hose 04 68 INDOOR UNITS INDOOR UNITS ...

Страница 208: ...e 50 hole 125 100 hole 655 530 45 65 500 245 990 65 Wall bracket Side of set Ceiling Left Indoor unit Right 150 or more 300 or more Left Right 300 or more 300 or more Ceiling 2300 or more Floor 20 or more 04 69 INDOOR UNITS INDOOR UNITS ...

Страница 209: ...rigerant pipe flare connection Liquid ø 9 52 mm ø 9 52 mm Gas ø 15 88 mm ø 19 05 mm Drain hose VP25 ø 25mm I D ø 32mm O D Knock out hole Drain outlet ø 50 mm Fresh air ø 200 mm Refrigerant pipe Hole for lifting bolt Use M10 screw bolt 5 6 7 1 2 4 Drain hose Drain port Drain port 04 70 INDOOR UNITS INDOOR UNITS ...

Страница 210: ...T Ceiling panel Ceiling panel 80 or more 150 or more 10 or more 30 30 Suspension bolt pitch 1 600 INDOOR UNIT TOP VIEW Dimensions Space Required for Installation 10 155 300 INDOOR UNIT Suspension bolt should extend outward 30 to 75 2500 or more Floor 2500 or more Floor 04 71 INDOOR UNITS INDOOR UNITS ...

Страница 211: ...ernal model MODELS AG E004GCAH AG E007GCAH AG E009GCAH AG E012GCAH AG E014GCAH AG A004 AG A007 AG A009 AG E004 AG E007 AG E009 AG A0012 AG A0014 AG E0012 AG E0014 Refrigerant pipe flare connection Liquid ø 6 35 mm ø 6 35 mm Gas ø 9 52 mm ø 12 7 mm Drain hose I D 13 8 mm O D 16 7 mm Drain hose L 600mm 04 72 INDOOR UNITS INDOOR UNITS ...

Страница 212: ...LACE Upper air outlet e r o m r o 0 8 e r o m r o 0 8 Lower air outlet 20 to 30 Indoor unit 100 or more Grating Wall cap 50 or more 80 or more 100 or more 80 or more 150 or below from the floor 04 73 INDOOR UNITS INDOOR UNITS ...

Страница 213: ... AS E004GTAH AS E007GTAH AS E009GTAH AS A004 AS A007 AS A009 AS E004 AS E007 AS E009 Refrigerant pipe flare connection Liquid ø 6 35 mm Gas ø 9 52 mm Drain hose I D 13 8 mm O D 15 8 16 7 mm Drain hose L 600mm 262 12 10 49 6 5 6 5 49 44 820 5 4 3 5 5 3 6 9 1 2 3 2 1 3 1 9 72 48 Outline of unit 04 74 INDOOR UNITS INDOOR UNITS ...

Страница 214: ... Unit mm INSTALLATION PLACE 80 or more 70 or more Outline of unit 200 or more 1 500 or more 1 800 or more 04 75 INDOOR UNITS INDOOR UNITS ...

Страница 215: ...GCAH AS A012 AS A014 AS E012 AS E014 Refrigerant pipe flare connection Liquid ø 6 35 mm Gas ø 12 7 mm Drain hose I D 13 8 mm O D 15 8 16 7 mm Drain hose L 600mm 315 840 840 203 430 410 310 295 209 216 34 268 268 74 233 144 381 Liquid pipe 165 178 321 for pipe inlet Ø65 for pipe inlet Ø65 315 Gas pipe 04 76 INDOOR UNITS INDOOR UNITS ...

Страница 216: ... Unit mm INSTALLATION PLACE 04 77 INDOOR UNITS INDOOR UNITS ...

Страница 217: ...odel MODELS AS E04GACH AS E07GACH AS E09GACH AS E12GACH AS E14GACH AS A04 AS A07 AS A09 AS A12 AS A14 AS E04 AS E07 AS E09 AS E12 AS E14 Refrigerant pipe flare connection Liquid ø 6 35 mm Gas ø 12 70 mm Drain hose I D 13 8 mm O D 15 8 16 7 mm Drain hose L 600mm 275 790 530 470 660 530 470 24 16 7 215 04 78 INDOOR UNITS INDOOR UNITS ...

Страница 218: ... Unit mm INSTALLATION PLACE Outline of indoor unit 49 or more 60 or more 44 or more 90 or more 45 or more 50 or more 1800 or more 1500 or more 04 79 INDOOR UNITS INDOOR UNITS ...

Страница 219: ...4 Refrigerant pipe flare connection Liquid ø 6 35 mm ø 9 52 mm Gas ø 12 70 mm ø 15 88 mm Drain hose I D 12 mm O D 16 mm Drain hose L 670mm 3 20 WALL MOUNTED TYPE MODELS AS A18GBCH AS A24GBCH 04 80 INDOOR UNITS INDOOR UNITS ...

Страница 220: ... Unit mm INSTALLATION PLACE 60 or more 77 or more 200 or more 50 or more 78 or more Outline of unit 267 or more 1500 or more 1800 or more 04 81 INDOOR UNITS INDOOR UNITS ...

Страница 221: ... AS A30 Refrigerant pipe flare connection Liquid ø 9 52 mm Gas ø 15 88 mm Drain hose I D 12 mm O D 16 mm Drain hose L 670mm MODELS AS A18GACH AS A24GACH AS A30GACH 998 228 320 520 520 590 721 04 82 INDOOR UNITS INDOOR UNITS ...

Страница 222: ... Unit mm INSTALLATION PLACE 43 or more 60 or more 133 or more 22 or more 50 or more Outline of unit 200 or more 1500 or more 1800 or more 04 83 INDOOR UNITS INDOOR UNITS ...

Страница 223: ...e connection Liquid ø 9 52 mm Gas ø 15 88 mm Drain hose I D 13 8 mm O D 15 8 16 7 mm Drain hose L 600mm MODELS AS A030GTAH AS A034GTAH 1150 Outline of unit 520 90 21 64 479 61 108 502 520 50 50 11 340 ø 8 0 ø 8 0 16 04 84 INDOOR UNITS INDOOR UNITS ...

Страница 224: ... Unit mm INSTALLATION PLACE 63 or more 80 or more 120 or more 59 or more 70 or more Outline of unit 200 or more 1500 or more 1800 or more 04 85 INDOOR UNITS INDOOR UNITS ...

Страница 225: ...4 WIRING DIAGRAMS 4 1 COMPACT CASSETTE TYPE MODELS AUXB04GBLH AUXB04GALH AUXB07GALH AUXB09GALH AUXB12GALH AUXB14GALH AUXB18GALH AUXB24GALH 04 86 INDOOR UNITS INDOOR UNITS ...

Страница 226: ...4 2 CASSETTE TYPE MODELS AUXD18GALH AUXD24GALH AUXA18GALH AUXA24GALH AUXA30GALH AUXA34GALH AUXA36GALH AUXA45GALH AUXA54GALH 04 87 INDOOR UNITS INDOOR UNITS ...

Страница 227: ...4 3 CIRCULAR FLOW CASSETTE TYPE MODELS AUXM018GLAH AUXM024GLAH AUXM030GLAH AUXK018GLAH AUXK024GLAH AUXK030GLAH AUXK034GLAH AUXK036GLAH AUXK045GLAH AUXK054GLAH 04 88 INDOOR UNITS INDOOR UNITS ...

Страница 228: ...4 4 LOW STATIC PRESSURE DUCT CONCEALED FLOOR TYPE MODELS ARXB07GALH ARXB09GALH ARXB12GALH ARXB14GALH ARXB18GALH 04 89 INDOOR UNITS INDOOR UNITS ...

Страница 229: ...4 5 MINI DUCT TYPE MODELS ARXK04GCLH ARXK07GCLH ARXK09GCLH ARXK12GCLH ARXK14GCLH ARXK18GCLH ARXK24GCLH 04 90 INDOOR UNITS INDOOR UNITS ...

Страница 230: ...4 6 SLIM DUCT SLIM CONCEALED FLOOR TYPE MODELS ARXD04GALH ARXD07GALH ARXD09GALH ARXD12GALH ARXD14GALH ARXD18GALH ARXD24GALH 04 91 INDOOR UNITS INDOOR UNITS ...

Страница 231: ...4 7 MEDIUM STATIC PRESSURE DUCT TYPE MODELS ARXA24GBLH ARXA30GBLH ARXA36GBLH ARXA45GBLH 04 92 INDOOR UNITS INDOOR UNITS ...

Страница 232: ...4 8 HIGH STATIC PRESSURE DUCT TYPE MODEL ARXC36GBTH MODELS ARXC45GATH ARXC60GATH 04 93 INDOOR UNITS INDOOR UNITS ...

Страница 233: ... MODELS ARXC72GBTH ARXC90GBTH ARXC96GATH 04 94 INDOOR UNITS INDOOR UNITS ...

Страница 234: ...4 9 LARGE AIRFLOW DUCT TYPE MODEL ARXN018GLBH 04 95 INDOOR UNITS INDOOR UNITS ...

Страница 235: ... MODELS ARXN024GTBH ARXN030GTBH 04 96 INDOOR UNITS INDOOR UNITS ...

Страница 236: ... MODELS ARXN18GATH ARXN24GATH ARXN30GATH ARXN34GATH ARXN36GATH ARXN45GATH 04 97 INDOOR UNITS INDOOR UNITS ...

Страница 237: ...4 10 FLOOR CEILING TYPE MODELS AB A12GATH AB A14GATH AB A18GATH AB A24GATH 04 98 INDOOR UNITS INDOOR UNITS ...

Страница 238: ...4 11 CEILING TYPE MODELS AB A30GATH AB A36GATH AB A45GATH AB A54GATH 04 99 INDOOR UNITS INDOOR UNITS ...

Страница 239: ...4 12 COMPACT FLOOR TYPE MODELS AG A004GCAH AG A007GCAH AG A009GCAH AG A012GCAH AG A014GCAH 04 100 INDOOR UNITS INDOOR UNITS ...

Страница 240: ...4 13 COMPACT FLOOR TYPE EEV external model MODELS AG E004GCAH AG E007GCAH AG E009GCAH AG E012GCAH AG E014GCAH 04 101 INDOOR UNITS INDOOR UNITS ...

Страница 241: ...4 14 WALL MOUNTED TYPE MODELS AS A004GTAH AS A007GTAH AS A009GTAH 04 102 INDOOR UNITS INDOOR UNITS ...

Страница 242: ... MODELS AS A012GCAH AS A014GCAH 04 103 INDOOR UNITS INDOOR UNITS ...

Страница 243: ... MODELS AS A04GACH AS A07GACH AS A09GACH AS A12GACH AS A14GACH 04 104 INDOOR UNITS INDOOR UNITS ...

Страница 244: ... MODELS AS A18GBCH AS A24GBCH AS A18GACH AS A24GACH AS A30GACH 04 105 INDOOR UNITS INDOOR UNITS ...

Страница 245: ... MODELS AS A030GTAH AS A034GTAH 04 106 INDOOR UNITS INDOOR UNITS ...

Страница 246: ...4 15 WALL MOUNTED TYPE EEV external model MODELS AS E004GTAH AS E007GTAH AS E009GTAH 04 107 INDOOR UNITS INDOOR UNITS ...

Страница 247: ... MODELS AS E012GCAH AS E014GCAH 04 108 INDOOR UNITS INDOOR UNITS ...

Страница 248: ... MODELS AS E04GACH AS E07GACH AS E09GACH AS E12GACH AS E14GACH 04 109 INDOOR UNITS INDOOR UNITS ...

Страница 249: ...gh Operation mode Fan Voltage 230V Top view Vertical airflow direction louver Up Side view Vertical airflow direction louver Up Unit m s 1 0 0 5 0 5 1 0 2 0 0 25 0 25 1 0 0 25 2 0 0 25 0 5 2 0 0 5 1 0 2 0 m m 0 1 2 3 3 1 2 4 4 3 4 2 1 0 1 2 3 4 m m Unit m s 0 0 1 1 2 2 3 3 1 2 2 7 4 4 0 25 0 25 0 5 0 5 1 0 1 0 2 0 2 0 04 110 INDOOR UNITS INDOOR UNITS ...

Страница 250: ...ribution z zAir temperature distribution Side view Vertical airflow direction louver Down Side view Vertical airflow direction louver Down 2 7 2 5 m Unit C m 2 1 0 0 1 2 3 4 1 2 3 4 22 24 26 28 30 2 7 2 5 m Unit m s m 2 1 0 0 1 2 3 4 1 2 3 4 0 25 0 5 1 0 1 5 2 0 04 111 INDOOR UNITS INDOOR UNITS ...

Страница 251: ...ew Vertical airflow direction louver Up Side view Vertical airflow direction louver Up Unit m s 1 0 0 5 0 5 1 0 2 0 0 25 0 25 1 0 0 25 2 0 0 25 0 5 2 0 0 5 1 0 2 0 m m 0 1 2 3 3 1 2 4 4 3 4 2 1 0 1 2 3 4 m m Unit m s 0 0 1 1 2 2 3 3 1 2 2 7 4 4 0 25 0 25 0 5 0 5 1 0 1 0 2 0 2 0 04 112 INDOOR UNITS INDOOR UNITS ...

Страница 252: ...ribution z zAir temperature distribution Side view Vertical airflow direction louver Down Side view Vertical airflow direction louver Down 2 7 2 5 m Unit C m 2 1 0 0 1 2 3 4 1 2 3 4 22 24 26 28 30 2 7 2 5 m Unit m s m 2 1 0 0 1 2 3 4 1 2 3 4 0 25 0 5 1 0 1 5 2 0 04 113 INDOOR UNITS INDOOR UNITS ...

Страница 253: ...ew Vertical airflow direction louver Up Side view Vertical airflow direction louver Up m m Unit m s 0 1 2 3 3 1 2 4 4 1 0 0 5 0 5 1 0 2 0 0 25 0 25 1 0 0 25 2 0 0 25 0 5 2 0 0 5 1 0 2 0 3 4 2 1 0 1 2 3 4 m m Unit m s 0 0 1 1 2 2 3 3 1 2 2 7 4 4 0 25 0 25 0 5 0 5 1 0 1 0 2 0 2 0 04 114 INDOOR UNITS INDOOR UNITS ...

Страница 254: ...ribution z zAir temperature distribution Side view Vertical airflow direction louver Down Side view Vertical airflow direction louver Down 2 7 2 5 m Unit C m 2 1 0 0 1 2 3 4 1 2 3 4 22 24 26 28 30 2 7 2 5 m Unit m s m 2 1 0 0 1 2 3 4 1 2 3 4 0 25 0 5 1 0 1 5 2 0 04 115 INDOOR UNITS INDOOR UNITS ...

Страница 255: ...ew Vertical airflow direction louver Up Side view Vertical airflow direction louver Up m m Unit m s 0 1 2 3 3 1 2 4 4 1 0 0 5 0 5 1 0 2 0 0 25 0 25 1 0 0 25 2 0 0 25 0 5 2 0 0 5 1 0 2 0 3 4 2 1 0 1 2 3 4 m m 0 0 1 1 2 2 3 3 1 2 2 7 4 4 0 25 0 25 0 5 0 5 1 0 1 0 2 0 2 0 Unit m s 04 116 INDOOR UNITS INDOOR UNITS ...

Страница 256: ...stribution z zAir temperature distribution Side view Vertical airflow direction louver Down Side view Vertical airflow direction louver Down m Unit m s m 2 7 2 5 2 1 0 0 1 2 3 4 1 2 3 4 0 25 0 5 1 0 1 5 m Unit C m 2 7 2 5 2 1 0 0 1 2 3 4 1 2 3 4 22 24 26 28 30 04 117 INDOOR UNITS INDOOR UNITS ...

Страница 257: ...view Vertical airflow direction louver Up Side view Vertical airflow direction louver Up m Unit m s m 0 1 2 3 3 1 2 4 1 0 0 5 0 5 1 0 2 0 0 25 0 25 1 0 0 25 2 0 0 25 0 5 2 0 0 5 1 0 2 0 3 4 2 1 0 1 2 3 4 m 0 0 1 1 2 2 3 3 1 2 2 7 4 4 0 25 0 25 0 5 0 5 1 0 1 0 2 0 2 0 Unit m s 04 118 INDOOR UNITS INDOOR UNITS ...

Страница 258: ...ribution z zAir temperature distribution Side view Vertical airflow direction louver Down Side view Vertical airflow direction louver Down m Unit C m 2 7 2 5 2 1 0 0 1 2 3 4 1 2 3 4 22 24 26 28 30 m Unit m s m 2 7 2 5 2 1 0 0 1 2 3 4 1 2 3 4 0 25 0 5 1 0 1 5 2 0 04 119 INDOOR UNITS INDOOR UNITS ...

Страница 259: ...iew Vertical airflow direction louver Up Side view Vertical airflow direction louver Up m Unit m s m 0 1 2 3 3 1 2 4 4 1 0 0 5 0 5 1 0 2 0 0 25 0 25 1 0 0 25 2 0 0 25 0 5 2 0 0 5 1 0 2 0 3 4 2 1 0 1 2 3 4 m 0 0 1 1 2 2 3 3 1 2 2 7 4 4 0 25 0 25 0 5 0 5 1 0 1 0 2 0 2 0 Unit m s 04 120 INDOOR UNITS INDOOR UNITS ...

Страница 260: ...ribution z zAir temperature distribution Side view Vertical airflow direction louver Down Side view Vertical airflow direction louver Down m Unit C m 2 7 2 5 2 1 0 0 1 2 3 4 1 2 3 4 22 24 26 28 30 m Unit m s m 2 7 2 5 2 1 0 0 1 2 3 4 1 2 3 4 0 25 0 5 1 0 1 5 2 0 04 121 INDOOR UNITS INDOOR UNITS ...

Страница 261: ...iew Vertical airflow direction louver Up Side view Vertical airflow direction louver Up m Unit m s m 0 1 2 3 3 1 2 4 4 1 0 0 5 0 5 1 0 2 0 0 25 0 25 1 0 0 25 2 0 0 25 0 5 2 0 0 5 1 0 2 0 3 4 2 1 0 1 2 3 4 m 0 0 1 1 2 2 3 3 1 2 2 7 4 4 0 25 0 25 0 5 0 5 1 0 1 0 2 0 2 0 Unit m s 04 122 INDOOR UNITS INDOOR UNITS ...

Страница 262: ...ribution z zAir temperature distribution Side view Vertical airflow direction louver Down Side view Vertical airflow direction louver Down m Unit C m 2 7 2 5 2 1 0 0 1 2 3 4 1 2 3 4 22 24 26 28 30 m Unit m s m 2 7 2 5 2 1 0 0 1 2 3 4 1 2 3 4 0 25 0 5 1 0 1 5 2 0 04 123 INDOOR UNITS INDOOR UNITS ...

Страница 263: ...ASSETTE TYPE MODEL AUXD18GALH z zAir velocity distribution Side view Vertical airflow direction louver Up Top view Vertical airflow direction louver Up Unit m s m 0 2 4 6 8 2 4 6 8 m 0 2 2 4 4 m m 0 2 0 1 2 3 6 8 2 4 4 6 8 Unit m s 04 124 INDOOR UNITS INDOOR UNITS ...

Страница 264: ...y distribution z zAir temperature distribution Side view Vertical airflow direction louver Down Side view Vertical airflow direction louver Down m Unit m s m 3 2 1 0 0 1 2 3 4 1 2 3 4 0 25 0 5 1 0 1 5 2 0 m Unit C m 3 2 1 0 0 1 2 3 4 1 2 3 4 22 24 26 28 30 04 125 INDOOR UNITS INDOOR UNITS ...

Страница 265: ...30V MODEL AUXD24GALH z zAir velocity distribution Side view Vertical airflow direction louver Up Top view Vertical airflow direction louver Up Unit m s m 0 2 4 6 8 2 4 6 8 m 0 2 2 4 4 m m 0 2 0 1 2 3 6 8 2 4 4 6 8 Unit m s 04 126 INDOOR UNITS INDOOR UNITS ...

Страница 266: ...y distribution z zAir temperature distribution Side view Vertical airflow direction louver Down Side view Vertical airflow direction louver Down m Unit m s m 3 2 1 0 0 1 2 3 4 1 2 3 4 0 25 0 5 1 0 1 5 2 0 m Unit C m 3 2 1 0 0 1 2 3 4 1 2 3 4 22 24 26 28 30 04 127 INDOOR UNITS INDOOR UNITS ...

Страница 267: ...XA18GALH AUXA24GALH z zAir velocity distribution Unit m s m 0 2 4 6 8 10 2 4 6 8 10 m 0 2 2 4 4 m 0 2 0 1 2 3 2 6 8 10 2 4 4 6 8 m 10 Unit m s Side view Vertical airflow direction louver Up Top view Vertical airflow direction louver Up 04 128 INDOOR UNITS INDOOR UNITS ...

Страница 268: ...z zAir velocity distribution z zAir temperature distribution m Unit m s m 3 2 3 2 1 0 0 1 2 3 4 1 2 3 4 Unit C m 3 2 3 2 1 0 m 0 1 2 3 4 1 2 3 4 Side view Vertical airflow direction louver Down Side view Vertical airflow direction louver Down 04 129 INDOOR UNITS INDOOR UNITS ...

Страница 269: ...EL AUXA30GALH z zAir velocity distribution Side view Vertical airflow direction louver Up Top view Vertical airflow direction louver Up Unit m s m 0 2 4 6 8 10 2 4 6 8 10 m 0 2 2 4 4 m 0 2 0 1 2 3 2 6 8 10 2 4 4 6 8 m 10 Unit m s 04 130 INDOOR UNITS INDOOR UNITS ...

Страница 270: ...stribution z zAir temperature distribution Side view Vertical airflow direction louver Down Side view Vertical airflow direction louver Down m Unit m s m 3 2 3 2 1 0 0 1 2 3 4 1 2 3 4 0 25 0 5 1 0 1 5 2 0 m Unit C m 3 2 3 2 1 0 0 1 2 3 4 1 2 3 4 22 24 26 28 30 04 131 INDOOR UNITS INDOOR UNITS ...

Страница 271: ...EL AUXA34GALH z zAir velocity distribution Side view Vertical airflow direction louver Up Top view Vertical airflow direction louver Up Unit m s m 0 2 4 6 8 10 2 4 6 8 10 m 0 2 2 4 4 m 0 2 0 1 2 3 2 6 8 10 2 4 4 6 8 m 10 Unit m s 04 132 INDOOR UNITS INDOOR UNITS ...

Страница 272: ...ta Side view Vertical airflow direction louver Down Side view Vertical airflow direction louver Down z zAir velocity distribution m Unit m s m 3 2 3 2 1 0 0 1 2 3 4 1 2 3 4 0 25 0 5 1 0 1 5 2 0 m 0 2 0 1 2 3 2 6 8 10 2 4 4 6 8 m 10 Unit m s 04 133 INDOOR UNITS INDOOR UNITS ...

Страница 273: ...EL AUXA36GALH z zAir velocity distribution Side view Vertical airflow direction louver Up Top view Vertical airflow direction louver Up Unit m s m 0 2 4 6 8 10 2 4 6 8 10 m 0 2 2 4 4 m 0 2 0 1 2 3 2 6 8 10 2 4 4 6 8 m 10 Unit m s 04 134 INDOOR UNITS INDOOR UNITS ...

Страница 274: ...stribution z zAir temperature distribution Side view Vertical airflow direction louver Down Side view Vertical airflow direction louver Down m Unit m s m 3 2 3 2 1 0 0 1 2 3 4 1 2 3 4 0 25 0 5 1 0 1 5 2 0 m Unit C m 3 2 3 2 1 0 0 1 2 3 4 1 2 3 4 22 24 26 28 30 04 135 INDOOR UNITS INDOOR UNITS ...

Страница 275: ...EL AUXA45GALH z zAir velocity distribution Side view Vertical airflow direction louver Up Top view Vertical airflow direction louver Up Unit m s m 0 2 4 6 8 10 2 4 6 8 10 m 0 2 2 4 4 m 0 2 0 1 2 3 2 6 8 10 2 4 4 6 8 m 10 Unit m s 04 136 INDOOR UNITS INDOOR UNITS ...

Страница 276: ...stribution z zAir temperature distribution Side view Vertical airflow direction louver Down Side view Vertical airflow direction louver Down m Unit C m 3 2 3 2 1 0 0 1 2 3 4 1 2 3 4 22 24 26 28 30 m Unit m s m 3 2 3 2 1 0 0 1 2 3 4 1 2 3 4 0 25 0 5 1 0 1 5 2 0 04 137 INDOOR UNITS INDOOR UNITS ...

Страница 277: ...EL AUXA54GALH z zAir velocity distribution Side view Vertical airflow direction louver Up Top view Vertical airflow direction louver Up Unit m s m 0 2 4 6 8 10 2 4 6 8 10 m 0 2 2 4 4 m 0 2 0 1 2 3 2 6 8 10 2 4 4 6 8 m 10 Unit m s 04 138 INDOOR UNITS INDOOR UNITS ...

Страница 278: ...stribution z zAir temperature distribution Side view Vertical airflow direction louver Down Side view Vertical airflow direction louver Down m Unit C m 3 2 3 2 1 0 0 1 2 3 4 1 2 3 4 22 24 26 28 30 m Unit m s m 3 2 3 2 1 0 0 1 2 3 4 1 2 3 4 0 25 0 5 1 0 1 5 2 0 04 139 INDOOR UNITS INDOOR UNITS ...

Страница 279: ...tribution Side view Vertical airflow direction louver Up Top view Vertical airflow direction louver Up m m Unit m s 3 2 1 0 3 2 1 1 1 1 0 1 0 1 0 1 0 2 2 2 0 2 0 0 3 3 5 4 4 5 6 6 7 7 0 5 0 5 0 5 0 5 0 25 0 25 m m Unit m s 3 2 2 1 0 1 1 1 0 1 0 2 2 0 3 3 5 4 4 5 6 6 7 7 5 0 5 0 0 25 0 25 2 0 2 0 04 140 INDOOR UNITS INDOOR UNITS ...

Страница 280: ...ide view Vertical airflow direction louver Down Side view Vertical airflow direction louver Down m m Unit m s 3 2 2 1 0 1 1 2 2 0 3 3 5 4 4 5 6 6 7 7 0 25 0 5 1 0 2 0 0 5 0 25 1 0 2 0 m m Unit m s 3 2 2 1 0 1 1 1 0 1 0 2 2 0 3 3 5 4 4 5 6 6 7 7 0 5 0 5 5 2 0 5 2 0 2 0 2 0 04 141 INDOOR UNITS INDOOR UNITS ...

Страница 281: ...iew Vertical airflow direction louver Up Top view Vertical airflow direction louver Up m m Unit m s 3 2 1 0 3 2 1 1 1 1 0 1 0 1 0 1 0 2 2 2 0 2 0 0 3 3 5 4 4 5 6 6 7 7 0 5 0 5 0 5 0 5 0 25 0 25 m m Unit m s 3 2 2 1 0 1 1 2 2 0 3 3 5 4 4 5 6 6 7 7 0 25 0 5 1 0 2 0 0 5 0 25 1 0 2 0 04 142 INDOOR UNITS INDOOR UNITS ...

Страница 282: ...Side view Vertical airflow direction louver Down Side view Vertical airflow direction louver Down m m Unit m s 3 2 2 1 0 1 1 2 2 0 3 3 5 4 4 5 6 6 7 7 0 25 0 5 1 0 2 0 0 5 0 25 1 0 2 0 m m Unit m s 3 2 2 1 0 1 1 2 2 0 3 3 5 4 4 5 6 6 7 7 0 25 0 5 1 0 2 0 0 5 0 25 1 0 2 0 04 143 INDOOR UNITS INDOOR UNITS ...

Страница 283: ... speed High Operation mode Fan Voltage 230V MODEL AUXM030GLAH z zAir velocity distribution Side view Vertical airflow direction louver Up Top view Vertical airflow direction louver Up 04 144 INDOOR UNITS INDOOR UNITS ...

Страница 284: ...peed High Operation mode Heat Voltage 230V Reference Data z zAir velocity distribution Side view Vertical airflow direction louver Down Side view Vertical airflow direction louver Down 04 145 INDOOR UNITS INDOOR UNITS ...

Страница 285: ...High Operation mode Fan Voltage 230V MODELS AUXK018GLAH AUXK024GLAH z zAir velocity distribution Side view Vertical airflow direction louver Up Top view Vertical airflow direction louver Up 04 146 INDOOR UNITS INDOOR UNITS ...

Страница 286: ...peed High Operation mode Heat Voltage 230V Reference Data z zAir velocity distribution Side view Vertical airflow direction louver Down Side view Vertical airflow direction louver Down 04 147 INDOOR UNITS INDOOR UNITS ...

Страница 287: ...High Operation mode Fan Voltage 230V MODELS AUXK030GLAH AUXK034GLAH z zAir velocity distribution Side view Vertical airflow direction louver Up Top view Vertical airflow direction louver Up 04 148 INDOOR UNITS INDOOR UNITS ...

Страница 288: ...peed High Operation mode Heat Voltage 230V Reference Data z zAir velocity distribution Side view Vertical airflow direction louver Down Side view Vertical airflow direction louver Down 04 149 INDOOR UNITS INDOOR UNITS ...

Страница 289: ...iew Vertical airflow direction louver Up Top view Vertical airflow direction louver Up m m Unit m s 3 2 1 0 3 2 1 1 1 1 0 1 0 1 0 1 0 2 2 2 0 2 0 0 3 3 5 4 4 5 6 6 7 7 5 0 5 0 0 5 0 5 0 25 0 25 m m Unit m s 3 2 2 1 0 1 1 2 2 0 3 3 5 4 4 5 6 6 7 7 5 0 5 0 0 25 0 25 1 0 1 0 2 0 2 0 04 150 INDOOR UNITS INDOOR UNITS ...

Страница 290: ...ide view Vertical airflow direction louver Down Side view Vertical airflow direction louver Down m m Unit m s 3 2 2 1 0 1 1 2 2 0 3 3 5 4 4 5 6 6 7 7 0 25 0 5 0 5 0 25 1 0 2 0 1 0 2 0 m m Unit m s 3 2 2 1 0 1 1 2 2 0 3 3 5 4 4 5 6 6 7 7 0 5 0 5 5 2 0 5 2 0 1 0 1 0 2 0 2 0 04 151 INDOOR UNITS INDOOR UNITS ...

Страница 291: ...iew Vertical airflow direction louver Up Top view Vertical airflow direction louver Up m m Unit m s 3 2 1 0 3 2 1 1 1 1 0 2 2 0 3 3 5 4 4 5 6 6 7 7 0 5 0 25 1 0 2 0 0 5 1 0 2 0 0 5 0 25 1 0 0 5 m m Unit m s 3 2 2 1 0 1 1 2 2 0 3 3 5 4 4 5 6 6 7 7 0 25 0 5 1 0 2 0 0 5 0 25 1 0 2 0 04 152 INDOOR UNITS INDOOR UNITS ...

Страница 292: ...Side view Vertical airflow direction louver Down Side view Vertical airflow direction louver Down m 3 2 2 1 0 m 1 1 2 2 0 3 3 5 4 4 5 6 6 7 7 0 25 0 5 1 0 2 0 0 5 0 25 1 0 2 0 Unit m s m m Unit m s 3 2 2 1 0 1 1 2 2 0 3 3 5 4 4 5 6 6 7 7 0 25 0 5 1 0 2 0 0 5 0 25 1 0 2 0 04 153 INDOOR UNITS INDOOR UNITS ...

Страница 293: ...Vertical airflow direction louver Up Top view Vertical airflow direction louver Up m m Unit m s 3 2 1 0 3 2 1 1 1 1 0 2 2 2 0 0 3 3 5 4 4 5 6 6 7 7 0 5 0 25 1 0 2 0 0 5 1 0 2 0 0 5 0 25 2 0 1 0 0 5 m m Unit m s 3 2 2 1 0 1 1 2 2 0 3 3 5 4 4 5 6 6 7 7 0 25 0 5 1 0 2 0 0 5 0 25 1 0 2 0 04 154 INDOOR UNITS INDOOR UNITS ...

Страница 294: ...Side view Vertical airflow direction louver Down Side view Vertical airflow direction louver Down m 3 2 2 1 0 0 25 0 5 1 0 2 0 0 5 0 25 1 0 2 0 m 1 1 2 2 0 3 3 5 4 4 5 6 6 7 7 Unit m s m m Unit m s 3 2 2 1 0 1 1 2 2 0 3 3 5 4 4 5 6 6 7 7 0 25 0 5 1 0 2 0 0 5 0 25 1 0 2 0 04 155 INDOOR UNITS INDOOR UNITS ...

Страница 295: ...1 0 m Unit m s 0 1 1 m Top view Vertical airflow direction louver Up Horizontal airflow direction louver Center 0 5 0 5 1 0 1 0 2 0 2 0 10 9 8 7 6 5 4 3 2 1 0 m Unit m s 0 1 1 2 2 3 3 4 4 5 m 5 Top view Vertical airflow direction louver Up Horizontal airflow direction louver Right Left 0 5 1 0 2 0 10 9 8 7 6 5 4 3 2 1 0 m Unit m s 0 1 2 2 5 3 m Side view Vertical airflow direction louver Up Horizo...

Страница 296: ... 6 5 4 3 2 1 0 m Unit m s 0 1 2 2 5 3 m 0 5 1 0 2 0 z zAir temperature distribution 10 9 8 7 6 5 4 3 2 1 0 m Unit C 0 1 2 2 5 3 m 30 28 26 24 22 Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center Conditions Fan speed High Operation mode Heat Reference Data 04 157 INDOOR UNITS INDOOR UNITS ...

Страница 297: ... 2 3 3 4 4 5 m 5 0 5 1 0 2 0 10 9 8 7 6 5 4 3 2 1 0 m Unit m s 0 1 1 m 0 5 1 0 2 0 10 9 8 7 6 5 4 3 2 1 0 m Unit m s 0 1 2 2 5 3 m Top view Vertical airflow direction louver Up Horizontal airflow direction louver Center Top view Vertical airflow direction louver Up Horizontal airflow direction louver Right Left Side view Vertical airflow direction louver Up Horizontal airflow direction louver Cent...

Страница 298: ... 6 5 4 3 2 1 0 m Unit m s 0 1 2 2 5 3 m 0 5 1 0 2 0 z zAir temperature distribution 10 9 8 7 6 5 4 3 2 1 0 m Unit C 0 1 2 2 5 3 m 30 28 26 24 22 Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center Conditions Fan speed High Operation mode Heat Reference Data 04 159 INDOOR UNITS INDOOR UNITS ...

Страница 299: ... 2 3 3 4 4 5 m 5 0 5 1 0 2 0 10 9 8 7 6 5 4 3 2 1 0 m Unit m s 0 1 1 m 0 5 1 0 2 0 10 9 8 7 6 5 4 3 2 1 0 m Unit m s 0 1 2 2 5 3 m Top view Vertical airflow direction louver Up Horizontal airflow direction louver Center Top view Vertical airflow direction louver Up Horizontal airflow direction louver Right Left Side view Vertical airflow direction louver Up Horizontal airflow direction louver Cent...

Страница 300: ... 6 5 4 3 2 1 0 m Unit m s 0 1 2 2 5 3 m 0 5 1 0 2 0 z zAir temperature distribution 10 9 8 7 6 5 4 3 2 1 0 m Unit C 0 1 2 2 5 3 m 30 28 26 24 22 Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center Conditions Fan speed High Operation mode Heat Reference Data 04 161 INDOOR UNITS INDOOR UNITS ...

Страница 301: ... 2 3 3 4 4 5 m 5 0 5 1 0 2 0 10 9 8 7 6 5 4 3 2 1 0 m Unit m s 0 1 1 m 0 5 1 0 2 0 10 9 8 7 6 5 4 3 2 1 0 m Unit m s 0 1 2 2 5 3 m Top view Vertical airflow direction louver Up Horizontal airflow direction louver Center Top view Vertical airflow direction louver Up Horizontal airflow direction louver Right Left Side view Vertical airflow direction louver Up Horizontal airflow direction louver Cent...

Страница 302: ... 6 5 4 3 2 1 0 m Unit m s 0 1 2 2 5 3 m 0 5 1 0 2 0 z zAir temperature distribution 10 9 8 7 6 5 4 3 2 1 0 m Unit C 0 1 2 2 5 3 m 30 28 26 24 22 Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center Conditions Fan speed High Operation mode Heat Reference Data 04 163 INDOOR UNITS INDOOR UNITS ...

Страница 303: ... 2 3 3 4 4 5 m 5 0 5 1 0 2 0 10 9 8 7 6 5 4 3 2 1 0 m Unit m s 0 1 1 m 0 5 1 0 2 0 10 9 8 7 6 5 4 3 2 1 0 m Unit m s 0 1 2 2 5 3 m Top view Vertical airflow direction louver Up Horizontal airflow direction louver Center Top view Vertical airflow direction louver Up Horizontal airflow direction louver Right Left Side view Vertical airflow direction louver Up Horizontal airflow direction louver Cent...

Страница 304: ... 6 5 4 3 2 1 0 m Unit m s 0 1 2 2 5 3 m 0 5 1 0 2 0 z zAir temperature distribution 10 9 8 7 6 5 4 3 2 1 0 m Unit C 0 1 2 2 5 3 m 30 28 26 24 22 Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center Conditions Fan speed High Operation mode Heat Reference Data 04 165 INDOOR UNITS INDOOR UNITS ...

Страница 305: ... direction louver Center Top view Vertical airflow direction louver Up Horizontal airflow direction louver Right Left Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 0 5 0 5 1 0 1 0 2 0 2 0 10 9 8 7 6 5 4 3 2 1 0 m Unit m s 0 1 1 2 2 3 3 4 4 5 m 5 0 5 1 0 2 0 10 9 8 7 6 5 4 3 2 1 0 m Unit m s 0 1 1 2 2 m 0 5 1 0 2 0 10 9 8 7 6 5 4 3 2 1 0 m Unit m s 0 1 2 ...

Страница 306: ...tion louver Down Horizontal airflow direction louver Center 10 9 8 7 6 5 4 3 2 1 0 m Unit m s 0 1 2 2 5 3 m 0 5 1 0 2 0 z zAir temperature distribution Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 10 9 8 7 6 5 4 3 2 1 0 m Unit C 0 1 2 2 5 3 m 30 28 26 24 22 04 167 INDOOR UNITS INDOOR UNITS ...

Страница 307: ...irection louver Up Horizontal airflow direction louver Right Left Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 0 5 0 5 1 0 1 0 2 0 2 0 10 9 8 7 6 5 4 3 2 1 0 m Unit m s 0 1 1 2 2 3 3 4 4 5 m 5 0 5 1 0 2 0 10 9 8 7 6 5 4 3 2 1 0 m Unit m s 0 1 1 2 2 m 0 5 1 0 2 0 10 9 8 7 6 5 4 3 2 1 0 m Unit m s 0 1 2 2 5 3 m Conditions Fan speed High Operation mode Fan...

Страница 308: ...tion louver Down Horizontal airflow direction louver Center 10 9 8 7 6 5 4 3 2 1 0 m Unit m s 0 1 2 2 5 3 m 0 5 1 0 2 0 z zAir temperature distribution Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 10 9 8 7 6 5 4 3 2 1 0 m Unit C 0 1 2 2 5 3 m 30 28 26 24 22 04 169 INDOOR UNITS INDOOR UNITS ...

Страница 309: ...rflow direction louver Center Top view Vertical airflow direction louver Up Horizontal airflow direction louver Right Left Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 0 5 0 5 1 0 1 0 2 0 2 0 10 9 8 7 6 5 4 3 2 1 0 m Unit m s 0 1 1 2 2 3 3 4 4 5 m 5 0 5 1 0 2 0 10 9 8 7 6 5 4 3 2 1 0 m Unit m s 0 1 1 2 2 m 0 5 1 0 2 0 10 9 8 7 6 5 4 3 2 1 0 m Unit m s 0...

Страница 310: ...tion louver Down Horizontal airflow direction louver Center 10 9 8 7 6 5 4 3 2 1 0 m Unit m s 0 1 2 2 5 3 m 0 5 1 0 2 0 z zAir temperature distribution Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 10 9 8 7 6 5 4 3 2 1 0 m Unit C 0 1 2 2 5 3 m 30 28 26 24 22 04 171 INDOOR UNITS INDOOR UNITS ...

Страница 311: ...rflow direction louver Center Top view Vertical airflow direction louver Up Horizontal airflow direction louver Right Left Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 0 5 0 5 1 0 1 0 2 0 2 0 10 9 8 7 6 5 4 3 2 1 0 m Unit m s 0 1 1 2 2 3 3 4 4 5 m 5 0 5 1 0 2 0 10 9 8 7 6 5 4 3 2 1 0 m Unit m s 0 1 1 2 2 m 0 5 1 0 2 0 10 9 8 7 6 5 4 3 2 1 0 m Unit m s 0...

Страница 312: ...tion louver Down Horizontal airflow direction louver Center 10 9 8 7 6 5 4 3 2 1 0 m Unit m s 0 1 2 2 5 3 m 0 5 1 0 2 0 z zAir temperature distribution Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 10 9 8 7 6 5 4 3 2 1 0 m Unit C 0 1 2 2 5 3 m 30 28 26 24 22 04 173 INDOOR UNITS INDOOR UNITS ...

Страница 313: ...rflow direction louver Center Top view Vertical airflow direction louver Up Horizontal airflow direction louver Right Left Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 0 5 0 5 1 0 1 0 2 0 2 0 10 9 8 7 6 5 4 3 2 1 0 m Unit m s 0 1 1 2 2 3 3 4 4 5 m 5 0 5 1 0 2 0 10 9 8 7 6 5 4 3 2 1 0 m Unit m s 0 1 1 2 2 m 0 5 1 0 2 0 10 9 8 7 6 5 4 3 2 1 0 m Unit m s 0...

Страница 314: ...tion louver Down Horizontal airflow direction louver Center 10 9 8 7 6 5 4 3 2 1 0 m Unit m s 0 1 2 2 5 3 m 0 5 1 0 2 0 z zAir temperature distribution Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 10 9 8 7 6 5 4 3 2 1 0 m Unit C 0 1 2 2 5 3 m 30 28 26 24 22 04 175 INDOOR UNITS INDOOR UNITS ...

Страница 315: ...rflow direction louver Center Top view Vertical airflow direction louver Up Horizontal airflow direction louver Right Left Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 0 5 0 5 1 0 1 0 2 0 2 0 10 9 8 7 6 5 4 3 2 1 0 m Unit m s 0 1 1 2 2 3 3 4 4 5 m 5 0 5 1 0 2 0 10 9 8 7 6 5 4 3 2 1 0 m Unit m s 0 1 1 2 2 m 0 5 1 0 2 0 10 9 8 7 6 5 4 3 2 1 0 m Unit m s 0...

Страница 316: ...tion louver Down Horizontal airflow direction louver Center 10 9 8 7 6 5 4 3 2 1 0 m Unit m s 0 1 2 2 5 3 m 0 5 1 0 2 0 z zAir temperature distribution Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 10 9 8 7 6 5 4 3 2 1 0 m Unit C 0 1 2 2 5 3 m 30 28 26 24 22 04 177 INDOOR UNITS INDOOR UNITS ...

Страница 317: ...rflow direction louver Center Top view Vertical airflow direction louver Up Horizontal airflow direction louver Right Left Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 0 5 0 5 1 0 1 0 2 0 2 0 10 9 8 7 6 5 4 3 2 1 0 m Unit m s 0 1 1 2 2 3 3 4 4 5 m 5 0 5 1 0 2 0 10 9 8 7 6 5 4 3 2 1 0 m Unit m s 0 1 1 2 2 m 0 5 1 0 2 0 10 9 8 7 6 5 4 3 2 1 0 m Unit m s 0...

Страница 318: ...tion louver Down Horizontal airflow direction louver Center 10 9 8 7 6 5 4 3 2 1 0 m Unit m s 0 1 2 2 5 3 m 0 5 1 0 2 0 z zAir temperature distribution Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 10 9 8 7 6 5 4 3 2 1 0 m Unit C 0 1 2 2 5 3 m 30 28 26 24 22 04 179 INDOOR UNITS INDOOR UNITS ...

Страница 319: ...flow direction louver Center Top view Vertical airflow direction louver Down Horizontal airflow direction louver Center Top view Vertical airflow direction louver Down Horizontal airflow direction louver Right Left 2 0 1 0 0 5 0 25 2 1 0 1 2 0 1 2 3 4 5 6 7 8 9 Unit m s m m 2 0 1 0 0 5 0 5 0 25 0 25 HORIZONTAL Right HORIZONTAL Left 1 0 0 1 2 3 4 5 6 7 8 9 3 2 1 0 1 2 3 Unit m s m m 2 0 1 0 0 5 0 2...

Страница 320: ...tion louver Center Top view Vertical airflow direction louver Up Horizontal airflow direction louver Right Left Top view Vertical airflow direction louver Up Horizontal airflow direction louver Center 2 0 1 0 0 5 0 25 2 1 0 1 2 0 1 2 3 4 5 6 7 8 9 Unit m s m m 2 0 1 0 0 5 0 5 0 25 0 25 1 0 0 1 2 3 4 5 6 7 8 9 3 2 1 0 1 2 3 Unit m s HORIZONTAL Right HORIZONTAL Left m m 2 0 1 0 0 5 0 25 3 2 1 0 1 2 ...

Страница 321: ...louver Center Top view Vertical airflow direction louver Down Horizontal airflow direction louver Right Left Top view Vertical airflow direction louver Down Horizontal airflow direction louver Center 2 0 1 0 0 5 0 25 2 1 0 1 2 0 1 2 3 4 5 6 7 8 9 Unit m s m m 2 0 1 0 0 5 0 5 0 25 0 25 1 0 0 1 2 3 4 5 6 7 8 9 3 2 1 0 1 2 3 Unit m s HORIZONTAL Right HORIZONTAL Left m m 2 0 1 0 0 5 0 25 3 2 1 0 1 2 3...

Страница 322: ...ouver Center Top view Vertical airflow direction louver Up Horizontal airflow direction louver Right Left Top view Vertical airflow direction louver Up Horizontal airflow direction louver Center 2 0 1 0 0 5 0 25 2 1 0 1 2 0 1 2 3 4 5 6 7 8 9 Unit m s m m 2 0 1 0 0 5 0 5 0 25 0 25 1 0 0 1 2 3 4 5 6 7 8 9 3 2 1 0 1 2 3 Unit m s HORIZONTAL Right HORIZONTAL Left m m 2 0 1 0 0 5 0 25 3 2 1 0 1 2 3 4 5 ...

Страница 323: ...ver Center Top view Vertical airflow direction louver Down Horizontal airflow direction louver Right Left Top view Vertical airflow direction louver Down Horizontal airflow direction louver Center 2 0 1 0 0 5 0 25 2 1 0 1 2 0 1 2 3 4 5 6 7 8 9 Unit m s m m 2 0 1 0 0 5 0 5 0 25 0 25 1 0 0 1 2 3 4 5 6 7 8 9 3 2 1 0 1 2 3 Unit m s HORIZONTAL Right HORIZONTAL Left m m 2 0 1 0 0 5 0 25 3 2 1 0 1 2 3 4 ...

Страница 324: ...ouver Center Top view Vertical airflow direction louver Up Horizontal airflow direction louver Right Left Top view Vertical airflow direction louver Up Horizontal airflow direction louver Center 2 0 1 0 0 5 0 25 2 1 0 1 2 0 1 2 3 4 5 6 7 8 9 Unit m s m m 2 0 1 0 0 5 0 5 0 25 0 25 1 0 0 1 2 3 4 5 6 7 8 9 m m 3 2 1 0 1 2 3 Unit m s HORIZONTAL Right HORIZONTAL Left 1 0 2 0 0 5 0 25 m m 3 2 1 0 1 2 3 ...

Страница 325: ...ver Up Horizontal airflow direction louver Right Left Top view Vertical airflow direction louver Up Horizontal airflow direction louver Center Unit m s m m 4 3 2 1 0 1 2 3 4 2 0 1 0 0 5 0 25 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Unit m s m m 4 3 2 1 0 1 2 3 4 2 0 1 0 1 0 0 5 0 5 0 25 0 25 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Unit m s m m 3 2 1 0 2 0 1 0 0 5 0 25 0 1 2 3 4 5 6 7 ...

Страница 326: ...rizontal airflow direction louver Right Left Top view Vertical airflow direction louver Up Horizontal airflow direction louver Center Unit m s m m 4 3 2 1 0 1 2 3 4 2 0 1 0 0 5 0 25 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Unit m s m m 4 3 2 1 0 1 2 3 4 2 0 1 0 1 0 0 5 0 5 0 25 0 25 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Unit m s m m 3 2 1 0 0 5 0 25 0 1 2 3 4 5 6 7 8 9 10 11 12 13 1...

Страница 327: ...rizontal airflow direction louver Right Left Top view Vertical airflow direction louver Up Horizontal airflow direction louver Center Unit m s m m 4 3 2 1 0 1 2 3 4 2 0 1 0 0 5 0 25 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Unit m s m m 4 3 2 1 0 1 2 3 4 2 0 1 0 1 0 0 5 0 5 0 25 0 25 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Unit m s m m 3 2 1 0 2 0 1 0 0 5 0 25 0 1 2 3 4 5 6 7 8 9 10 11...

Страница 328: ...rflow direction louver Center Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center Top view Vertical airflow direction louver Up Horizontal airflow direction louver Right Left Top view Vertical airflow direction louver Up Horizontal airflow direction louver Center 1 0 2 0 0 5 0 25 1 0 1 0 2 0 0 5 0 5 0 25 0 25 2 0 1 0 0 5 0 25 0 5 0 25 1 0 2 0 1 0 2 0 0 25 0 5 ...

Страница 329: ...cal airflow direction louver Up Horizontal airflow direction louver Center Top view Vertical airflow direction louver Up Horizontal airflow direction louver Right Left Top view Vertical airflow direction louver Up Horizontal airflow direction louver Center UPPER LOWER 1 0 0 5 0 1 3 2 4 0 1 2 2 1 m Unit m s m 0 1 3 2 4 0 1 2 3 m Unit m s m 0 5 1 0 0 1 3 2 4 0 1 2 3 m Unit m s m 0 5 1 0 0 0 1 2 2 1 ...

Страница 330: ...ical airflow direction louver Up Horizontal airflow direction louver Center Top view Vertical airflow direction louver Up Horizontal airflow direction louver Right Left Top view Vertical airflow direction louver Up Horizontal airflow direction louver Center 0 1 3 2 4 0 1 2 2 1 m Unit m s m 1 0 0 5 UPPER LOWER 0 1 3 2 4 0 1 2 3 0 5 1 0 m Unit m s m 0 1 3 2 4 0 1 2 3 m Unit m s m 0 5 1 0 0 0 1 2 2 1...

Страница 331: ... direction louver Up Horizontal airflow direction louver Center Top view Vertical airflow direction louver Up Horizontal airflow direction louver Right Left Top view Vertical airflow direction louver Up Horizontal airflow direction louver Center 0 1 3 2 4 0 1 2 2 1 1 0 0 5 UPPER LOWER m Unit m s m 0 1 3 2 4 0 1 2 3 m Unit m s m 0 5 1 0 0 1 3 2 4 0 1 2 3 m Unit m s m 0 5 1 0 0 0 1 2 2 1 1 3 2 4 m U...

Страница 332: ...eration mode FAN Fan select UPPER LOWER UPPER FAN LOWER FAN Side view Vertical airflow direction louver Center Horizontal airflow direction louver Center Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center Top view Vertical airflow direction louver Up Horizontal airflow direction louver Right Left Top view Vertical airflow direction louver Up Horizontal airflo...

Страница 333: ...izontal airflow direction louver Center Top view Vertical airflow direction louver Up Horizontal airflow direction louver Right Left Top view Vertical airflow direction louver Up Horizontal airflow direction louver Center 1 0 2 0 0 5 1 0 0 5 m m Unit m s 0 1 2 3 4 5 6 7 8 2 3 1 0 3 2 1 0 5 2 0 1 0 m m Unit m s 0 1 2 3 4 5 6 7 8 2 0 1 1 2 0 1 2 3 4 5 6 7 8 0 1 2 3 m m Unit m s 1 0 2 0 0 5 m Unit m ...

Страница 334: ...flow direction louver Center Top view Vertical airflow direction louver Up Horizontal airflow direction louver Right Left Top view Vertical airflow direction louver Up Horizontal airflow direction louver Center 0 1 2 3 4 5 6 7 8 2 3 1 0 3 2 1 1 0 2 0 0 5 1 0 0 5 m m Unit m s 0 1 2 3 4 5 6 7 8 2 0 1 1 2 m Unit m s m 1 0 2 0 0 5 m Unit m s m 0 1 2 3 4 5 6 7 8 0 1 2 3 1 0 2 0 0 5 0 1 2 3 4 5 6 7 8 3 ...

Страница 335: ...flow direction louver Center Top view Vertical airflow direction louver Up Horizontal airflow direction louver Right Left Top view Vertical airflow direction louver Up Horizontal airflow direction louver Center 0 1 2 3 4 5 6 7 8 2 3 1 0 3 2 1 1 0 2 0 0 5 1 0 0 5 m m Unit m s 0 1 2 3 4 5 6 7 8 2 0 1 1 2 m Unit m s m 1 0 2 0 0 5 m Unit m s m 1 0 2 0 0 5 0 1 2 3 4 5 6 7 8 0 1 2 3 0 1 2 3 4 5 6 7 8 3 ...

Страница 336: ...view Vertical airflow direction louver Up Horizontal airflow direction louver Center Top view Vertical airflow direction louver Up Horizontal airflow direction louver Right Left Top view Vertical airflow direction louver Up Horizontal airflow direction louver Center 1 0 1 0 0 5 0 5 2 0 m m Unit m s 2 0 0 5 1 0 m m Unit m s 1 0 0 5 2 0 m m Unit m s m m Unit m s 1 0 0 5 2 0 04 197 INDOOR UNITS INDOO...

Страница 337: ...view Vertical airflow direction louver Up Horizontal airflow direction louver Center Top view Vertical airflow direction louver Up Horizontal airflow direction louver Right Left Top view Vertical airflow direction louver Up Horizontal airflow direction louver Center 1 0 1 0 0 5 0 5 2 0 m m Unit m s 2 0 1 0 0 5 m m Unit m s 1 0 0 5 2 0 m m Unit m s 1 0 2 0 0 5 m m Unit m s 04 198 INDOOR UNITS INDOO...

Страница 338: ... direction louver Up Horizontal airflow direction louver Right Left Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center Unit m s 0 1 2 3 4 5 6 7 8 1 5 1 0 5 0 0 5 1 1 5 m m 2 0 1 0 0 5 0 25 Unit m s 0 1 2 3 4 5 6 7 8 2 1 0 1 2 m m 2 0 1 0 0 5 1 0 0 5 0 25 0 25 Unit m s 0 1 2 3 4 5 6 7 8 3 2 4 2 1 0 m m 2 0 1 0 0 5 0 25 04 199 INDOOR UNITS INDOOR UNITS ...

Страница 339: ...on louver Center Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center Unit m s 0 1 2 3 4 5 6 7 8 3 2 4 2 1 0 m m 2 0 1 0 0 5 0 25 Unit C 0 1 2 3 4 5 6 7 8 3 2 4 2 1 0 m m 26 24 22 28 30 22 Conditions Fan speed High Operation mode Heat Voltage 230V Reference Data 04 200 INDOOR UNITS INDOOR UNITS ...

Страница 340: ...de view Vertical airflow direction louver Up Horizontal airflow direction louver Center Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center Unit m s 0 1 2 3 4 5 6 7 8 1 5 1 0 5 0 0 5 1 1 5 m m 2 0 1 0 0 5 0 25 Unit m s 0 1 2 3 4 5 6 7 8 2 1 0 1 2 m m 2 0 1 0 0 5 1 0 0 5 0 25 0 25 Unit m s 0 1 2 3 4 5 6 7 8 3 2 4 2 1 0 m m 2 0 1 0 0 5 0 25 Unit m s 0 1 2 3 4 ...

Страница 341: ... Vertical airflow direction louver Up Horizontal airflow direction louver Right Left Top view Vertical airflow direction louver Up Horizontal airflow direction louver Center Unit m s 0 1 2 3 4 5 6 7 8 1 5 1 0 5 0 0 5 1 1 5 m m 2 0 1 0 0 5 0 25 Unit m s 0 1 2 3 4 5 6 7 8 2 1 0 1 2 m m 0 5 0 5 1 0 1 0 2 0 0 25 0 25 Unit m s 0 1 2 3 4 5 6 7 8 3 2 4 2 1 0 m m 2 0 1 0 0 5 0 25 Unit m s 0 1 2 3 4 5 6 7 ...

Страница 342: ...ew Vertical airflow direction louver Up Horizontal airflow direction louver Right Left Top view Vertical airflow direction louver Up Horizontal airflow direction louver Center Unit m s 0 1 2 3 4 5 6 7 8 m m 1 5 1 0 5 0 0 5 1 1 5 2 0 1 0 0 5 0 25 Unit m s 0 1 2 3 4 5 6 7 8 m m 2 1 0 1 2 0 5 1 0 2 0 0 5 0 25 0 25 Unit m s 0 1 2 3 4 5 6 7 8 3 2 4 2 1 0 m m 2 0 1 0 0 5 0 25 Unit m s 0 1 2 3 4 5 6 7 8 ...

Страница 343: ...al airflow direction louver Up Horizontal airflow direction louver Right Left Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center Unit m s 0 1 2 3 4 5 6 7 8 1 5 1 0 5 0 0 5 1 1 5 m m 2 0 1 0 0 5 0 25 Unit m s 0 1 2 3 4 5 6 7 8 2 1 0 1 2 m m 2 0 1 0 0 5 1 0 0 5 0 25 0 25 Unit m s 0 1 2 3 4 5 6 7 8 3 2 4 2 1 0 m m 2 0 1 0 0 5 0 25 04 204 INDOOR UNITS INDOOR UNIT...

Страница 344: ...on louver Center Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center Unit m s 0 1 2 3 4 5 6 7 8 3 2 4 2 1 0 m m 2 0 1 0 0 5 0 25 Unit C 0 1 2 3 4 5 6 7 8 3 2 4 2 1 0 m m 26 24 22 28 30 22 Conditions Fan speed High Operation mode Heat Voltage 230V Reference Data 04 205 INDOOR UNITS INDOOR UNITS ...

Страница 345: ...p view Vertical airflow direction louver Up Horizontal airflow direction louver Right Left Top view Vertical airflow direction louver Up Horizontal airflow direction louver Center Unit m s 0 1 2 3 4 5 6 7 8 1 5 1 0 5 0 0 5 1 1 5 m m 2 0 1 0 0 5 0 25 Unit m s 0 1 2 3 4 5 6 7 8 2 1 0 1 2 m m 2 0 1 0 0 5 1 0 0 5 0 25 0 25 Unit m s 0 1 2 3 4 5 6 7 8 3 2 4 2 1 0 m m 2 0 1 0 0 5 0 25 Unit m s 0 1 2 3 4 ...

Страница 346: ... Top view Vertical airflow direction louver Up Horizontal airflow direction louver Right Left Top view Vertical airflow direction louver Up Horizontal airflow direction louver Center Unit m s 0 1 2 3 4 5 6 7 8 1 5 1 0 5 0 0 5 1 1 5 m m 2 0 1 0 0 5 0 25 Unit m s 0 1 2 3 4 5 6 7 8 2 1 0 1 2 m m 0 5 0 5 1 0 1 0 2 0 0 25 0 25 Unit m s 0 1 2 3 4 5 6 7 8 3 2 4 2 1 0 m m 2 0 1 0 0 5 0 25 Unit m s 0 1 2 3...

Страница 347: ...er Top view Vertical airflow direction louver Up Horizontal airflow direction louver Right Left Top view Vertical airflow direction louver Up Horizontal airflow direction louver Center Unit m s 0 1 2 3 4 5 6 7 8 m m 1 5 1 0 5 0 0 5 1 1 5 2 0 1 0 0 5 0 25 Unit m s 0 1 2 3 4 5 6 7 8 m m 2 1 0 1 2 0 5 1 0 2 0 0 5 0 25 0 25 Unit m s 0 1 2 3 4 5 6 7 8 3 2 4 2 1 0 m m 2 0 1 0 0 5 0 25 Unit m s 0 1 2 3 4...

Страница 348: ...ion louver Center Top view Vertical airflow direction louver Up Horizontal airflow direction louver Right Left Top view Vertical airflow direction louver Up Horizontal airflow direction louver Center 2 1 0 1 2 m m Unit m s 0 1 2 3 4 5 6 7 8 2 0 1 0 0 5 3 2 1 0 m m Unit m s 0 1 2 3 4 5 6 7 8 2 0 1 0 0 5 3 2 1 0 m m Unit m s 0 1 2 3 4 5 6 7 8 2 0 1 0 0 5 1 0 0 5 0 5 2 0 1 0 3 2 1 0 1 2 3 m m Unit m ...

Страница 349: ... 7 8 2 0 1 0 0 5 3 2 1 0 m m Unit m s 0 1 2 3 4 5 6 7 8 Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center Top view Vertical airflow direction louver Up Horizontal airflow direction louver Right Left Top view Vertical airflow direction louver Up Horizontal airflow dire...

Страница 350: ... 2 0 1 0 0 5 3 2 1 0 m m Unit m s 0 1 2 3 4 5 6 7 8 Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center Top view Vertical airflow direction louver Up Horizontal airflow direction louver Right Left Top view Vertical airflow direction louver Up Horizontal airflow directio...

Страница 351: ...ntal airflow direction louver Right Left Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 1 2 3 4 0 1 2 3 4 m m Unit m s 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 1 5 1 0 2 0 5 1 2 3 4 0 1 2 3 4 m m Unit m s 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 5 0 5 1 0 1 0 2 0 1 5 1 5 3 2 1 0 m m Unit m s 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 2 0 1 5 1 0 0 5 04 212 INDOO...

Страница 352: ...ontal airflow direction louver Right Left Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 1 2 3 4 1 2 3 4 m Unit m s m 2 0 1 5 1 0 m Unit m s m 0 1 2 3 4 1 2 3 4 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 4 1 0 1 5 2 0 1 0 1 5 0 5 0 5 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 1 2 3 1 5 1 0 2 0 0 5 m m Unit m s 04 213 INDOOR...

Страница 353: ...ow m3 h Cooling Airflow m3 h High mode upper limit Outlet Temperature Outlet Temperature Capacity Capacity Low mode upper limit High mode lower limit High mode Hi Low mode Hi High mode Lo Low mode Lo 400 350 300 250 200 400 350 300 250 200 400 350 300 250 200 60 50 40 20 10 30 0 100 100 110 110 80 80 90 90 60 60 50 50 40 10 11 12 13 14 15 16 70 70 47 46 45 44 43 42 41 40 04 214 INDOOR UNITS INDOOR...

Страница 354: ...de upper limit Outlet Temperature Outlet Temperature Capacity Capacity Low mode upper limit High mode lower limit High mode Hi Low mode Hi High mode Lo Low mode Lo 450 400 350 300 250 450 400 350 300 250 450 400 350 300 250 60 50 40 20 10 30 0 100 110 80 90 60 50 10 11 12 13 14 15 16 70 100 110 80 90 60 50 40 70 47 46 45 44 43 42 41 40 04 215 INDOOR UNITS INDOOR UNITS ...

Страница 355: ...it Outlet Temperature Outlet Temperature Capacity Capacity Low mode upper limit High mode lower limit High mode Hi Low mode Hi High mode Lo Low mode Lo 450 500 550 600 400 350 300 450 500 550 600 400 350 300 450 500 550 600 400 350 300 60 50 40 20 10 30 0 100 110 80 90 60 50 10 11 12 13 14 15 16 70 100 110 80 90 60 50 40 70 47 46 45 44 43 42 41 40 04 216 INDOOR UNITS INDOOR UNITS ...

Страница 356: ...it Outlet Temperature Outlet Temperature Capacity Capacity Low mode upper limit High mode lower limit High mode Hi Low mode Hi High mode Lo Low mode Lo 750 800 850 900 700 650 600 750 800 850 900 700 650 600 750 800 850 900 700 650 600 60 50 40 20 10 30 0 100 110 80 90 60 50 10 11 12 13 14 15 16 70 100 110 80 90 60 50 40 70 47 46 45 44 43 42 41 40 04 217 INDOOR UNITS INDOOR UNITS ...

Страница 357: ... Temperature Outlet Temperature Capacity Capacity Low mode upper limit High mode lower limit High mode Hi Low mode Hi High mode Lo Low mode Lo 800 1 000 900 700 300 400 500 600 800 1 000 900 700 300 400 500 600 800 1 000 900 700 300 400 500 600 60 50 40 20 10 30 0 100 110 80 90 60 50 10 11 12 13 14 15 16 70 100 110 80 90 60 50 40 70 47 46 45 44 43 42 41 40 04 218 INDOOR UNITS INDOOR UNITS ...

Страница 358: ...t SP mode00 upper limit Lo SP mode00 Lo SP mode03 Lo Normal SP Hi SP mode03 SP mode03 lower limit Hi Normal SP Normal SP lower limit Hi SP mode00 External Static Pressure Pa Airflow m3 h External Static Pressure Pa Airflow m3 h Available airflow rate range Hi speed 1 Available airflow rate range when Auto louver grille option is installed Fan speed High Vertical flap Up 04 219 INDOOR UNITS INDOOR ...

Страница 359: ...flow m3 h External Static Pressure Pa 12 13 14 15 16 17 18 19 0 20 40 60 80 100 120 140 300 400 500 600 Capacity Outlet Temperature 35 36 37 38 39 40 41 42 0 20 40 60 80 100 120 140 300 400 500 600 Outlet Temperature Capacity 20 10 0 10 20 30 40 0 10 20 30 40 50 60 300 400 500 600 04 220 INDOOR UNITS INDOOR UNITS ...

Страница 360: ...SP lower limit Hi SP mode03 Hi SP mode00 Hi SP mode02 Hi SP mode03 Hi Normal SP Hi SP mode00 Lo Normal SP Hi Normal SP Lo SP mode03 Lo SP mode00 600 300 400 500 600 300 400 500 60 50 40 20 10 30 0 60 50 40 20 10 30 0 Available airflow rate range Hi speed 1 1 Available airflow rate range when Auto louver grille option is installed Fan speed High Vertical flap Up 04 221 INDOOR UNITS INDOOR UNITS ...

Страница 361: ...irflow m3 h 60 100 40 80 20 0 120 140 60 100 40 80 20 0 120 140 13 15 12 14 11 10 9 16 Capacity Capacity Outlet Temperture Outlet Temperture 43 42 44 41 40 39 38 37 Outlet Temperature Capacity Outlet Temperature Capacity 600 300 400 500 600 300 400 500 20 10 0 10 20 30 40 0 10 20 30 40 50 60 300 400 500 600 04 222 INDOOR UNITS INDOOR UNITS ...

Страница 362: ...SP lower limit Hi SP mode03 Hi SP mode00 Hi SP mode02 Hi SP mode03 Hi Normal SP Hi SP mode00 Lo Normal SP Hi Normal SP Lo SP mode03 Lo SP mode00 600 300 400 500 600 300 400 500 60 50 40 20 10 30 0 60 50 40 20 10 30 0 Available airflow rate range Hi speed 1 1 Available airflow rate range when Auto louver grille option is installed Fan speed High Vertical flap Up 04 223 INDOOR UNITS INDOOR UNITS ...

Страница 363: ...irflow m3 h 60 100 40 80 20 0 120 140 60 100 40 80 20 0 120 140 13 15 12 14 11 10 9 16 Capacity Capacity Outlet Temperture Outlet Temperture 43 42 44 41 40 39 38 37 Outlet Temperature Capacity Outlet Temperature Capacity 600 300 400 500 600 300 400 500 20 10 0 10 20 30 40 0 10 20 30 40 50 60 300 400 500 600 04 224 INDOOR UNITS INDOOR UNITS ...

Страница 364: ...Hi SP mode03 Hi SP mode00 Hi SP mode02 Hi SP mode03 Hi Normal SP Hi SP mode00 Lo Normal SP Hi Normal SP Lo SP mode03 Lo SP mode00 700 600 300 400 500 700 600 300 400 500 60 50 40 20 10 30 0 60 50 40 20 10 30 0 Available airflow rate range Hi speed 1 1 Available airflow rate range when Auto louver grille option is installed Fan speed High Vertical flap Up 04 225 INDOOR UNITS INDOOR UNITS ...

Страница 365: ... m3 h 60 100 40 80 20 0 120 140 60 100 40 80 20 0 120 140 13 15 12 14 11 10 9 16 Capacity Capacity Outlet Temperture Outlet Temperture 43 42 44 41 40 39 38 37 Outlet Temperature Capacity Outlet Temperature Capacity 700 600 300 400 500 700 600 300 400 500 60 40 20 0 20 40 60 0 10 20 30 40 50 60 300 400 500 600 700 04 226 INDOOR UNITS INDOOR UNITS ...

Страница 366: ...e01 Hi SP mode02 Hi SP mode03 Hi SP mode04 Hi SP mode05 Hi Normal SP Hi SP mode00 Lo Normal SP Hi Normal SP Lo SP mode05 Lo SP mode00 700 800 900 1000 600 300 400 500 700 800 900 1000 600 300 400 500 60 70 50 40 20 10 30 0 60 70 50 40 20 10 30 0 Available airflow rate range Hi speed 1 1 Available airflow rate range when Auto louver grille option is installed Fan speed High Vertical flap Up 04 227 ...

Страница 367: ...0 40 80 20 0 120 140 13 15 12 14 11 10 9 16 Capacity Capacity Outlet Temperture Outlet Temperture 43 42 44 41 40 39 38 37 Outlet Temperature Capacity Outlet Temperature Capacity 700 800 900 1000 600 300 400 500 700 800 900 1000 600 300 400 500 120 100 80 60 40 20 0 20 40 60 80 100 0 10 20 30 40 50 60 70 80 90 100 110 300 400 500 600 700 800 900 1000 04 228 INDOOR UNITS INDOOR UNITS ...

Страница 368: ... Hi SP mode01 Hi SP mode02 Hi SP mode03 Hi SP mode04 Hi SP mode05 Hi Normal SP Hi SP mode00 Lo Normal SP Hi Normal SP Lo SP mode05 Lo SP mode00 700 800 900 1000 1100 600 400 500 700 800 900 1000 1100 600 400 500 60 70 50 40 20 10 30 0 60 70 50 40 20 10 30 0 Available airflow rate range Hi speed 1 1 Available airflow rate range when Auto louver grille option is installed Fan speed High Vertical fla...

Страница 369: ...40 80 20 0 120 140 13 15 12 14 11 10 9 16 Capacity Capacity Outlet Temperture Outlet Temperture 43 42 44 45 46 41 40 39 Outlet Temperature Capacity Outlet Temperature Capacity 700 800 900 1000 1100 600 400 500 700 800 900 1000 1100 600 400 500 100 80 60 40 20 0 20 40 60 80 100 120 0 10 20 30 40 50 60 70 80 90 100 110 400 500 600 700 800 900 1000 1100 04 230 INDOOR UNITS INDOOR UNITS ...

Страница 370: ...i SP mode01 Hi SP mode02 Hi SP mode03 Hi SP mode04 Hi SP mode05 Hi Normal SP Hi SP mode00 Lo Normal SP Hi Normal SP Lo SP mode05 Lo SP mode00 700 800 900 1000 1100 1200 1300 600 700 800 900 1000 1100 1200 1300 600 60 70 50 40 20 10 30 0 60 70 50 40 20 10 30 0 Available airflow rate range Hi speed 1 1 Available airflow rate range when Auto louver grille option is installed Fan speed High Vertical f...

Страница 371: ...ic Pressure Pa Input W Airflow m3 h 60 100 40 80 20 0 120 140 60 100 40 80 20 0 120 140 13 15 12 14 11 10 9 16 Capacity Capacity Outlet Temperture Outlet Temperture 43 42 44 45 46 41 40 39 Outlet Temperature Capacity Outlet Temperature Capacity 80 60 40 20 0 20 40 60 80 100 120 140 0 10 20 30 40 50 60 70 80 90 100 110 600 700 800 900 1000 1100 1200 1300 04 232 INDOOR UNITS INDOOR UNITS ...

Страница 372: ... SP mode09 700 600 300 200 400 500 60 100 50 90 40 80 20 10 30 70 0 110 z zHeating SP mode09 upper limit Normal SP upper limit SP mode00 upper limit SP mode09 lower limit Normal SP lower limit Hi SP mode09 Hi Normal SP Hi SP mode00 Lo Normal SP Med Normal SP Med SP mode09 Med SP mode00 Lo SP mode00 Lo SP mode09 700 600 300 200 400 500 60 100 50 90 40 80 20 10 30 70 0 110 Airflow m3 h Airflow m3 h ...

Страница 373: ...when Auto louver grille option is installed Fan speed High Vertical flap Up 700 600 300 200 400 500 700 600 300 200 400 500 700 600 300 200 400 500 Capacity Cooling Airflow m3 h Outlet Temperature C 60 100 40 80 20 0 120 140 60 100 40 80 20 0 120 140 13 15 12 14 11 10 16 17 Capacity Outlet Temperature Capacity Heating Airflow m3 h Outlet Temperature C Capacity Outlet Temperature 43 45 42 44 41 40 ...

Страница 374: ...de01 Hi SP mode 06 Hi SP mode02 Hi SP mode07 Hi SP mode08 Hi SP mode09 Hi Normal SP Hi SP mode00 Lo Normal SP Med Normal SP Hi Normal SP Med SP mode09 Med SP mode00 Lo SP mode00 Lo SP mode09 700 600 300 400 500 700 600 300 400 500 60 100 110 50 90 40 80 20 10 30 70 0 60 100 50 90 40 80 20 10 30 70 0 110 Available airflow rate range Hi speed 1 1 Available airflow rate range when Auto louver grille ...

Страница 375: ...et Temperature C Outlet Temperature C 700 600 300 400 500 700 600 300 400 500 60 100 40 80 20 0 120 140 60 100 40 80 20 0 120 140 13 15 12 14 11 10 16 17 Capacity Capacity Outlet Temperature Outlet Temperature 43 45 42 44 41 40 46 47 04 236 INDOOR UNITS INDOOR UNITS ...

Страница 376: ...mode00 Lo SP mode00 Lo SP mode09 60 100 50 90 40 80 20 10 30 70 0 110 700 600 300 400 500 800 700 600 300 400 500 800 60 100 110 50 90 40 80 20 10 70 0 30 Hi SP mode03 Hi SP mode04 Hi SP mode00 Hi SP mode05 Hi SP mode01 Hi SP mode06 Hi SP mode02 Hi SP mode07 Hi SP mode08 Hi SP mode09 Hi Normal SP Available airflow rate range Hi speed 1 1 Available airflow rate range when Auto louver grille option ...

Страница 377: ...emperature C Outlet Temperature C 700 600 300 400 500 60 100 40 80 20 0 120 140 60 100 40 80 20 0 120 140 13 15 12 14 11 10 16 17 Capacity Capacity Outlet Temperature Outlet Temperature 800 700 600 300 400 500 800 43 45 42 44 41 40 46 47 04 238 INDOOR UNITS INDOOR UNITS ...

Страница 378: ...00 Lo SP mode00 Lo SP mode09 700 600 300 400 500 800 700 600 300 400 500 800 60 100 50 90 40 80 20 10 30 70 0 110 120 60 100 50 90 40 80 20 10 30 70 0 110 120 Hi SP mode03 Hi SP mode04 Hi SP mode00 Hi SP mode05 Hi SP mode01 Hi SP mode06 Hi SP mode02 Hi SP mode07 Hi SP mode08 Hi SP mode09 Hi Normal SP Available airflow rate range Hi speed 1 1 Available airflow rate range when Auto louver grille opt...

Страница 379: ...emperature C Outlet Temperature C 700 600 300 400 500 60 100 40 80 20 0 120 140 60 100 40 80 20 0 120 140 13 15 12 14 11 10 16 17 Capacity Capacity Outlet Temperature Outlet Temperature 800 700 600 300 400 500 800 43 45 42 44 41 40 46 47 04 240 INDOOR UNITS INDOOR UNITS ...

Страница 380: ...ode00 Lo SP mode09 60 100 50 90 40 80 20 10 30 70 0 110 120 60 100 50 90 40 80 20 10 30 70 0 110 120 700 600 300 400 500 800 900 1000 700 600 300 400 500 800 900 1000 Hi SP mode03 Hi SP mode04 Hi SP mode00 Hi SP mode05 Hi SP mode01 Hi SP mode06 Hi SP mode02 Hi SP mode07 Hi SP mode08 Hi SP mode09 Hi Normal SP Available airflow rate range Hi speed 1 1 Available airflow rate range when Auto louver gr...

Страница 381: ...e C Outlet Temperature C 60 100 40 80 20 0 120 140 60 100 40 80 20 0 120 140 13 15 12 14 11 10 16 17 43 45 42 44 41 40 46 47 Capacity Capacity Outlet Temperature Outlet Temperature 700 600 300 400 500 800 1000 900 700 600 300 400 500 800 1000 900 04 242 INDOOR UNITS INDOOR UNITS ...

Страница 382: ...SP mode09 60 100 50 90 40 80 20 10 30 70 0 110 120 60 100 50 90 40 80 20 10 30 70 0 110 120 700 600 300 400 500 800 900 1000 1100 1200 700 600 300 400 500 800 900 1000 1100 1200 Hi SP mode03 Hi SP mode04 Hi SP mode00 Hi SP mode05 Hi SP mode01 Hi SP mode06 Hi SP mode02 Hi SP mode07 Hi SP mode08 Hi SP mode09 Hi Normal SP Available airflow rate range Hi speed 1 1 Available airflow rate range when Aut...

Страница 383: ... Temperature C 60 100 40 80 20 0 120 140 60 100 40 80 20 0 120 140 13 15 12 14 11 10 16 17 Capacity Capacity Outlet Temperature Outlet Temperature 700 600 300 400 500 800 1000 900 1100 1200 700 600 300 400 500 800 1000 900 1100 1200 43 45 42 44 41 40 46 47 04 244 INDOOR UNITS INDOOR UNITS ...

Страница 384: ...ode00 Lo SP mode00 Lo SP mode05 60 100 50 90 40 80 20 10 30 70 0 110 120 60 100 50 90 40 80 20 10 30 70 0 110 120 1100 1000 700 800 900 1200 1300 1400 1500 1600 1100 1000 700 800 900 1200 1300 1400 1500 1600 Hi SP mode03 Hi SP mode04 Hi SP mode00 Hi SP mode05 Hi SP mode01 Hi SP mode02 Hi Normal SP Available airflow rate range Hi speed 1 1 Available airflow rate range when Auto louver grille option...

Страница 385: ...perature C 60 100 40 80 20 0 120 140 60 100 40 80 20 0 120 140 13 15 12 14 11 10 16 17 Capacity Capacity Outlet Temperature Outlet Temperature 700 800 1000 900 1100 1200 1300 1400 1500 1600 700 800 1000 900 1100 1200 1300 1400 1500 1600 43 45 42 44 41 40 46 47 04 246 INDOOR UNITS INDOOR UNITS ...

Страница 386: ...0 140 160 1100 1000 700 800 900 1200 1300 1400 1500 600 1100 1000 700 800 900 1200 1300 1400 1500 600 Hi SP mode00 Hi SP mode01 Hi SP mode02 Hi SP mode03 Hi SP mode05 Hi SP mode06 Hi SP mode07 Hi SP mode08 Hi SP mode09 Hi SP mode10 Hi SP mode11 Hi SP mode12 Hi SP mode13 Hi SP mode14 Hi Normal SP 6 4 MEDIUM STATIC PRESSURE DUCT TYPE MODEL ARXA24GBLH Airflow m3 h External Static Pressure Pa External...

Страница 387: ... C 70 100 110 80 90 120 70 100 110 80 90 120 13 15 12 14 11 16 Capacity Capacity Outlet Temperature Outlet Temperature 43 45 42 44 46 47 1100 1000 700 800 900 1200 1300 1400 1500 600 1100 1000 700 800 900 1200 1300 1400 1500 600 Airflow m3 h Airflow m3 h 04 248 INDOOR UNITS INDOOR UNITS ...

Страница 388: ...40 80 20 0 120 140 160 1100 1000 700 800 900 1200 1300 1400 1500 1600 1700 1100 1000 700 800 900 1200 1300 1400 1500 1600 1700 Hi SP mode00 Hi SP mode01 Hi SP mode02 Hi SP mode03 Hi SP mode04 Hi SP mode06 Hi SP mode07 Hi SP mode08 Hi SP mode09 Hi SP mode10 Hi SP mode11 Hi SP mode12 Hi SP mode13 Hi SP mode14 Hi Normal SP MODEL ARXA30GBLH Airflow m3 h External Static Pressure Pa External Static Pres...

Страница 389: ...0 80 90 120 70 100 110 80 90 120 13 12 14 11 10 9 Capacity Capacity Outlet Temperature Outlet Temperature 45 44 46 47 48 49 Airflow m3 h Airflow m3 h 1100 1000 700 800 900 1200 1300 1400 1500 1600 1700 1100 1000 700 800 900 1200 1300 1400 1500 1600 1700 04 250 INDOOR UNITS INDOOR UNITS ...

Страница 390: ... 100 40 80 20 0 120 140 160 1100 1000 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 1100 1000 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 Hi SP mode00 Hi SP mode01 Hi SP mode02 Hi SP mode03 Hi SP mode04 Hi SP mode06 Hi SP mode07 Hi SP mode08 Hi SP mode09 Hi SP mode10 Hi SP mode11 Hi SP mode12 Hi Normal SP MODEL ARXA36GBLH Airflow m3 h External Static Pressure Pa External Static Pressure ...

Страница 391: ... Outlet Temperature Outlet Temperature 45 44 46 47 48 49 Airflow m3 h Airflow m3 h 1100 1000 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 1100 1000 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 70 100 80 90 120 110 70 100 80 90 120 110 13 14 15 12 11 10 04 252 INDOOR UNITS INDOOR UNITS ...

Страница 392: ...0 100 40 80 20 0 120 140 160 1100 1000 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 1100 1000 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 Hi SP mode00 Hi SP mode01 Hi SP mode02 Hi SP mode03 Hi SP mode04 Hi SP mode05 Hi SP mode07 Hi SP mode08 Hi SP mode09 Hi SP mode10 Hi SP mode11 Hi Normal SP MODEL ARXA45GBLH Airflow m3 h External Static Pressure Pa External Static Pressure Pa...

Страница 393: ...city Capacity Outlet Temperature Outlet Temperature 45 44 46 47 48 49 Airflow m3 h Airflow m3 h 70 100 80 90 120 110 70 100 80 90 120 110 1100 1000 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 1100 1000 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 04 254 INDOOR UNITS INDOOR UNITS ...

Страница 394: ... 100 40 80 20 0 120 160 200 60 100 40 80 20 0 120 160 200 1200 1400 1600 1800 2000 2200 Hi SP mode06 Hi SP mode12 Hi SP mode02 Hi SP mode03 Hi SP mode04 Hi SP mode05 Hi SP mode07 Hi SP mode08 Hi SP mode09 Hi SP mode13 Hi SP mode15 Hi SP mode16 Hi SP mode14 Hi SP mode11 Hi Normal SP Airflow m3 h External Static Pressure Pa External Static Pressure Pa 600 800 1000 1200 1400 1600 1800 2000 2200 600 8...

Страница 395: ...22 26 30 18 14 10 Capacity Capacity Outlet Temperature Outlet Temperature 39 35 43 47 51 55 Airflow m3 h Airflow m3 h 70 100 80 90 120 110 70 100 80 90 120 110 1200 1400 1600 1800 2000 2200 600 800 1000 1200 1400 1600 1800 2000 2200 600 800 1000 04 256 INDOOR UNITS INDOOR UNITS ...

Страница 396: ...Airflow m3 h Airflow m3 h 0 50 100 150 200 250 300 1 000 1 500 2 000 2 500 3 000 3 500 4 000 80 90 100 110 120 1 000 1 500 2 000 2 500 3 000 3 500 4 000 8 10 12 14 16 80 90 100 110 120 1 000 1 500 2 000 2 500 3 000 3 500 4 000 35 40 45 50 55 Outlet Temperature Outlet Temperature Capacity Lo Hi Capacity 04 257 INDOOR UNITS INDOOR UNITS ...

Страница 397: ...Airflow m3 h Airflow m3 h 0 50 100 150 200 250 300 1 000 1 500 2 000 2 500 3 000 3 500 4 000 80 90 100 110 120 1 000 1 500 2 000 2 500 3 000 3 500 4 000 8 10 12 14 16 80 90 100 110 120 1 000 1 500 2 000 2 500 3 000 3 500 4 000 35 40 45 50 55 Outlet Temperature Outlet Temperature Capacity Lo Hi Capacity 04 258 INDOOR UNITS INDOOR UNITS ...

Страница 398: ...4 Lo SP mode27 50 100 0 200 250 300 11 23 19 17 21 07 Hi SP mode05 08 06 Hi SP mode04 09 10 12 13 14 24 26 Hi SP mode27 25 22 20 18 16 Normal SP Airflow m3 h External Static Pressure Pa External Static Pressure Pa 150 0 2000 2000 2200 2200 2800 2800 3800 3800 2400 2400 3400 3400 3000 3000 4000 4000 2600 2600 3600 3600 3200 3200 4200 4200 4400 4400 50 100 200 250 300 150 04 259 INDOOR UNITS INDOOR ...

Страница 399: ...city Capacity Outlet Temperature Outlet Temperature 44 40 48 52 56 60 Airflow m3 h Airflow m3 h 70 100 80 90 120 110 70 100 80 90 120 110 2000 2200 2800 3800 2400 3400 3000 4000 2600 3600 3200 4200 4400 2000 2200 2800 3800 2400 3400 3000 4000 2600 3600 3200 4200 4400 04 260 INDOOR UNITS INDOOR UNITS ...

Страница 400: ...P lower limit SP mode05 upper limit SP mode24 lower limit Hi SP mode24 Hi Normal SP Hi SP mode05 Lo Normal SP Lo SP mode05 Lo SP mode24 100 0 50 200 06 Hi SP mode19 17 12 10 Hi SP mode05 07 08 09 Hi SP mode20 13 Hi SP mode22 Hi SP mode24 Hi SP mode23 16 Hi SP mode21 14 18 11 NormalSP Airflow m3 h External Static Pressure Pa External Static Pressure Pa 150 250 0 300 100 50 200 150 250 04 261 INDOOR...

Страница 401: ...city Capacity Outlet Temperature Outlet Temperature Airflow m3 h Airflow m3 h 70 100 80 90 120 110 70 100 80 90 120 110 4600 4600 4800 4800 2800 2800 3800 3800 5000 5000 3400 3400 3000 3000 4000 4000 2600 2600 3600 3600 3200 3200 4200 4200 4400 4400 44 40 48 52 56 60 04 262 INDOOR UNITS INDOOR UNITS ...

Страница 402: ...mit SP mode29 lower limit Hi SP mode29 Hi Normal SP Hi SP mode05 Lo Normal SP Lo SP mode05 Lo SP mode24 06 17 19 21 23 25 27 28 12 10 Hi SP mode05 07 08 09 13 Hi SP mode29 16 14 18 20 22 24 26 11 NormalSP Airflow m3 h External Static Pressure Pa External Static Pressure Pa 0 300 100 50 200 150 250 0 300 100 50 200 150 250 04 263 INDOOR UNITS INDOOR UNITS ...

Страница 403: ...irflow m3 h Airflow m3 h 70 100 80 90 120 110 70 100 80 90 120 110 5000 3000 4000 6000 5000 3000 4000 6000 15 16 17 14 13 12 41 40 42 43 44 45 Outlet Temperature C Outlet Temperature C Outlet Temperature Outlet Temperature 04 264 INDOOR UNITS INDOOR UNITS ...

Страница 404: ...500 2100 1300 2300 2200 1200 1100 1000 1400 1800 1900 2000 External Static Pressure Pa 90 70 80 110 100 120 60 20 30 40 50 0 10 Airflow m3 h 800 900 1700 1600 1500 2100 1300 2300 2200 1200 1100 1000 1400 1800 1900 2000 External Static Pressure Pa Hi SP mode02 Hi SP mode00 Hi SP mode01 Hi SP mode04 Hi Normal SP Hi SP mode06 Hi SP mode07 Hi SP mode08 Hi SP mode03 Available airflow rate Hi speed 90 7...

Страница 405: ...200 1000 1400 1800 2000 Airflow m3 h Outlet Temperature C 14 15 16 13 12 11 10 18 17 Capacity Capacity Outlet Temperature Heating 130 140 120 80 90 100 110 60 70 Outlet Temperature C 46 47 48 45 44 43 42 50 49 800 1600 2200 1200 1000 1400 1800 2000 Airflow m3 h 04 266 INDOOR UNITS INDOOR UNITS ...

Страница 406: ...400 1600 2600 2500 1500 1400 1300 1700 2100 2200 2300 External Static Pressure Pa 90 70 80 110 100 120 60 20 30 40 50 0 10 Airflow m3 h 1100 1200 2000 1900 1800 2400 1600 2600 2500 1500 1400 1300 1700 2100 2200 2300 External Static Pressure Pa 90 70 80 110 100 120 60 20 30 40 50 0 10 Hi SP mode02 Hi SP mode00 Hi SP mode01 Available airflow rate Hi speed Hi SP mode03 Hi SP mode04 Hi Normal SP Hi SP...

Страница 407: ...900 1300 1300 1700 1700 2100 2100 2300 2300 Airflow m3 h Outlet Temperature C 14 15 16 13 12 11 10 18 17 2500 2500 1500 1500 Capacity Capacity Outlet Temperature Heating 130 140 120 80 90 100 110 60 70 Outlet Temperature C 46 47 48 45 44 43 42 50 49 Airflow m3 h 04 268 INDOOR UNITS INDOOR UNITS ...

Страница 408: ...0 3200 1600 1400 2000 2600 2800 Airflow m3 h 1200 2400 2200 3000 1800 3200 1600 1400 2000 2600 2800 External Static Pressure Pa 90 70 80 110 100 120 60 20 30 40 50 0 10 External Static Pressure Pa 90 70 80 110 100 120 60 20 30 40 50 0 10 Hi SP mode02 Hi SP mode00 Hi SP mode01 Available airflow rate Hi speed Hi SP mode03 Hi SP mode04 Hi Normal SP Hi SP mode06 Hi SP mode07 Hi SP mode08 Hi SP mode09 ...

Страница 409: ...3 12 11 10 18 17 Capacity Capacity Outlet Temperature Heating 130 140 120 80 90 100 110 60 70 Outlet Temperature C 46 47 48 45 44 43 42 50 49 Airflow m3 h 1200 2400 2200 3000 1800 3200 1600 1400 2000 2600 2800 Airflow m3 h 1200 2400 2200 3000 1800 3200 1600 1400 2000 2600 2800 04 270 INDOOR UNITS INDOOR UNITS ...

Страница 410: ... MODEL ARXN18GATH SP mode06 SP mode07 SP mode08 SP mode09 SP mode10 Normal SP External Static Pressure Pa Airflow m3 h 1500 2000 2500 3000 3500 300 250 200 150 100 50 0 04 271 INDOOR UNITS INDOOR UNITS ...

Страница 411: ...let Temperature C 14 15 16 13 12 11 48 49 50 47 46 45 Capacity Capacity Outlet Temperature Outlet Temperature 70 100 80 90 120 110 70 100 80 90 120 110 Airflow m3 h 1500 2000 2500 3000 3500 Airflow m3 h 1500 2000 2500 3000 3500 04 272 INDOOR UNITS INDOOR UNITS ...

Страница 412: ...06 SP mode07 SP mode08 SP mode09 SP mode10 SP mode12 SP mode14 SP mode11 SP mode13 SP mode15 Normal SP External Static Pressure Pa Airflow m3 h 1500 2000 2500 3000 3500 300 250 200 150 100 50 0 04 273 INDOOR UNITS INDOOR UNITS ...

Страница 413: ...let Temperature C 14 15 16 13 12 11 48 49 50 47 46 45 Capacity Capacity Outlet Temperature Outlet Temperature 70 100 80 90 120 110 70 100 80 90 120 110 Airflow m3 h 1500 2000 2500 3000 3500 Airflow m3 h 1500 2000 2500 3000 3500 04 274 INDOOR UNITS INDOOR UNITS ...

Страница 414: ...12 SP mode14 SP mode16 SP mode18 SP mode20 SP mode22 SP mode24 SP mode11 SP mode13 SP mode15 SP mode17 SP mode19 SP mode21 SP mode23 SP mode25 Normal SP External Static Pressure Pa Airflow m3 h 2000 2500 3000 3500 4000 300 250 200 150 100 50 0 04 275 INDOOR UNITS INDOOR UNITS ...

Страница 415: ...let Temperature C 14 15 16 13 12 11 44 45 46 43 42 41 Capacity Outlet Temperature Outlet Temperature 70 100 80 90 120 110 70 100 80 90 120 110 Airflow m3 h 2000 2500 3000 3500 4000 Airflow m3 h 2000 2500 3000 3500 4000 Capacity 04 276 INDOOR UNITS INDOOR UNITS ...

Страница 416: ...12 SP mode14 SP mode16 SP mode18 SP mode20 SP mode22 SP mode24 SP mode11 SP mode13 SP mode15 SP mode17 SP mode19 SP mode21 SP mode23 SP mode25 Normal SP External Static Pressure Pa Airflow m3 h 3000 3500 4000 4500 5000 300 250 200 150 100 50 0 04 277 INDOOR UNITS INDOOR UNITS ...

Страница 417: ...let Temperature C 14 15 16 13 12 11 42 43 44 41 40 39 Capacity Capacity Outlet Temperature Outlet Temperature 70 100 80 90 120 110 70 100 80 90 120 110 Airflow m3 h 3000 3500 4000 4500 5000 Airflow m3 h 3000 3500 4000 4500 5000 04 278 INDOOR UNITS INDOOR UNITS ...

Страница 418: ...12 SP mode14 SP mode16 SP mode18 SP mode20 SP mode22 SP mode24 SP mode11 SP mode13 SP mode15 SP mode17 SP mode19 SP mode21 SP mode23 SP mode25 SP mode05 External Static Pressure Pa Airflow m3 h 3000 3500 4000 4500 5000 300 250 200 150 100 50 0 04 279 INDOOR UNITS INDOOR UNITS ...

Страница 419: ...let Temperature C 14 15 16 13 12 11 40 41 42 39 38 37 Capacity Capacity Outlet Temperature Outlet Temperature 70 100 80 90 120 110 70 100 80 90 120 110 Airflow m3 h 3000 3500 4000 4500 5000 Airflow m3 h 3000 3500 4000 4500 5000 04 280 INDOOR UNITS INDOOR UNITS ...

Страница 420: ...12 SP mode14 SP mode16 SP mode18 SP mode20 SP mode22 SP mode24 SP mode11 SP mode13 SP mode15 SP mode17 SP mode19 SP mode21 SP mode23 SP mode25 SP mode05 External Static Pressure Pa Airflow m3 h 3000 3500 4000 4500 5000 300 250 200 150 100 50 0 04 281 INDOOR UNITS INDOOR UNITS ...

Страница 421: ...let Temperature C 14 15 16 13 12 11 40 41 42 39 38 37 Capacity Capacity Outlet Temperature Outlet Temperature 70 100 80 90 120 110 70 100 80 90 120 110 Airflow m3 h 3000 3500 4000 4500 5000 Airflow m3 h 3000 3500 4000 4500 5000 04 282 INDOOR UNITS INDOOR UNITS ...

Страница 422: ...atic pressure of Fresh air intake characteristics Duct static pressure Pa Airflow m3 min 0 1 2 3 4 5 0 1 2 3 4 5 AB30 AB36 45 54 z zInstallation For half concealed installation Fresh air inlet position UTD RF204 Optional parts Flexible duct 1 1 Locally procured parts 04 283 INDOOR UNITS INDOOR UNITS ...

Страница 423: ... Inside Dia ø70mm Static pressure required to take in fresh air Duct Fan 98 49 0 10 8 6 4 2 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 Airflow m3 min Duct static pressure Pa Duct static pressure mmAq z zInstallation Fresh air inlet position Duct flange 2 Flexible duct 2 Flexible duct 2 Fan 2 Insulation 1 Top view 2 5 mm hole 4 70 mm 62 mm 62 mm Detail B Fresh air inlet position A View A Fresh air inlet posit...

Страница 424: ...d 810 225 477 Low 730 203 430 Type Model Airflow m3 h l s CFM Compact cassette AUXB04 GBLH GALH High 530 147 312 Med 1 450 420 125 117 265 247 Low 1 350 300 97 83 206 177 AUXB07 GALH High 540 150 318 Med 450 125 265 Low 350 97 206 AUXB09 GALH High 550 153 324 Med 450 125 265 Low 350 97 206 AUXB12 GALH High 600 167 353 Med 530 147 312 Low 390 108 230 AUXB14 GALH High 680 189 400 Med 590 164 347 Low...

Страница 425: ...000 277 589 Med 720 199 424 Low 580 161 342 AB A24 GATH High 1000 277 589 Med 820 227 483 Low 680 188 401 1 This value is cooling operation heating operation Type Model Airflow m3 h l s CFM Mini duct ARXK04 GCLH High 460 128 271 Me Hi 440 122 259 Med 420 117 247 Lo Hi 400 111 235 Low 370 103 218 Quiet 340 94 200 ARXK07 GCLH High 460 128 271 Me Hi 440 122 259 Med 420 117 247 Lo Hi 400 111 235 Low 3...

Страница 426: ...High 1630 452 960 Med 1370 379 807 Low 1140 316 671 AB A36 GATH High 1690 469 995 Med 1400 389 824 Low 1170 325 689 AB A45 GATH High 2010 558 1183 Med 1600 444 942 Low 1230 342 724 AB A54 GATH High 2270 629 1337 Med 1780 493 1048 Low 1280 355 754 Compact floor AG A004 GCAH High 1 380 430 106 119 224 253 Me Hi 350 97 206 Med 320 89 188 Lo Hi 310 86 182 Low 280 78 165 Quiet 210 58 124 AG A007 GCAH H...

Страница 427: ... Quiet 330 92 194 AS A007 GTAH High 550 153 324 Me Hi 460 128 271 Med 420 117 247 Lo Hi 390 108 230 Low 360 100 212 Quiet 330 92 194 AS A009 GTAH High 720 200 424 Me Hi 570 158 336 Med 500 139 294 Lo Hi 410 114 241 Low 360 100 212 Quiet 330 92 194 AS A012 GCAH High 690 192 406 Me Hi 610 169 359 Med 560 156 330 Lo Hi 530 147 312 Low 470 131 277 Quiet 330 92 194 AS A014 GCAH High 800 222 471 Me Hi 7...

Страница 428: ...125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 Low High Med MODEL AUXB07GALH MODEL AUXB09GALH Octave band sound pressure level dB 0dB 0 0002µbar Octave band center frequency Hz Med High Low 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 Octave band sound pressu...

Страница 429: ... 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 MODEL AUXB18GALH MODEL AUXB24GALH Octave band center frequency Hz Octave band sound pressure level dB 0dB 0 0002µbar 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 Med High Low Octave band sound pressure level dB 0dB 0 0002µbar Oct...

Страница 430: ... dB 0dB 0 0002µbar Octave band center frequency Hz Octave band center frequency Hz Octave band sound pressure level dB 0dB 0 0002µbar Octave band sound pressure level dB 0dB 0 0002µbar Octave band center frequency Hz Octave band sound pressure level dB 0dB 0 0002µbar Octave band center frequency Hz 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15...

Страница 431: ...bar Octave band center frequency Hz Octave band sound pressure level dB 0dB 0 0002µbar Octave band center frequency Hz Octave band sound pressure level dB 0dB 0 0002µbar Octave band center frequency Hz Octave band sound pressure level dB 0dB 0 0002µbar Octave band center frequency Hz Med High Low 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 N...

Страница 432: ...ure level dB 0dB 0 0002µbar Octave band center frequency Hz Octave band sound pressure level dB 0dB 0 0002µbar Octave band center frequency Hz Octave band sound pressure level dB 0dB 0 0002µbar Octave band center frequency Hz Octave band sound pressure level dB 0dB 0 0002µbar Octave band center frequency Hz 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC...

Страница 433: ...B 0 0002µbar Octave band center frequency Hz Octave band sound pressure level dB 0dB 0 0002µbar Octave band center frequency Hz Octave band sound pressure level dB 0dB 0 0002µbar Octave band center frequency Hz Octave band sound pressure level dB 0dB 0 0002µbar Octave band center frequency Hz 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25...

Страница 434: ... pressure level dB 0dB 0 0002µbar Octave band center frequency Hz NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 High Low Med 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 40 NC 20 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 High Low Med 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 04 295 INDOOR UNITS INDOOR UNITS ...

Страница 435: ...enter frequency Hz NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 High Low Med 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 High Low Med 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 45 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 55 NC 65 High Low Med 0 10 20 30 40 ...

Страница 436: ...center frequency Hz NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 High Low 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 High Low NC 40 NC 20 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 High Low 0 10 20 30 40 50 60 70 80...

Страница 437: ...B 0 0002µbar Octave band center frequency Hz NC 45 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 55 NC 65 High Low 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 45 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 55 NC 65 High Low 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 04 298 INDOOR UNITS INDOOR UNITS ...

Страница 438: ...50 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 Low High MODEL ARXD07GALH MODEL ARXD09GALH Octave band center frequency Hz Octave band sound pressure level dB 0dB 0 0002µbar NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 High Low 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 Octave band sound pressure level dB 0...

Страница 439: ...C 55 NC 65 High Low 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 MODEL ARXD18GALH MODEL ARXD24GALH Octave band sound pressure level dB 0dB 0 0002µbar Octave band center frequency Hz High Low NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 Octave band sound pressure level dB 0dB 0 0002µbar Octave ...

Страница 440: ...r frequency Hz NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 High Low Med 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 High Low Med 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 High Low Med 0 10 20 30 40 50 6...

Страница 441: ... 0002µbar Octave band center frequency Hz 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 High Low 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 High Low 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 N...

Страница 442: ... Octave band sound pressure level dB 0dB 0 0002µbar Octave band center frequency Hz Octave band sound pressure level dB 0dB 0 0002µbar Octave band center frequency Hz 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 High Low 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 3...

Страница 443: ...002µbar Octave band center frequency Hz 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 High Low 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 High Low 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC ...

Страница 444: ...nd center frequency Hz NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 ...

Страница 445: ...band sound pressure level dB 0dB 0 0002µbar Octave band center frequency Hz NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 04 306 INDOOR UNITS INDOOR UNITS ...

Страница 446: ...nter frequency Hz 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 High Low NC 45 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 55 NC 65 High Low 0 10 20 30 40 50 60 70 80 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 2...

Страница 447: ... frequency Hz 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 High Low NC 25 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 High Low 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25...

Страница 448: ...enter frequency Hz 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 High Low 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 High Low 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 ...

Страница 449: ... pressure level dB 0dB 0 0002µbar Octave band center frequency Hz 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 High Low 04 310 INDOOR UNITS INDOOR UNITS ...

Страница 450: ...ve band center frequency Hz 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 High Low 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 High Low 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC ...

Страница 451: ... pressure level dB 0dB 0 0002µbar Octave band center frequency Hz 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 High Low 04 312 INDOOR UNITS INDOOR UNITS ...

Страница 452: ...2µbar Octave band center frequency Hz 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 High Low 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 High Low 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50...

Страница 453: ... 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 Low High High Octave band center frequency Hz Octave band sound pressure level dB 0dB 0 0002µbar 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 High High Low 04 314 INDOOR UNITS INDOOR UNITS ...

Страница 454: ... 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 High Med Low MODEL AS A07GACH MODEL AS A09GACH Octave band center frequency Hz Octave band sound pressure level dB 0dB 0 0002µbar 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 Med High Low Octave band center frequency Hz Octave band sound pre...

Страница 455: ... 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 Med High Low Octave band center frequency Hz Octave band sound pressure level dB 0dB 0 0002µbar 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 Med High Low 04 316 INDOOR UNITS INDOOR UNITS ...

Страница 456: ...µbar Octave band center frequency Hz NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 High Low 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 High Low 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 High Low 0 10 20 ...

Страница 457: ...dB 0 0002µbar Octave band center frequency Hz 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 High Low 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 High Low 04 318 INDOOR UNITS INDOOR UNITS ...

Страница 458: ...0dB 0 0002µbar Octave band center frequency Hz 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 High Low 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 High Low 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC...

Страница 459: ...dB 0 0002µbar Octave band center frequency Hz 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 Low High 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 Low High 04 320 INDOOR UNITS INDOOR UNITS ...

Страница 460: ... 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 Low High Med MODEL AS E07GACH MODEL AS E09GACH Octave band sound pressure level dB 0dB 0 0002µbar Octave band center frequency Hz 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 Med High Low Octave band sound pressure level dB 0dB 0 0002µbar Oc...

Страница 461: ...0002µbar Octave band center frequency Hz 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 Med High Low 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 NC 20 NC 40 NC 50 NC 60 NC 30 NC 15 NC 25 NC 35 NC 45 NC 55 NC 65 Med High Low 04 322 INDOOR UNITS INDOOR UNITS ...

Страница 462: ...ic pressure duct type Medium static pressure duct type High static pressure duct type Large airflow duct type z zFloor Ceiling type Compact floor type z zCeiling type z z Wall mounted type MIC Air 1 5m 2m 1m Air Microphone Airflow 1 m Airflow 1 m MIC 1 5m MIC 1m 1m MIC 1m 1m 04 323 INDOOR UNITS INDOOR UNITS ...

Страница 463: ...3 15A Activate at 110 15 10 C Fan motor stop Reset at 105 15 10 C Fan motor restart AUXD24GALH AUXA18GALH AUXA24GALH AUXA30GALH AUXA34GALH AUXA36GALH AUXA45GALH AUXA54GALH Low static pressure duct Concealed floor ARXB07GALH 250V 3 15A Activate at 140 5 C Fan motor stop 2 ARXB09GALH ARXB12GALH ARXB14GALH ARXB18GALH Activate at 150 5 C Fan motor stop Mini duct ARXK04GCLH 250V 3 15A Activate at 135 1...

Страница 464: ...024GTBH Activate at 100 5 C Fan motor stop Reset at 70 15 C Fan motor restart ARXN030GTBH ARXN18GATH 250V 3 15A 250V 20A 1 Activate at 100 15 10 C Fan motor stop Reset at 95 15 10 C Fan motor restart ARXN24GATH ARXN30GATH ARXN34GATH ARXN36GATH ARXN45GATH Floor ceiling AB A12GATH 250V 3 15A Activate at 135 15 C Fan motor stop Reset at 115 15 C Fan motor restart AB A14GATH AB A18GATH AB A24GATH Ceil...

Страница 465: ...120 15 C Fan motor stop Activate at 102 C AS A24GBCH AS A18GACH AS A24GACH AS A30GACH AS A030GTAH Activate at 150 15 C Fan motor stop Reset less than 135 C Fan motor restart AS A034GTAH Wall mounted EEV external model AS E004GTAH 250V 3 15A Activate at 160 25 C Fan motor stop Reset at 110 25 C Fan motor restart AS E007GTAH AS E009GTAH AS E012GCAH Activate at 160 25 C Fan motor stop Reset at 110 25...

Страница 466: ...5 CONTROL SYSTEM DTV_VR2E018E_12 CHAPTER05 2017 10 31 ...

Страница 467: ...L UTY ALGX Option UTY PLGXA1 UTY PLGXR1 UTY PLGXE1 05 33 2 3 TOUCH PANEL CONTROLLER 05 38 2 4 CENTRAL REMOTE CONTROLLER 05 53 2 5 GROUP REMOTE CONTROLLER 05 61 2 6 WIRED REMOTE CONTROLLER Touch panel 05 65 2 7 WIRED REMOTE CONTROLLER 05 70 2 8 WIRED REMOTE CONTROLLER 05 74 2 9 SIMPLE REMOTE CONTROLLER With Operation mode 05 79 2 9 1 MODEL UTY RSR 05 79 2 9 2 MODEL UTY RSK 05 84 2 10 SIMPLE REMOTE ...

Страница 468: ...05 145 3 6 MODBUS CONVERTOR FOR INDOOR UNIT 05 154 3 7 NETWORK CONVERTOR FOR LONWORKS 05 160 3 8 BACnet GATEWAY HARDWARE 05 170 3 9 BACnet GATEWAY SOFTWARE 05 179 3 9 1 MODEL UTY ABGXZ1 05 179 3 9 2 MODEL UTY ABGX 05 184 3 10 SIGNAL AMPLIFIER 05 189 3 11 WIRELESS LAN ADAPTER 05 193 3 12 EXTERNAL SWITCH CONTROLLER 05 196 3 12 1 MODEL UTY TERX 05 196 3 12 2 MODEL UTY TEKX 05 203 4 SERVICE WEB MONITO...

Страница 469: ...se setting operation Control System Configuration Expansion Optimum system configuration by various controller combinations allowing for various applications and future expansion Free System Configuration Up to 400 indoor units are connectable in one system System is adaptable to various applications from small to large buildings Flexible Control System to Meet a Variety of Needs Flexible Control ...

Страница 470: ...ing can be supported by additional options in order to meet your demands Group Remote Controller UTY CGG UTY CGGGU Group control of indoor units with simple operation Network convertor UTY VGGX is required to connect group remote controllers to a VRF system UTY CGGGU is for UAE market only Remote side VRF network system side System Status Error Information Error notification can be automatically t...

Страница 471: ...le and sophisticated operation with a choice of 4 daily timers UTY LNHGU is for UAE market only Simple Remote Controller With Operation mode UTY RSR UTY RSK Compact remote controller concentrates on the basic functions such as Start Stop Fan Control Temperature Setting and Operation mode UTY RSK is not available in UAE market Simple Remote Controller Without Operation mode UTY RHR UTY RHK Compact ...

Страница 472: ...Multi system UTY ASGXZ1 Software UTY AMGXZ1 Software VRF network system Side User Side Monitoring side Remote Monitoring side Transmission line VRF Network Transmission line LONWORKS Network LONWORKS Network Modbus Network USB line Remote controller line 3 wire Remote controller line 2 wire Remote controller line Single system Signal line Single system Shielded Twist Pair Cable Remote controller l...

Страница 473: ...otel or office guest Wired simple and wireless remote controllers can be used jointly 2 remote controllers can be connected with single indoor unit Up to 16 indoor units can be controlled with one simple remote controller Enables easy control of basic functions by the hotel or office guest Wired simple and wireless remote controllers can be used jointly 4 remote controllers can be connected with s...

Страница 474: ... system or Big multi system can be connected to the VRF network system and can be controlled from Touch panel controller or System controller Wired remote controller Touch panel controller Network Convertor UTY VGGXZ1 Single split system or Big multi system Combination with Single split or Big multi type Up to 16 indoor units Single control for hotel room with switch External switch controller Car...

Страница 475: ...ntrolled with one group remote controller Up to 4 Group remote controllers can be connected to a single network convertor UTY VGGXZ1 One network convertor UTY VGGXZ1 is allowed 2 refrigerant systems Up to a total of 16 network convertors central remote controllers and touch panel controllers group remote controller and network convertor for LONWORKS can be connected to single VRF network system 1 ...

Страница 476: ... 400 indoor units 400 groups can be controlled with one touch panel controller Up to a total of 16 network convertors central remote controllers and touch panel controllers group remote controller and network convertor for LONWORKS can be connected to a single VRF network system Commercial building Medium class Touch panel controller Touch panel controller Up to 16 Touch panel controllers Up to 10...

Страница 477: ...er Client 1 VRF network system 400 Indoor units 100 Outdor units Max controllable 3 600m Max transmission line length USB Port On site central control Max 4 VRF network systems USB Adaptor System Controller Client Internet or Telephone Line or LAN Server Server Server Server Server Remote central control Controlled sites of up to 10 System Controller System Controller System Controller System Cont...

Страница 478: ...entral control Monitored from up to 100 users 1 Personal Computer Personal Computer Personal Computer Personal Computer Personal Computer Touch Panel Controller Site with VRF system 1 Up to 4 administrators and 10 general users can log in simultaneously 05 10 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 479: ... Static Pressure Duct 3 High Static Pressure Duct 3 Large Airflow Duct 3 Compact Floor 7 7 Compact Floor EEV external 7 7 Floor Ceiling Ceiling Wall Mounted EEV external 6 7 7 4 Wall Mounted 6 7 7 5 1 UTY LNHGU is for UAE market only 2 IR Receiver Unit Optional part UTY LRH B1 is necessary 3 IR Receiver Unit Optional part UTB WC is necessary 4 AS 004 007 009GTAH only 5 AS A030 034GTAH only 6 It is...

Страница 480: ...Locally purchased Network Convertor for LonWorks UTY VLGX BACnet Gateway UTY VBGX UTY ABGXZ1 UTY ABGX Modbus Convertor UTY VMGX UTY VMSX KNX Convertor UTY VKGX UTY VKSX VRF network system Other System Single Split system Other System Single Split System Multi System BMS BAS Network Convertor UTY VTGX UTY VTGXV UTY VGGXZ1 USB adaptor 3 Locally purchased Network Convertor for LonWorks UTY VLGX BACne...

Страница 481: ...lications By adopting a separate interface it is possible to connect other products and systems by FUJITSU GENERAL such as Single type models excluding some models J series or Multi air conditioner for buildings e g Big multi Refer to 3 1 NETWORK CONVERTOR System Controller allows to control up to 4 VRF network systems Max 1600 indoor units suitable for huge scale application RELIABILITY AND EASY ...

Страница 482: ... network system side Monitoring side Monitoring side BACnet Gateway UTY ABGXZ1 BACnet BACnet 3 600 m Max Transmission line length BACnet Operator Workstation B OWS Combination of individual remote controller Wired simple and wireless remote controllers can be used jointly Monitoring side Internet USB Adaptor USB Adaptor Internet or Public Telephone Line Internet Central Remote Controller Maximum 1...

Страница 483: ...tem 2 Network Convertor for LONWORKS 4 UTY VLGX 1 system 128 3 100 BACnet Gateway UTY VBGX 4 system 128 3 100 UTY ABGXZ1 UTY ABGX USB Adaptor 1 system 1600 4 VRF Networks 400 4 VRF Networks Modbus Convertor UTY VMGX 9 system 128 3 100 UTY VMSX 1 KNX Convertor UTY VKGX 9 system 128 3 100 UTY VKSX 1 Signal Amplifier UTY VSGXZ1 40 system Wireless LAN adapter UTY TFSXZ1 Service and Maintenance Service...

Страница 484: ...ple Remote Controller with operation mode UTY RSR Simple Remote Controller without operation mode UTY RHR Wired Remote Controller UTY RNK 2 Remote control group 3 wire type Simple Remote Controller with operation mode UTY RSK Simple Remote Controller without operation mode UTY RHK Adaptor Convertor External Switch Controller UTY TERX UTY TEKX 2 wire 3 wire type IR Receiver unit 1 Indoor unit 1 UTY...

Страница 485: ...thout operation mode z zWireless Remote Controller z zIR Receiver Unit Central Control System Controller System Controller Lite Touch Panel Controller Group Remote Controller Central Remote Controller Individual Control Simple Remote Controller With operation mode Without operation mode IR Receiver Unit Wired Remote Controller Touch panel SET TEMP START STOP Wireless Remote Controller 05 17 CONTRO...

Страница 486: ...g manager and owner needs are met Corresponds to 7 different languages English Chinese French German Spanish Russian Polish Connection between VRF network system to personal computer is possible via small U10 USB interface However both U10 USB interface and personal computer are locally purchased items Extended feature supported by use of options Electricity charge apportionment using electricity ...

Страница 487: ...n site control Max 4 VRF network systems USB Port Internet or Telephone Line or LAN VRF Explorer VRF Explorer VRF Explorer VRF Building 1 Building Management Company A In charge of the day shift Remote centralized control maintenance center Remote control maintenance to multiple buildings Remote control maintenance from multiple sites Building Management Company B In charge of the night shift Secu...

Страница 488: ...4 bit SP1 Microsoft Windows 8 1 32 bit or 64 bit Windows 8 1 Pro 32 bit or 64 bit Microsoft Windows 10 Home 32 bit or 64 bit Windows 10 Pro 32 bit or 64 bit Supported languages English Chinese French German Russian Spanish and Polish CPU Intel CoreTM i3 2 GHz or higher Memory 2 GB or more for Windows 7 32 bit 4 GB or more for Windows 7 64 bit Windows 8 1 and Windows 10 HDD 40 GB or more of free sp...

Страница 489: ... 600 1 unit may belong to up to 1 600 groups Auto generation By site building and floor Memory operation Operation pattern memorized and reused Pattern operation Reuse operation pattern once used Operation status monitoring Controlled status See items controlled by operation Special operation Defrost Oil Recovery Room Temp Room temperature 1 Error management Error notification Audible alarm Error ...

Страница 490: ...an Spanish Russian Polish Floor layout editor Floor layout import export NOTE In S and V series there are some functions that cannot be used such as energy saving function and elec tricity meter use The electricity charge apportionment function of VRF system can only be performed from one equipment simultaneously 1 To display the room temperature on the monitor connect the wired remote controller ...

Страница 491: ...r needs are met Corresponds to 7 different languages English Chinese French German Spanish Russian Polish Connection between VRF network system to personal computer is possible via small U10 USB interface However both U10 USB interface and personal computer are locally purchased items Extended feature supported by use of options Electricity charge apportionment using electricity meter energy savin...

Страница 492: ... Internet or Telephone Line or LAN VRF Explorer VRF Explorer VRF Explorer VRF Building 1 Building Management Company A In charge of the day shift Remote centralized control maintenance center Remote control maintenance to multiple buildings Remote control maintenance from multiple sites Building Management Company B In charge of the night shift Security Company VRF Building 2 VRF Building 3 VRF Bu...

Страница 493: ...L COMPUTER SYSTEM REQUIREMENTS Operating system Microsoft Windows 7 Home Premium 32 bit or 64 bit SP1 Windows 7 Professional 32 bit or 64 bit SP1 Microsoft Windows 8 1 32 bit or 64 bit Windows 8 1 Pro 32 bit or 64 bit Microsoft Windows 10 Home 32 bit or 64 bit Windows 10 Pro 32 bit or 64 bit Supported languages English Chinese French German Russian Spanish and Polish CPU Intel CoreTM i3 2 GHz or h...

Страница 494: ...ation pattern once used Operation status monitoring Controlled status See items controlled by operation Special operation Defrost Oil Recovery Error management Error notification Audible alarm Error e mail notification History management Error history 1 year Operation control status history 1 year Energy saving management Indoor unit rotation Outdoor unit capacity save Peak cut control 1 month Pow...

Страница 495: ...us high level functions from individual control to yearly schedule management operation history and error history management Corresponds to 7 different languages English Chinese French German Spanish Russian Polish Connection between VRF network system to personal computer is possible via small U10 USB interface However both U10 USB interface and personal computer are locally purchased items The s...

Страница 496: ...separated by network 1 VRF Explorer software does not require WibuKey software protection key 1 UTY PLGXR2 option is necessary VRF Controller VRF Explorer USB Adaptor System Controller Lite On site control Max 1 VRF network system USB Port Internet or Telephone Line or LAN VRF Explorer VRF Explorer VRF Explorer VRF Building 1 Building Management Company A In charge of the day shift Remote centrali...

Страница 497: ...lled in remote site personal computers System Controller Lite UTY ALGXZ1 can be installed in the local site PCs VRF Controller connected to the VRF network system and multiple remote site PCs VRF Explorer can be connected to VRF Controller via Internet or LAN Just this single product creates the control management and monitor ing environment for the customer s properties including remote operation...

Страница 498: ...aximum number of required USB port depends on the applicable system configuration Graphic accelerator Microsoft DirectX 9 0c compatible Software Adobe Reader 9 0 or later AVAILABLE OPTION Electricity charge apportionment option UTY PLGXA2 Apportions the power used by indoor and outdoor units and automatically calculates the electricity charge such as for hotels or muli tenant buildings Computation...

Страница 499: ...400 groups Auto generation By site building and floor Others Memory operation Operation pattern memorized and reused Pattern operation Reuse operation pattern once used Operation status monitoring Controlled status See items controlled by operation Special operation Defrost Oil Recovery Room Temp Room temperature 1 Error management Error notification Audible alarm Error e mail notification History...

Страница 500: ...implified Chinese French German Spanish Russian Polish Floor layout editor Floor layout import export NOTE In S and V series there are some functions that cannot be used such as energy saving function and elec tricity meter use The electricity charge apportionment function of VRF system can only be performed from one equipment simultaneously 1 To display the room temperature on the monitor connect...

Страница 501: ...m individual control to yearly schedule management operation history and error history management Corresponds to 7 different languages English Chinese French German Spanish Russian Polish Connection between VRF network system to personal computer is possible via small U10 USB interface However both U10 USB interface and personal computer are locally purchased items The status of units can be monit...

Страница 502: ...separated by network 1 VRF Explorer software does not require WibuKey software protection key 1 UTY PLGXR1 option is necessary VRF Controller VRF Explorer USB Adaptor System Controller Lite On site control Max 1 VRF network system USB Port Internet or Telephone Line or LAN VRF Explorer VRF Explorer VRF Explorer VRF Building 1 Building Management Company A In charge of the day shift Remote centrali...

Страница 503: ...alled in the local site PCs VRF Controller connected to the VRF network system and multiple remote site PCs VRF Explorer can be connected to VRF Con troller via Internet or LAN Just this single product creates the control management and monitoring environment for the customer s properties including remote operation The WibuKey is not required for PCs on the remote site side Some functions such as ...

Страница 504: ...or the Server PC that works as VRF Controller Maximum of 4 USB ports are required for WibuKey connection 1 USB port is required for Echelon U10 USB Network Interface The maximum number of required USB port depends on the applicable system configuration Graphic accelerator Microsoft DirectX 9 0c compatible Software Adobe Reader 9 0 or later Optical drive DVD ROM drive AVAILABLE OPTION Electricity C...

Страница 505: ...status See items controlled by operation Special operation Defrost Oil Recovery Error management Error notification Audible alarm Error e mail notification History management Error history 1 year Operation control status history 1 year Energy saving management Indoor unit rotation Outdoor unit capacity save Peak cut control 1 month Power consumption monitor Electricity meters supported 200 Outdoor...

Страница 506: ...eration Stylish shape and design to suit all application No additional component is required for installation Up to 400 indoor units can be controlled Selectable 2 display types Icon List in monitoring mode Corresponds to 7 different languages English Chinese French German Spanish Russian Polish 05 38 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 507: ...ges Max 3 stages Settable up to 400 groups Set data can be written to and read from USB flash drive Background light and beep sound Backlighting off time and brightness setting BEEP sound operation setting Password Management level 3 kinds Schedule timer Max 30 items settable Temperature range Celsius Fahrenheit switching cooling heating and AUTO each settable Network function of Email notificatio...

Страница 508: ...nagement System BMS via BACnet Gateway or via Network Convertor the number of operations for each indoor unit must not exceed 7 500 times year If the number of setting change exceeds the above specified number the rewriting count limit of the non volatile memory memory built into the air conditioner and used for recording settings will be exceeded and may cause breakdown 1 Product specifications a...

Страница 509: ...30 items settable Temperature range Celsius Fahrenheit switching cooling heating and AUTO each settable Network function of Email notification for malfunction or electricity charge apportionment option is used via LAN Low noise operation Low noise operation is set to all the outdoor units registered by this controller Time zone Set the time zone of the area where this unit is used Electricity char...

Страница 510: ...tting Indoor unit registration Function settings of Touch Panel Controller User setting System setting Date and time Group Password Schedule timer Language setting Network 1 Low noise operation 1 Time zone 1 Electricity charge apportionment 1 Display item setting Environment setting Panel positioning Background light setting Sound setting Panel cleaning History Error history Status history Operati...

Страница 511: ...y to use display mode can be selected Easy to understand GUI of adopted icon z zOperation setting example Large button is designed for easy to access List display example Icon display Operation setting display Optional setting display 05 43 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 512: ... in the figure Control and monitoring are performed in these group units Group setting screen Group Hallway Group Division A Touch Panel Controller Group Tenant A Group Tenant B Group Tenant F Group Division C Group Division B Group 3F Group 2F 05 44 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 513: ...rding can be also written to USB flash drive Error history Max 10 items each recorded for touch panel controller and each unit indoor unit outdoor unit Status history Max 100 operations each recorded for indoor unit of each room Operation history Operation of Max 100 operations recorded Schedule setting screen Optional history screen 05 45 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 514: ... SCREEN EXAMPLES For Remote monitoring z zMain screens of Monitor Mode example Icon display List display z zMain screens of Control example Operation setting display 05 46 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 515: ...rojecting parts NOTE The switchbox that Touch Panel Controller is to be mounted to should be installed horizontally in advance CAUTION Following installation positions are prohibited Horizontal way Horizontal way Upside down 100mm or more 200mm or more 200mm or more 100mm or more Wall 200mm or more 05 47 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 516: ...y for UTY DTG Z1 K1 K2 K1 K2 CH1 CH2 TM201 EXTERNAL INPUT WHITE CN411 RED CN412 CN201 Electricity meter PCB PCB X1 X2 K1 K2 K1 K2 CH1 CH2 L N Power supply cable through hole Power supply 1ø 100 240 V Ground Ground External input Input type Edge pulse VRF LONWORKS Transmission Transmission cable connection terminals POWER SUPPLY EXTERNAL INPUT TRANSMISSION Power supply cable connection terminals Tr...

Страница 517: ... terminal c CF card a b c Transmission cable Transmission cable power supply cable power supply cable Washer Cable tie Harness Connection cable Cable tie Touch pen tray Switch box Hole in wall Installation plate Screw Screw Case of UTY DTG Z1 Case of UTY DTG z zThe diagram of the mounting plate screw hole positions 147 53 51 7 95 211 180 90 10 142 189 74 2 56 7 62 6 12 4 145 190 10 57 12 R 4 R4 R ...

Страница 518: ...ion M4 20 mm Washer 8 Washer for Touch Panel Controller installation Touch pen 1 Pen for Touch Panel Controller operation Cable tie 4 Prevents dropping off of the cable CD R 1 Includes the operating manual and file making sheet of this controller Installation manual 1 Operation manual 1 Top view Front view Side view Side view Rear view USB port Installation plate Touch panel Touch pen Unit mm 05 5...

Страница 519: ...urce frequency Hz 50 60 Input Power W 22 Display 7 5 inch TFT color LCD 640 480 pixels with Touch panel LED indicator Power LED Green External interface USB 2 0 Transmission line Ethernet port 1 Ethernet port is required for remote connection using internet External Input Either emergency stop or batch operation stop Electricity meter 1 Either Dry contact or Apply voltage can be selected External ...

Страница 520: ...eter is also possible z zSpecifications Number of sites Max 20 Number of contracts Max 400 per site Number of blocks Max 1600 per site Data storage period Max 2 years z zPersonal computer system requirements ELECTRICITY CHRGRE APPORTIONMENT TOOL Operating system Microsoft Windows 7 Home Premium 32 bit or 64 bit SP1 Windows 7 Professional 32 bit or 64 bit SP1 Microsoft Windows 8 1 32 bit or 64 bit ...

Страница 521: ...uttons 6 Arrow button 7 MENU button Individual control and monitor of 100 indoor units 5 inch TFT color screen User friendly view and easy operation External input output contact Detachable power supply unit Corresponds to 7 different languages English Chinese French German Spanish Russian Polish 05 53 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 522: ...mp Timer Filter R C prohibition setting prohibits individual remote control operation from this controller z z Room temperature set point upper and lower limitation z z Weekly timer Weekly timer can set the timer by various combinations Weekday 28 C 28 C 26 C 26 C Set temp Weekend 26 C 26 C Time 8 00 12 00 13 00 18 00 21 00 Holiday 28 C 28 C 05 54 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 523: ... screen display auto switching Main Screen automatically switches at 5 steps by the number of connected indoor units 1 2 3 4 5 Number of connected indoor units 1 to 9 units 10 to 20 units 21 to 40 units 41 to 80 units 81 to 100 units Display pattern 9 units display 20 units display 40 units display 80 units display 100 units display 9 20 units display pattern 40 80 100 units display pattern 05 55 ...

Страница 524: ...50 Service space Power supply cable Reley connector output DC 5 V Power supply 1ø 100 240 V POWER SUPPLY Power supply terminal Ground Screw size M4 Rear panel side Power supply DC 5 V DC 5 V Red Rear panel connecting terminal Ground Screw size M2 6 Ground VRF LONWORKS Transmission GND Black X1 X2 Green Unit mm 05 56 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 525: ... Wall Extension cable Service parts Control panel Integrated type Refer to an installation manual for the details Transmission cable Power supply cable Cable tie One touch bush Screw x 6 Accessories Relay connector Screw x 4 Screw CN13 Connecting cable Cable tie Cable tie One touch bush Wall hole Power supply cable 05 57 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 526: ...ble tie One touch bush 2 Wall Screw 2 Accessories Cut out When wiring the transmission cable in the upward direction of the front panel Power unit cover Screw 4 Screw 2 Screw 2 Screw 2 Accessories Screw 2 Accessories Ceiling z zMounting plate screw hole positions Unit mm 46 46 84 99 5 2 Ø5 R2 5 135 05 58 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 527: ...ion M4 20 mm Connecting cable 1 For power supply unit connection Cable tie 4 Prevents dropping off of the cable CD R 1 Includes the operating manual for Central remote controller Installation manual 1 Operation manual 1 Instruction book for operation Unit mm DIMENSIONS z zControl unit 25 7 162 118 120 44 8 Front view Side view Rear view z zPower supply unit Front view 84 99 67 25 22 29 99 46 135 3...

Страница 528: ...or LCD panel QVGA External interface Transmission line External Input Either emergency stop or batch operation stop Either Dry contact or Apply voltage can be selected External Output Operation state error state Usage temperature range C 0 to 40 Usage humidity range 0 to 85 no condensation Storage temperature range C 20 to 70 Storage humidity range 0 to 85 no condensation Dimensions mm H W D Contr...

Страница 529: ...pes and applications Up to 64 group remote controllers with 16 network convertors UTY VGGXZ1 can be connected in one VRF network system Start Stop operation mode set temperature timer control and fan speed can be controlled monitored centrally or individually Easy installation with a slim shape with no bulge in the back One touch Start Stop operation of each indoor unit is possible All the indoor ...

Страница 530: ...s has malfunction s Press the ALL OFF button to turn off all of the indoor units Press the ALL ON button to turn on all of the indoor units Press the ALL TIMER button to turn the timer operation on or off for all indoor units Press the ON OFF button to turn the corresponding indoor unit on or off Write the names of the indoor units on the included labels and attach them Setting Indicator Day Indic...

Страница 531: ...work convertor UTY VGGXZ1 G 1 2 3 L N POWER X1 X2 TRANSMISSION Y1 Y2 Y3 J1 REMOTE INDOOR UNIT REMOTE CONTROLLER LINE J2 J3 Group Remote Controller Transmission Line Transmission Line SWITCH FUSE 3 A 1Φ 50 60 Hz 208 240 V Power Supply NETWORK CONVERTOR Group remote controller cable Locally purchased cross section 0 33 mm2 Polar 3 core Shielded 1 12 V 2 Signal 3 COM 120 120 Name plate Accessory 84 x...

Страница 532: ...remote controller and remote controller cable binding Installation manual 1 Operating manual 1 WIRING SPECIFICATIONS Use Size Wire type Remarks Remote controller cable 0 33 mm2 22AWG Polar 3 core Use sheathed PVC cable or shielded cable in accordance with the regional cable standard SPECIFICATIONS Model name UTY CGG UTY CGGGU Dimensions H W D mm 120 120 18 Weight g 200 05 64 CONTROL SYSTEM CONTROL...

Страница 533: ...urkish and Dutch FUNCTIONS 1 Room temperature sensor inside 2 On Off button It is possible to operate only while displaying the Monitor Mode screen 3 LED lamp Operation indicator 4 Touch panel display 5 Set Temp Set the operating temperature 6 R C Group name 7 Mode Set the operation mode 8 Status icons 9 Clock 10 Fan Set the fun speed 11 Room temperature 12 Menu Set the various settings 13 Status ...

Страница 534: ... B C 500 m A B C D 500 m NOTE Multiple installation method described above is prohibited to combine with UTY RNK 3 wired type or UTY RSK 3 wired type or UTY RHK 3 wired type and UTY RNR 2 wired type or UTY RNR Z1 2 wired type or UTY RLR 2 wired type z zGroup control With a single remote controller up to 16 units can be simultaneously operated Master A B C D E I U I U I U I U A B C D E Remote contr...

Страница 535: ... is a functional earthing Indoor unit Remote controller Remote controller 2 Y 2 Y 1 Y 1 Y Y2 Y3 Y1 z zGroup control When there is a functional earthing Indoor units Remote controller Y2 Y2 Y2 Y2 Y2 Y3 Y3 Y3 Y3 Y1 Y1 Y1 Y1 Y1 DIMENSIONS Hole 9 4 5 Hole 6 4 5 Hole 12 5 4 5 20 4 120 30 33 23 15 3 83 5 120 45 3 63 5 Unit mm 05 67 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 536: ...rn B 1 Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable as shown in Fig 1 Connect the remote controller cable and connecting cable as shown in Fig 2 Be sure to insulate the connection between the cables Remote controller cable Non polar Insulated connection White Black 20 mm Red Connecting cable Cut and insula...

Страница 537: ...Y RNR Z2 UTY RNR Z1 UTY RNR Use sheathed twisted pair cable Use shielded cable locally purchased in accordance with the regional cable standard SPECIFICATIONS Model name UTY RNR Z2 UTY RNR Z1 UTY RNR Input voltage DC 12 V Power consumption Max 0 3 W Display 3 8 inch FSTN LCD 255 160 dots with Touch panel Usage temperature range 0 to 40 C Usage humidity range 20 to 90 no condensation Storage temper...

Страница 538: ...l Up to 4 remote controllers can be used to operate the indoor units Master A I U Slave Slave Master A B C I U Slave Master A B I U Slave Slave Slave Master A B C D I U A B C D Remote controller cable Refer to Chapter6 4 4 for detail specifications A 500m A B 500m A B C 500m A B C D 500m NOTE Multiple installation method described above is prohibited to combine with UTY RNK 3 wired type or UTY RSK...

Страница 539: ...e is a functional earthing Indoor unit Remote controller Remote controller 2 Y 2 Y 1 Y 1 Y Y2 Y3 Y1 z zGroup control When there is a functional earthing Indoor units Remote controller Y2 Y2 Y2 Y2 Y2 Y3 Y3 Y3 Y3 Y1 Y1 Y1 Y1 Y1 DIMENSIONS Hole 9 4 5 Hole 6 4 5 Hole 12 5 4 5 30 33 23 15 3 83 5 45 3 63 5 17 120 120 Unit mm 05 71 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 540: ...rn B 1 Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable as shown in Fig 1 Connect the remote controller cable and connecting cable as shown in Fig 2 Be sure to insulate the connection between the cables Remote controller cable Non polar Insulated connection White Black 20 mm Red Connecting cable Cut and insula...

Страница 541: ... Remote controller cable 0 33 to 1 25 mm2 Non polar 2 core UTY RLR Use sheathed twisted pair cable Use shielded cable locally purchased in accordance with the regional cable standard SPECIFICATIONS Input voltage DC 12 V Power consumption Max 0 23 W Usage temperature range 0 to 46 C Usage humidity range 0 to 90 no condensation Storage temperature range 20 to 70 C Storage humidity range 0 to 90 no c...

Страница 542: ...setting up a timer start stop and the temperature setup can be changed When a failure occurs the error code is displayed Error history Last 16 error codes can be accessed Up to 16 indoor units can be simultaneously controlled The room temperature can be controlled by detecting the temperature accurately with Built in thermo sensor SET TEMP START STOP 05 74 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 543: ...ly timer is deleted 13 Timer set button Sets the date hour minute and on off time 14 Economy button Thermo sensor button 15 Maintenance button Filter reset button 16 Operation lamp Lights during operation and when the timer is on 17 Timer and clock indicator 18 Operation mode indicator 19 Fan speed indicator 20 Operation lock indicator 21 Temperature indicator Displayed temperature is set temperat...

Страница 544: ...te controller cable Refer to 6 4 4 for detail specifications A 500 m B C 500 m Indoor unit REMOTE CONTROLLER 1 2 3 G G 1 2 3 Master Slave Indoor unit 1 2 3 G G 1 2 3 G 1 2 3 REMOTE CONTROLLER Remote controller Remote controllers 1 RED 12 V 2 WHITE Signal 3 BLACK COM 83 5 15 3 63 5 Hole 45 3 4 5 9 12 5 Hole x 2 Hole x 3 4 5 4 5 6 30 33 5 23 120 120 120 18 Front View Side View Rear View Unit mm 05 7...

Страница 545: ...ly terminal block z zPattern B 1 Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable as shown in Fig 1 Connect the remote controller cable and connecting cable as shown in Fig 2 Be sure to insulate the connection between the cables Remote controller cable Insulated connection White Black 20 mm Red Connecting cabl...

Страница 546: ...al 1 1 UTY RNKYT does not contain cables WIRING SPECIFICATIONS Use Cable size Wire type Model name 2 Remarks Remote controller cable 0 33mm2 22AWG Polar 3 core UTY RNKY UTY RNKG Use sheathed PVC cable UTY RNKYT Use shielded cable locally purchased in accordance with the regional cable standard 2 UTY RNKY FUJITSU BRAND UTY RNKG GENERAL BRAND UTY RNKYT Oceania MODEL SPECIFICATIONS Model name UTY RNK...

Страница 547: ...ge LCD screen simple operation buttons Built in background light function Easy installation with a slim shape with no bulge in the back Up to 16 indoor units can be simultaneously controlled Can be installed onto SW BOX applies to European and other country s standard 05 79 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 548: ...T 11 Airflow direction indicator 12 Status icons Mode mismatch Filter sign 5 Defrost operation Oil recovery operation Under maintenance Error Special state Conducting electricity Emergency stop Operation controlled Forced stop Remote controller sensor is enabled 5 Central controlled Setting temperature range is enabled Operation prohibited 13 Indicates the remote controller address 4 FUNCTIONS Dis...

Страница 549: ...rthing Indoor units Remote controller Y2 Y2 Y2 Y2 Y2 Y3 Y3 Y3 Y3 Y1 Y1 Y1 Y1 Y1 DIMENSIONS Front View Side View Rear View Unit mm 75 19 Hole 9 4 5 30 0 30 0 23 0 Hole 6 4 5 Hole 12 5 4 5 120 14 7 18 8 39 8 44 7 SYSTEM DIAGRAM z z1 remote controller z z4 remote controllers A B C D E Remote controller cable Refer to 6 4 4 for detail specifications A 500 m B C D E 500 m Indoor unit Remote controller ...

Страница 550: ...pment may fail if it is connected to the outdoor unit or the power supply terminal block z zPattern B 1 Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable as shown in Fig 1 Connect the remote controller cable and connecting cable as shown in Fig 2 Be sure to insulate the connection between the cables 2 Insert co...

Страница 551: ...ie 1 For binding remote controller and remote controller cable WIRING SPECIFICATIONS Cable type Size Remarks Sheathed cable 0 33 to 1 25 mm 22 to 16 AWG Non polar 2 core Twisted pair Shielded cable Use shielded cable in accordance with local rules for remote controller cable SPECIFICATIONS Model name UTY RSR Dimensions H W D mm 120 75 19 Weight g 120 05 83 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 552: ...recovery and defrosting operation 8 Power source indicator Indicates the main power ON 9 Central control indicator Indicates when function is locked from Touch Panel Controller or System Controller 10 Fan speed indicator AUTO HIGH MED LOW 11 Set temperature Indicates Error history number 4 Indicates Indoor unit address 5 12 Operating mode indicator AUTO 1 COOL DRY FAN 2 HEAT 3 13 Upper Indicates t...

Страница 553: ... unit B C ELECTRICAL WIRING z z1 remote controller Indoor unit REMOTE CONTROLLER 1 2 3 G G 1 2 3 Master Slave Indoor unit 1 2 3 G G 1 2 3 G 1 2 3 REMOTE CONTROLLER Remote controller Remote controllers 1 RED 12 V 2 WHITE Signal 3 BLACK COM DIMENSIONS Front View Side View Rear View Unit mm 120 75 49 39 23 5 14 4 11 4 5 12 5 hole x 2 hole x 2 8 60 6 18 9 47 5 83 5 z z2 remote controllers 05 85 CONTRO...

Страница 554: ...ly terminal block z zPattern B 1 Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable as shown in Fig 1 Connect the remote controller cable and connecting cable as shown in Fig 2 Be sure to insulate the connection between the cables Remote controller cable Insulated connection White Black 20 mm Red Connecting cabl...

Страница 555: ...cable binding Installation manual 1 Operating manual 1 1 UTY RSKYT does not contain cables WIRING SPECIFICATIONS Use Size Wire type Model name 2 Remarks Remote controller cable 0 33 mm2 22AWG Polar 3 core UTY RSKY UTY RSKG Use sheathed PVC cable 2 UTY RSKY FUJITSU BRAND UTY RSKG GENERAL BRAND SPECIFICATIONS Model name UTY RSKY UTY RSKG UTY RSKYT Dimensions H W D mm 120 75 14 Weight g 90 100 05 87 ...

Страница 556: ...arge LCD screen simple operation buttons Built in background light function Easy installation with a slim shape with no bulge in the back Up to 16 indoor units can be simultaneously controlled Can be installed onto SW BOX applies to European and other country s standard 05 88 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 557: ...ng temperature is different depending on the place of use 4 Fan control button Selects the fan speed 5 Louver button Set the airflow direction 6 Room temperature sensor inside 7 Operating mode indicator AUTO 1 COOL DRY FAN 2 HEAT 3 8 Set temperature Indicates Indoor unit address 4 9 Fan speed indicator AUTO HIGH MED LOW QUIET 10 Airflow direction indicator 11 Status icons Mode mismatch Filter sign...

Страница 558: ...rthing Indoor units Remote controller Y2 Y2 Y2 Y2 Y2 Y3 Y3 Y3 Y3 Y1 Y1 Y1 Y1 Y1 DIMENSIONS Front View Side View Rear View Unit mm 75 19 Hole 9 4 5 30 0 30 0 23 0 Hole 6 4 5 Hole 12 5 4 5 120 14 7 18 8 39 8 44 7 SYSTEM DIAGRAM z z1 remote controller z z4 remote controllers A B C D E Remote controller cable Refer to 6 4 4 for detail specifications A 500 m B C D E 500 m Indoor unit Remote controller ...

Страница 559: ...il if it is connected to the outdoor unit or the power supply terminal block z zPattern B 1 Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable as shown in Fig 1 Connect the remote controller cable and connecting cable as shown in Fig 2 Be sure to insulate the connection between the cables 2 Insert connecting cab...

Страница 560: ...ie 1 For binding remote controller and remote controller cable WIRING SPECIFICATIONS Cable type Size Remarks Sheathed cable 0 33 to 1 25 mm 22 to 16 AWG Non polar 2 core Twisted pair Shielded cable Use shielded cable in accordance with local rules for remote controller cable SPECIFICATIONS Model name UTY RHR Dimensions H W D mm 120 75 19 Weight g 120 05 92 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 561: ...re 18 30 C COOL 16 30 C HEAT 6 Standby indicator Indicates during the oil recovery and defrosting operation 7 Power source indicator Indicates the main power ON 8 Central control indicator Indicates when function is locked from Touch Panel Controller or System Controller 9 Fan speed indicator AUTO HIGH MED LOW 10 Set temperature Indicates Error history number 4 Indicates Indoor unit address 5 11 O...

Страница 562: ... unit B C ELECTRICAL WIRING z z1 remote controller Indoor unit REMOTE CONTROLLER 1 2 3 G G 1 2 3 Master Slave Indoor unit 1 2 3 G G 1 2 3 G 1 2 3 REMOTE CONTROLLER Remote controller Remote controllers 1 RED 12 V 2 WHITE Signal 3 BLACK COM DIMENSIONS Front View Side View Rear View Unit mm 120 75 49 39 23 5 14 4 11 4 5 12 5 hole x 2 hole x 2 8 60 6 18 9 47 5 83 5 z z2 remote controllers 05 94 CONTRO...

Страница 563: ...ly terminal block z zPattern B 1 Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable as shown in Fig 1 Connect the remote controller cable and connecting cable as shown in Fig 2 Be sure to insulate the connection between the cables Remote controller cable Insulated connection White Black 20 mm Red Connecting cabl...

Страница 564: ...cable binding Installation manual 1 Operating manual 1 1 UTY RHKYT does not contain cables WIRING SPECIFICATIONS Use Size Wire type Model name 2 Remarks Remote controller cable 0 33 mm2 22AWG Polar 3 core UTY RHKY UTY RHKG Use sheathed PVC cable 2 UTY RHKY FUJITSU BRAND UTY RHKG GENERAL BRAND SPECIFICATIONS Model name UTY RHKY UTY RHKG UTY RHKYT Dimensions H W D mm 120 75 14 Weight g 90 100 05 96 ...

Страница 565: ...e ON OFF PROGRAM SLEEP Up to 16 indoor units connected within the remote controller group can be simultaneously controlled Can be used jointly with wired remote controllers Easy to change custom code max 4 codes NOTE UTY LNHGU is for UAE market only 05 97 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 566: ...timer mode OFF TIMER ON TIMER PROGRAM TIMER TIMER RESET 12 Timer set button Sets the current time and on off time 13 Clock adjust button Sets the current time 14 Reset button Used when replacing batteries 15 Test run button Used when testing the air conditioner after installation 16 Signal transmitter 17 Temperature set indicator 18 Economy indicator 19 Operating mode indicator 20 Sleep indicator ...

Страница 567: ... and receiver ii There is an instant start type inverter type etc fluorescent lamp in the room Air conditioner might not work correctly when strong light hits the signal receiver window Shut off the direct sunlight and also keep the illuminator far away from the receiver window 56 19 170 Front View Rear View Top View Side View Front View Side View Bottom View Unit mm 05 99 CONTROL SYSTEM CONTROL S...

Страница 568: ...te controller holder 1 Use as remote controller holder Screw M3 12 mm 2 For remote controller holder installation Battery 1 5 V R03 AAA 2 For remote controller SPECIFICATIONS Model name UTY LNH UTY LNHGU Dimensions H W D mm 170 56 19 Weight g 85 w o batteries 05 100 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 569: ...roller if the IR receiver unit is used FUNCTIONS SYSTEM DIAGRAM z zATTACHMENT RANGE z zSIGNAL ANGLE OPERATION LAMP TIMER LAMP FILTER SIGN MANUAL AUTO SIGNAL RECEIVER L 1 L 1 1 Connection cable length L Cable A Standard accessory 5 m Cable C Optional service parts 10 m 120 5 m 120 5 m 05 101 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 570: ...control box PC board Connected to PC board 2 Connected to IR Receiver unit IR Receiver unit Connected to Connection cable 60 mm 120 mm hole 1 Connection cable Connection cable D 2 Connected to PC board CN18 DIMENSIONS 11 5 8 5 145 90 18 5 60 57 6 8 3 5 22 9 118 4 72 4 13 6 57 4 13 6 7 2 7 2 17 Front View Side View Rear View Unit mm 05 102 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 571: ...nit to receiver unit Connection cable B 0 15 m 1 Connection cable D 0 15 m 1 For connecting PC board of indoor unit to receiver unit Hook metal 1 For installing receiver unit to indoor unit Bracket cover 1 For receiver unit SPECIFICATIONS Model name UTB WC Dimensions H W D mm 145 90 30 Weight g 150 OPTIONAL SERVICE PARTS Use the parts number shown below to order the cable from your sales represent...

Страница 572: ...ess remote controller if the IR receiver unit is used FUNCTIONS ELECTRICAL WIRING Filter lamp Red Timer lamp Orange Operation lamp Green Manual auto Signal receiver Indoor unit Cassette type Wiring hole Wire from IR Receiver unit IR Receiver unit Connected to CN18 of PC board 05 104 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 573: ...uantity Application Installation manual 1 Strap 1 Prevents receiver kit from falling down SPECIFICATIONS Model name UTY LRH B1 Dimensions H W D mm 193 9 193 9 31 2 Weight g 140 Front View Side View Unit mm 05 105 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 574: ...ontroller if the IR receiver unit is used FUNCTIONS ELECTRICAL WIRING Wire from IR receiver unit Wiring hole Indoor unit Attach the corner plate firmly in 5 places Remote control signal receiver and Manual Auto button FILTER Indicator lamp RED OPERATION Indicator lamp GREEN TIMER Indicator lamp ORANGE 05 106 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 575: ...y Application IR receiver unit 1 For receiving the signal from the remote control unit Strap 1 Prevent IR receiver unit from falling down Cable tie 2 For electrical wiring SPECIFICATIONS Model name UTY LBHXD Dimensions H W D mm 164 5 164 5 22 6 Weight g 110 05 107 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 576: ...TTE TYPE MODEL UTY SHZXC Motion sensor save operation catches the movements of people for wide area and operation stop is also judged automatically ELECTRICAL WIRING Wire from Human sensor unit Strap Hook Strap 05 108 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 577: ...ovement Cable tie 3 For binding wires Strap 1 To prevent Human sensor unit from falling Insulation 3 To fasten the Human sensor wire SPECIFICATIONS Model name UTY SHZXC Dimensions H W D mm 164 5 164 5 27 5 Weight g 110 Unit mm 164 5 55 3 27 5 Front View Side View 05 109 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 578: ...ure that the wires do not contact each other Remote sensor To indoor unit Cable INSTALLATION z zWhen the cable is attached to the wall Remove the material covering the wiring penetration thin material in the cover of the sensor unit with a pair of cutters The cable passes through this hole Now attach the remote sensor on the wall using the screws 40 55 Screw M4 16 mm Unit mm Mounting hole dimensio...

Страница 579: ... the cable penetration with putty 20 ø6 ø10 20 55 1 Screw M4 16 mm Mounting hole dimensions Unit mm z zFinish Fit the cover on the remote sensor and screw it in place DIMENSIONS 55 2 70 2 PACKING LIST Name and shape Quantity Application Installation manual 1 Cable 10 m 1 Screw M4 16 mm 2 Screw M4 10 mm 2 Cord clamp 1 SPECIFICATIONS Model name UTY XSZX Dimensions H W D mm 70 2 55 2 18 05 111 CONTRO...

Страница 580: ... same remote controller group will conduct the same operation When using 2 remote controllers Last command has priority Operation mode might be fixed by system operation Timer setting function on the slave remote controller or Wireless Remote Controller may become invalid Without Remote Controller Connectable indoor unit 1 16 Connectable remote controller 0 2 Max 16 indoor units 05 112 CONTROL SYS...

Страница 581: ...stem Refrigerant system 2 Heat pump system System controller Group A Group is possible with only one indoor unit Group B Group is possible with spanning the RB groups Group C Group is possible with spanning the RB group and indoor unit of cooling only type Group D Group is possible with spanning the refrigerant systems The contents of a setting may not be reflected by operational status B C D grou...

Страница 582: ...00 100 8 1 1 1 1 1 1 Max controllable indoor units 1600 400 400 100 3 16 16 16 16 16 16 Max controllable groups 1600 400 400 16 Air conditioning control function On Off Operation mode setting Fan speed setting Room temp setting Room temp set point limitation Test operation Up down air direction flap setting Right left air direction flap setting Group setting RC prohibition Anti freeze setting Econ...

Страница 583: ...r Week Week Week Week Week On Off Temp mode times per day 144 144 20 20 4 8 8 4 On Off timer Sleep timer Program timer Auto off timer Day off Min unit of timer setting Minutes 10 10 10 10 10 10 30 30 30 5 Control Status monitoring system Electricity charge calculation Error history Emergency stop 3 3 Control via Internet E mail notiffication for malfunction Key lock Password setting Password setti...

Страница 584: ...TY VMSX For connection between Single split indoor unit and a Modbus open network Network Convertor for LONWORKS UTY VLGX For connection between VRF network system and a LONWORKS open network for management of small to medium sized BMS BACnet Gateway UTY VBGX Hardware For connection between VRF network system to the BMS system using BACnet protocol BACnet Gateway UTY ABGXZ1 UTY ABGX Software The c...

Страница 585: ...nvertor by UTY VTGX Up to 100 network convertors can be connected in one VRF network system One Network convertor is regarded as one refrigerant system The total refrigerant systems in one VRF network system must be within 100 SYSTEM DIAGRAM Group of Single Split System 1 Single Split System VRF system To outdoor units Multi System 2 2 to 4 rooms multi Multi System 2 8 rooms multi Outdoor unit for...

Страница 586: ... WBE AR WBF AR WDC AR WDD arbitrary character FUNCTIONS Operation Non polar 2 wire Polar 3 wire Operation of louver from VRF Operation of louver from wired remote controller Restriction of wireless remote controller from central Restriction of wired remote controller from central Antifreeze Setting high and low temperature limit Indoor unit rotation Turning off indoor unit external thermostat Outd...

Страница 587: ...ntroller Transmission Cable Max 1 unit SET TEMP START STOP NOTES Do not bind the power cable and remote controller cable to avoid an erroneous operation Use shield cable for transmission cable in accordance with the regional cable standard Use sheathed PVC cable or shielded cable for remote controller cable in accordance with the regional cable standard Use ground wire to ground the network conver...

Страница 588: ...cable Refer to Chapter6 4 4 for detail specifications A 2 m and A B C D E 500 m z zFor polar 3 wire Network convertor Indoor unit A B X C D E SET TEMP START STOP A B C D E X Remote controller cable Refer to Chapter6 4 4 for detail specifications A 2 m A B C D E 100 m and X 100 m 05 120 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 589: ...ing the network convertor WIRING SPECIFICATIONS Use Size Wire type Remarks Transmission cable 0 33 mm2 22AWG LEVEL4 NEMA non polar 2 core twisted pair solid core Shielded LONWORKS compatible cable Remote controller cable 2 wire type 0 33 to 1 25 mm2 22 16AWG Non polar 2core Use sheathed PVC cable or shielded cable in accordance with the regional cable standard Remote controller cable 3 wire type 0...

Страница 590: ...oor unit Wired remote controller Max 16 units Max 2 units Transmission Cable 1Ø 50 60 Hz 208 240 V SET TEMP START STOP SET TEMP START STOP L L1 N L2 NOTES Do not bind the power cable and remote controller cable to avoid an erroneous operation Use shield cable for transmission cable in accordance with the regional cable standard Use sheathed PVC cable or shielded cable for remote controller cable i...

Страница 591: ...o Chapter6 4 4 for detail specifications A 2 m and A B C D E 500 m z zFor polar 3 wire Network convertor Indoor unit A B X Y C D E SET TEMP START STOP SET TEMP START STOP A B C D E X Y Remote controller cable Refer to Chapter6 4 4 for detail specifications A 2 m A B C D E 100 m and X Y 100 m 05 123 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 592: ...cable Maximum 1 25 mm2 16AWG 60245 IEC 57 or equivalent 1 ø AC 208 240 V 50 60 Hz 2 Wire ground Always ground the unit Minimum 0 5 mm2 20AWG Transmission cable 0 33 mm2 22AWG LEVEL4 NEMA non polar 2 core twisted pair solid core Shielded LONWORKS compatible cable Remote controller cable 2 wire type 0 33 to 1 25 mm2 22 16AWG Non polar 2core Use sheathed PVC cable or shielded cable in accordance with...

Страница 593: ... network convertor are operating under same status 2 Network convertor is necessary for each indoor unit to control indoor unit individually With this network convertor single split type and multi system air conditioners can be controlled by Central remote controller Touch panel controller System controller in VRF network system or by wired remote controller that is connected to the Network conver...

Страница 594: ...red Remote Controller Indoor Unit Power Supply NETWORK CONVERTOR RC line to indoor unit RC line to RC Transmission line Power supply NOTES Do not bind the power cable and remote controller cable to avoid an erroneous operation Use shield cable for transmission line and remote controller line The shield metal should be grounded Use ground wire to ground the network convertor 05 126 CONTROL SYSTEM C...

Страница 595: ...is unit RC number AR 3TA AR 6TC AR WAE EZ 099DHSE R EZ 000DHSE R EZ 0001HSE R EZ 000GHSE R EZ 00004HSE R EZ 00005HSE R EZ 0015HSE R EZ 0019HSE R EZ 099DHSEFR EZ 0001HSEFR EZ 000DHSEFR EZ 000GHSEFR EZ 0015HSEFR EZ 0994HSE R EZ 000EHSE R EZ 0994HSEFR EZ 099CWSE R EZ 000AWSE R EZ 0001WSE R EZ 000FWSE R EZ 0012WSE R EZ 099CWSEFR EZ 0001WSEFR EZ 000AWSEFR EZ 09906WSE R EZ 000BWSE R EZ 09906WSEFR EZ typ...

Страница 596: ...60 Hz 208 240 V SWITCH FUSE 3 A Transmission Line to VRF System Transmission Line to VRF System Power Supply NETWORK CONVERTOR Group Remote Controllers Max 4 sets L1 L2 L3 L4 Y1 Y2 Y3 J1 REMOTE INDOOR UNIT REMOTE CONTROLLER LINE J2 J3 RC line to indoor unit RC line to RC Transmission line Power supply Total remote controller cable length L1 L2 L3 L4 100 m It is recommended to use a terminal box wh...

Страница 597: ...rks Power supply cable Maximum 1 25 mm2 60245 IEC 57 or equivalent 1 ø AC 208 240 V 50 60 Hz 2 Wire ground Always ground the unit Minimum 0 5 mm2 Transmission cable 0 33 mm2 22AWG LEVEL4 NEMA non polar 2 core twisted pair solid core Shielded LONWORKS compatible cable Remote controller cable 0 33 mm2 22AWG Polar 3 core Use sheathed PVC cable or shielded cable in accordance with the regional cable s...

Страница 598: ... purpose KNX device Maximum 128 Indoor units Maximum 100 Outdoor units Maximum 100 Outdoor units Maximum 128 Indoor units Indoor unit VRF network VRF Outdoor unit Lighting facilities Security system Ventilation system Automatic fire alarm interface z zConnected unit Maximum controllable indoor unit number per 1 KNX Convertor 128 Maximum controllable outdoor unit number per 1 KNX Convertor 100 Maxim...

Страница 599: ...of VRF Network Batch control Commands from KNX Network are sent to all indoor units connected to VRF Network KNX Network All indoor units of VRF Network z zIndoor unit status monitoring Indoor unit status is communicated to the KNX Network in the form of LON Network variables KNX Network All indoor units of VRF Network 05 131 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 600: ...ed in VRF Network System are an object Emergency STOP Setting Set Emergency STOP command Outdoor Unit Control Individual Outdoor Unit Low Noise Outdoor unit low noise level setting Outdoor Unit Capacity Save Outdoor unit capacity save setting Indoor Unit Monitoring Individual ON OFF Status ON OFF status Operation Mode Setting Status Heating Cooling Auto Fan Dry mode status Temperature Setting Stat...

Страница 601: ...e indoor unit which is now error can be monitored in all indoor units Outdoor Unit Monitoring Individual Outdoor Unit Low Noise Outdoor unit low noise level can be monitored Outdoor Unit Capacity Save Outdoor unit capacity save can be monitored Convertor Unit Monitoring Individual Error code Status Error code status Model Name Convertor model name can be confirmed Software Version Convertor softwa...

Страница 602: ... minutes must elapse More than 10 minutes must elapse Stop operation Set indoor unit forced thermostat off mode Start operation Release indoor unit forced thermostat off mode Forced thermostat OFF instruction Only one equipment can send these instructions for each refrigerant system When these instructions are sent by multiple equipment the system may not respond as instructed or may malfunction S...

Страница 603: ...r UTY VKGX applicable PC needs to satisfy the following system requirements Operating System Microsoft Windows 7 SP1 Home 32 bit or 64 bit Windows 7 SP1 Pro 32 bit or 64 bit Microsoft Windows 8 1 32 64 bit Microsoft Windows 10 Home 32 bit or 64 bit Windows 10 Pro 32 bit or 64 bit Supported languages English Chinese French German Russian Spanish and Polish Display 1366 768 dots or higher resolution...

Страница 604: ... proof bushing For M4x16mm screws Unit mm ELECTRICAL WIRING Power supply cable KNX cable Transmission cable to VRF network General purpose KNX device TRANSMISSION CABLE OUTDOOR UNIT MASTER OR SLAVE OUTDOOR UNIT INDOOR UNIT TRANSMISSION This product BREAKER EARTH 1Ø 50 60 Hz 220 240 V KNX CABLE Twisted pair POWER SUPPLY CABLE 05 136 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 605: ...EL4 NEMA nonpolar 2 core twisted pair solid core Shielded LONWORKS compatible cable KNX cable Maximum 0 8 mm2 18AWG AWG18 20 2Wire twisted pair KNX TP1 Twister Pair 1 cable Minimum 0 5 mm2 20AWG PCB FOR KNX CONVERTOR UTY VKGX Programming Button Prog Button KNX connector VRF Network connection port VRF terminal resister switch SET2 1 Test run switch SET2 3 Scan switch SET2 4 Convertor address switc...

Страница 606: ...erforming the scan again is necessary 3 Setting from PC NOTE For detailed information check the Application Manual which is included inside packaged DVD STEP 1 Install Tool for Convertor software for UTY VKGX in PC Tool for Convertor is the accessory item of UTY VKGX STEP 2 Connect the PC and KNX convertor for VRF UTY VKGX Connection will be done by the connector cable provided as an accessory ite...

Страница 607: ...KNX network SYSTEM DIAGRAM z zProper system diagram z zConnected unit Maximum connectable indoor unit number per 1 KNX Convertor 1 General purpose KNX device KNX Convertor UTY VKSX KNX Convertor UTY VKSX KNX Network Connector cable Connector cable Indoor unit Indoor unit Lighting facilitie Security system Automatic fire alarm interface Ventilation system 05 139 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 608: ...om KNX Network are sent to indoor unit KNX Network indoor unit z zIndoor unit status monitoring Indoor unit status is communicated to the KNX Network in the form of indoor unit variables KNX Network indoor unit 05 140 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 609: ...peration Mode Setting Status Heating Cooling Auto Fan Dry mode status Temperature Setting Status Room set temperature status Airflow Mode Setting Status Airflow mode status Thermostat Off Setting Status Thermostat off set value status Centrally Control Filter Reset Status Remote controller filter reset prohibition status Centrally Control All Mode Status Remote controller all mode prohibition stat...

Страница 610: ...function More than 10 minutes must elapse More than 10 minutes must elapse Stop operation Set indoor unit forced thermostat off mode Start operation Release indoor unit forced thermostat off mode SPECIFICATIONS Power consumption W 0 6 Temperature C Operating 0 46 Packaged 10 60 Humidity Packaged 0 95 RH No condensation Dimensions H W D mm 43 x 117 x 140 Weight g 215 PACKING LIST Name and shape Qua...

Страница 611: ...x 8 140 For M4x16mm screws Hole pitch Hole Hole Hole For code For code For code For code For open case Unit mm ELECTRICAL WIRING General purpose KNX device INDOOR UNIT Connector cable to Indoor Unit KNX cable This product KNX CABLE CONNECTOR CABLE 05 143 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 612: ... type Remarks KNX cable Maximum 0 8 mm2 18AWG AWG18 20 2Wire twisted pair KNX TP1 Twister Pair 1 cable Minimum 0 5 mm2 20AWG PCB FOR KNX CONVERTOR UTY VKSX Programming Button Prog Button KNX connector 05 144 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 613: ...28 indoor units Maximum 100 outdoor units Maximum 100 outdoor units Maximum 128 indoor units VRF network Lighting facilities Security system Ventilation system Automatic fire alarm interface z zConnected unit Maximum controllable indoor unit number per 1 Modbus Convertor 128 Maximum controllable outdoor unit number per 1 Modbus Convertor 100 Maximum connectable Modbus Convertor number per 1 VRF ne...

Страница 614: ...VRF Network Batch control Commands from Modbus Network are sent to all indoor units connected to VRF Network Modbus Network All indoor units of VRF Network z zIndoor unit status monitoring Indoor unit status is communicated to the Modbus Network in the form of LON Network variables Modbus Network All indoor units of VRF Network 05 146 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 615: ...ed in VRF Network System are an object Emergency STOP Setting Set Emergency STOP command Outdoor Unit Control Individual Outdoor Unit Low Noise Outdoor unit low noise level setting Outdoor Unit Capacity Save Outdoor unit capacity save setting Indoor Unit Monitoring Individual ON OFF Status ON OFF status Operation Mode Setting Status Heating Cooling Auto Fan Dry mode status Temperature Setting Stat...

Страница 616: ...onitored in all indoor units Outdoor Unit Monitoring Individual Outdoor Unit Low Noise Outdoor unit low noise level can be monitored Outdoor Unit Capacity Save Outdoor unit capacity save can be monitored Convertor Unit Monitoring Individual Error code Status Error code status Modbus Communication Setting Information Baud rate slave address can be monitored Model Name Convertor model name can be co...

Страница 617: ...tat off mode Forced thermostat OFF instruction Only one equipment can send these instructions for each refrigerant system When these instructions are sent by multiple equipment the system may not respond as instructed or may malfunction SPECIFICATIONS Power supply 1ø AC208 240 V 50 60 Hz Input Power W 2 0 Temperature C Operating 0 to 46 Packaged 10 to 60 Humidity Packaged 0 to 95 RH No condensatio...

Страница 618: ...EM REQUIREMENTS To install Tool for Convertor UTY VMGX applicable PC needs to satisfy the following system requirements Operating System Microsoft Windows 7 SP1 Home 32 bit or 64 bit Windows 7 SP1 Pro 32 bit or 64 bit Microsoft Windows 8 1 32 64 bit Microsoft Windows 10 Home 32 bit or 64 bit Windows 10 Pro 32 bit or 64 bit Supported languages English Chinese French German Russian Spanish and Polis...

Страница 619: ...ng Unit mm ELECTRICAL WIRING General purpose building control computer Modbus device Transmission cable Outdoor unit Master or Slave outdoor unit Indoor unit Power supply cable Transmission cable to Modbus network Transmission cable to VRF network Modbus convertor Switch Disconnect switch Fuse 2 A 1Ø 50 60 Hz 208 240 V Modbus cable Power supply cable L L1 N L2 05 151 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 620: ... mm2 16AWG AWG16 26 3Wire Sheathed PVC cable Minimum 0 128 mm2 26AWG Fuse capacity 2 A PCB FOR MODBUS CONVERTOR UTY VMGX Modbus Network connection port VRF Network connection port Modbus terminal resister switch SET7 4 VRF terminal resister switch SET2 1 Test run switch SET2 3 Scan switch SET2 4 Modbus communication baud rate switch SET6 4 Modbus communication parity switch SET6 3 Modbus communica...

Страница 621: ...g boards When scan error is generated performing the scan again is necessary 3 Setting from PC NOTE For detailed information check the Application Manual which is included inside packaged DVD STEP 1 Install Tool for Convertor software for UTY VMGX in PC Tool for Convertor is the accessory item of UTY VMGX STEP 2 Connect the PC and Modbus convertor for VRF UTY VMGX Connection will be done by the co...

Страница 622: ...nnectable indoor unit number per 1 Modbus Convertor 1 Maximum number of connected Modbus Convertor units to one Modbus master unit Without repeater 31 With repeater 247 Modbus Convertor UTY VMSX Modbus Convertor UTY VMSX Modbus Network General purpose Modbus master unit Modbus device Lighting facilities Security system Automatic fire alarm interface Ventilation system Connector cable Connector cab...

Страница 623: ...bus Network are sent to indoor unit Modbus Network indoor unit z zIndoor unit status monitoring Indoor unit status is communicated to the Modbus Network in the form of indoor unit variables Modbus Network indoor unit 05 155 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 624: ...tus Temperature Setting Status Room set temperature status Airflow Mode Setting Status Airflow mode status Antifreeze Setting Set antifreeze command Thermostat Off Setting Status Thermostat off set value status Centrally Control Filter Reset Status Remote controller filter reset prohibition status Centrally Control All Mode Status Remote controller all mode prohibition status Centrally Control Tim...

Страница 625: ...ICATIONS Power consumption W 1 2 Temperature C Operating 0 46 Packaged 10 60 Humidity Packaged 0 95 RH No condensation Dimensions H W D mm 43 117 140 Weight g 200 z zTransmission specifications Transfer mode RTU mode Communication method Half duplex operation Master slave method Communication speed 9600bps 19200bps Synchronous system Asynchronous communication method Data bit 8 bit Parity even odd...

Страница 626: ... screws Hole pitch Hole Hole Hole For code For code For code For code For open case Unit mm ELECTRICAL WIRING General purpose building control computer Modbus device Indoor Unit Connector cable to Indoor Unit Modbus cable Modbus convertor Modbus cable Connector cable 05 158 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 627: ... 0 128 mm2 26AWG SWITCH AND CONNECTOR LOCATION ON PCB Modbus Network connection port Modbus terminal resister switch SET7 4 Modbus communication baud rate switch SET6 4 Modbus communication parity switch SET6 3 Modbus communication stop bit switch SET6 2 Modbus slave address switch SET4 SET5 05 159 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 628: ...twork Convertors for LONWORKS can be connected to 1 BMS SYSTEM DIAGRAM z zProper system diagram Network convertor for LONWORKS UTY VLGX Network convertor for LONWORKS UTY VLGX LONWORKS Network General purpose building control computer LONWORKS device Maximum 128 indoor units Maximum 100 outdoor units Maximum 4 Network convertors for LONWORKS UTY VLGX Maximum 100 outdoor units Maximum 128 indoor un...

Страница 629: ...door units Maximum 100 outdoor units Maximum 100 outdoor units Maximum 128 indoor units VRF network system 1 VRF network system 2 Example 2 Prohibited Maximum 128 indoor units Maximum 128 indoor units Network convertor for LONWORKS UTY VLGX Network convertor for LONWORKS UTY VLGX LONWORKS Network Maximum 100 outdoor units 05 161 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 630: ...F Network Batch control Commands from LONWORKS Network are sent to all indoor units connected to VRF Network LONWORKS Network All indoor units of VRF Network z zIndoor unit status monitoring Indoor unit status is communicated to the LONWORKS Network in the form of LON Network variables LONWORKS Network All indoor units of VRF Network 05 162 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 631: ...ON OFF Status ON OFF status Operation Mode Setting Status Heating Cooling Auto Fan Dry mode status Temperature Setting Status Room set temperature status Airflow Mode Setting Status Airflow mode status Set Point Temperature Limit Status Room set temperature limit status Thermostat Off Setting Status Thermostat off set value status Centrally Control Filter Reset Status Remote controller filter rese...

Страница 632: ...t off mode Forced thermostat OFF instruction Only one equipment can send these instructions for each refrigerant system When these instructions are sent by multiple equipment the system may not respond as instructed or may malfunction SPECIFICATIONS Power supply 1ø AC 208 240 V 50 60 Hz Input Power W 4 5 Dimensions H W D mm 67 288 211 Weight g 1500 z zOperating environment Temperature C Operating ...

Страница 633: ...y cable PERSONAL COMPUTER SYSTEM REQUIREMENTS To install Tool for Network Convertor UTY VLGX applicable PC needs to satisfy the following system requirements Operating System Microsoft Windows 7 Professional 32 bit Microsoft Windows 8 1 32 bit Microsoft Windows 10 Home 32 bit or 64 bit Windows 10 Pro 32 bit or 64 bit Supported languages English and Chinese Memory 1 GB or more Display 1024 768 or h...

Страница 634: ...n Use shield cable for transmission cable The shield metal should be grounded Do not forget to ground the Network Convertor FUSE 3 A OUTDOOR UNIT SWITCH TRANSMISSION CABLE TRANSMISSION CABLE General purpose building control computer LONWORKS Device POWER SUPPLY CABLE MASTER OR SLAVE OUTDOOR UNIT 1Φ 50 60 Hz 208 240 V VRF LON NETWORK CONVERTOR INDOOR UNIT INDOOR UNIT B1 B2 X1 X2 Power supply Transm...

Страница 635: ...Tool e g LonMaker Neuron ID is sent upon pushing BMS service switch SW2 Tool for network convertor Software LONWORKS Open Network Network Convertor Interface for LONWORKS Making XIF of Network Convertor using a Tool for network convertor Software provided by Fujitsu General Job is done by Network Integrator Binding VRF with BMS By Network Integrator Outdoor unit address Refrigerant circuit address...

Страница 636: ...tial setting data to UTY VLGX Click Register dialog STEP 7 Set Configuration Properties It is the communication properties of UTY VLGX Select the following Communication items Communication type if necessary Otherwise communication will be taken place by the Default values Select Communication items Event Driven communication or Cyclic communication Default Cyclic 3minutes Communication Interval T...

Страница 637: ...twork system address allocation information must not be same Binding and Commissioning is not executed During binding read out the Network Convertor Neuron ID by pushing BMS service switch SW 2 on the main PC board of Network Convertor If the ID number registered to the Network Convertor is not same as the ID number which is included in the XIF of Network Convertor 05 169 CONTROL SYSTEM CONTROL SY...

Страница 638: ...M DIAGRAM z zSystem diagram BACnet Gateway UTY VBGX BACnet Gateway UTY VBGX BACnet IP General purpose building control computer BACnet Gateway device Maximum 128 indoor units Maximum 100 outdoor units Maximum 4 Network BACnet Gateway UTY VBGX Maximum 100 outdoor units Maximum 128 indoor units VRF network system 1 VRF network system 4 VRF network Lighting facilities Security system Ventilation syst...

Страница 639: ...of VRF Network Batch control Commands from BACnet Network are sent to all indoor units connected to VRF Network BACnet Network All indoor units of VRF Network z zIndoor unit status monitoring Indoor unit status is communicated to the BACnet Network in the form of BACnet objects BACnet Network All indoor units of VRF Network 05 171 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 640: ... Room Temperature In AI Representative Error In BI Error Code In MI Temperature H L Limit Status Setting In AI AO H L limit per 3 operation Mode HEAT COOL DRY and AUTO Temperature Limit Validity Status Setting In BI BO Filter Sign Status Reset In BI BO Only reset for control Forced Thermo Off Status Setting In BI BO Emergency Stop In BI R C Prohibition Status Setting In MI MO Vertical Fan Status S...

Страница 641: ...tat off mode Start operation Release indoor unit forced thermostat off mode Forced thermostat OFF instruction Only one equipment can send these instructions for each refrigerant system When these instructions are sent by multiple equipment the system may not respond as instructed or may malfunction SPECIFICATIONS Power supply 1ø AC 208 240 V 50 60 Hz Input Power W 4 6 Dimensions H W D mm 60 x 270 ...

Страница 642: ...QUIREMENTS To install Tool for BACnet Gateway applicable PC needs to satisfy the following system requirements Operating System Microsoft Windows 7 Professional 32 bit Microsoft Windows 8 Pro 32 bit Microsoft Windows 10 Home 32 bit or 64 bit Windows 10 Pro 32 bit or 64 bit Memory 1 GB or more Display 1024 768 or higher resolution 16 bit or higher color Interface USB port x 1 Software Adobe Reader ...

Страница 643: ...not forget to ground the BACnet Gateway FUSE 1 25 A OUTDOOR UNIT SWITCH TRANSMISSION CABLE TRANSMISSION CABLE General purpose building control computer BMS POWER SUPPLY CABLE MASTER OR SLAVE OUTDOOR UNIT 1Φ 50 60 Hz 100 240 V BACnet Gateway INDOOR UNIT INDOOR UNIT C2 RJ45 A B SGND Power supply Transmission cable to LONWORKS network BACnet Gateway Ethernet cable to BMS 05 175 CONTROL SYSTEM CONTROL...

Страница 644: ...evices to the frames sent by gateway check that they are operational and reachable from the network connection used by the gateway Check the gateway Ethernet interface sending Pings to its IP address using a PC connected to the same Ethernet IP network If the problem persists communicating through the LAN of the building contact the network administrator The BACnet Gateway for VRF System comes wit...

Страница 645: ... scan from the Configuration Tool and check that all VRF indoor outdoor units are detected and available 7 Remove the USB cable from the Gateway and close the case At this point BACnet Gateway should be accessible from the BMS workstation Integration of BACnet system is ready to be performed 05 177 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 646: ...s 1 Brown Line L 2 Yellow Earth Ground E 3 Blue Neutral N Ethernet BACnet IP UDP Console UDP TCP Connect the cable coming from the IP network to the connector ETH of the gateway Use an Ethernet CAT5 or higher cable VRF Network Connect the LON bus to connectors A B and SNGD of gateway s PCB Console Port Connect a mini type B USB cable from your computer to the gateway to allow communication between...

Страница 647: ...ACnet BACnet Operator Workstation B OWS PC Hardware locally purchased USB adap tor locally purchased USB adap tor locally purchased USB adap tor locally purchased USB adap tor locally purchased USB port LAN port Max 4 VRF network systems VRF network system 1 VRF network system 2 VRF network Ethernet Lighting facilities Security system Ventilation system Automatic fire alarm interface USB FUNCTIONS...

Страница 648: ...ormal Mismatch 21 Protect antifreeze status Reset Set 22 Temp limit valid status Invalid Valid BO 10 Operation setting OFF ON 14 Filter sign resetting Reset Not reset 15 Antifreeze operation setting Reset Set 16 SAVE operation setting Reset Set 17 Forced thermostat OFF setting Reset Set 18 Emergency stop setting Reset Set 19 Temp limit valid setting Invalid Valid MI 10 Operation mode status Cool H...

Страница 649: ...ext 5 Text 6 Device Device information BI 00 LON Network Adaptor error status Normal Abnormal 01 Gateway error status Normal Abnormal 02 ES Status Not Used Energy Saving BO 02 ES Setting Not Used Energy Saving MI 00 LON Network Adaptor unit error code Refer to FGL original error code 01 Gateway error code Refer to FGL original error code 02 ECA 1 status Invalid Invalid Stop Include Indoor Unit Onl...

Страница 650: ...on WHITE USB KEY software protection key with software 1 Includes the software and manuals for Web Monitoring Tool Additionally it works as the software protection key Software protection key to be connected to an USB port on the PC that the Web Monitoring Tool is installed Web Monitoring Tool runs only on a PC with this WHITE USB KEY OTHER REQUIRED DEVICES Locally purchased Personal computer that...

Страница 651: ...r the BACnet Gateway are connected to the PC Step5 Start the application Step6 Configure necessary settings for startup operation as follows 1 Perform all necessary initial settings such as IP address etc Then click the OK button Adaptor Setting window appears automatically 2 Select the connected adaptor and click OK button Then Unit Registration window appears and starts scanning all connected un...

Страница 652: ...erator Workstation B OWS PC Hardware locally purchased USB adap tor locally purchased USB adap tor locally purchased USB adap tor locally purchased USB adap tor locally purchased USB port LAN port Max 4 VRF network systems VRF network system 1 VRF network system 2 VRF network Ethernet Lighting facilities Security system Ventilation system Automatic fire alarm interface USB FUNCTIONS z zIndoor unit...

Страница 653: ...ormal Mismatch 21 Protect antifreeze status Reset Set 22 Temp limit valid status Invalid Valid BO 10 Operation setting OFF ON 14 Filter sign resetting Reset Not reset 15 Antifreeze operation setting Reset Set 16 SAVE operation setting Reset Set 17 Forced thermostat OFF setting Reset Set 18 Emergency stop setting Reset Set 19 Temp limit valid setting Invalid Valid MI 10 Operation mode status Cool H...

Страница 654: ...ext 5 Text 6 Device Device information BI 00 LON Network Adaptor error status Normal Abnormal 01 Gateway error status Normal Abnormal 02 ES Status Not Used Energy Saving BO 02 ES Setting Not Used Energy Saving MI 00 LON Network Adaptor unit error code Refer to FGL original error code 01 Gateway error code Refer to FGL original error code 02 ECA 1 status Invalid Invalid Stop Include Indoor Unit Onl...

Страница 655: ...ame and shape Quantity Application DVD ROM 1 Includes the software and manuals for BACnet Gateway WibuKey Software protection key 1 Software protection key to be connected to an USB port on the PC that is BACnet Gateway is installed BACnet Gateway runs only on a PC with this WibuKey OTHER REQUIRED DEVICES Locally purchased Personal computer that satisfies the following system requirements Echelon ...

Страница 656: ...he BACnet Gateway are connected to the PC Step5 Start the application Step6 Configure necessary settings for startup operation as follows 1 Perform all necessary initial settings such as IP address etc Then click the OK button Adaptor Setting window appears automatically 2 Select the connected adaptor and click OK button Then Unit Registration window appears and starts scanning all connected units...

Страница 657: ... 64 indoor units However only when VR II Series is installed To prevent the drop of signal level by taking distance of length or quantity of unit in VRF network with installing signal amplifier signal level can be recovered ELECTRICAL WIRING z z Except in the case of V and S SeriesI Indoor unit is installed 320 units or less CH A CH B X1 X2 X1 X2 L N TRANSMISSION POWER SUPPLY NO HIGH VOLTAGE IN U ...

Страница 658: ...tion Switch Disconnect switch FUSE 3 A 1Ø 50 60 Hz 208 240 V Terminal resistor Signal amplifier Filter mode OFF RB unit Other RB unit or indoor unit Switch Disconnect switch FUSE 3 A 1Ø 50 60 Hz 208 240 V Signal amplifier Filter mode ON Outdoor A direction Outdoor B direction C direction A F Make sure to install 1 piece of terminal resistor to each segment Terminal resister is provided for each outd...

Страница 659: ... on the PC board When the Filter mode setting is changed turn the power off once Otherwise the setting will not be recognized CN4 Body PC board Connecting wire Accessory DIMENSIONS 211 241 6 288 2 Ø5 67 89 5 89 5 29 Ø28 For dust proof bushing 4 Ø5 For M4 20 mm screws Ø28 For dust proof bushing For M4 20 mm screws 272 Hole pitch 95 Hole pitch 95 Hole pitch Ø22 2 For conduit Unit mm 05 191 CONTROL S...

Страница 660: ...setting the filter mode WIRING SPECIFICATIONS Use Size Wire type Remarks Power supply cable Maximum 1 25 mm2 60245 IEC 57 or equivalent 1 ø AC208 240 V 50 60 Hz 2 Wire ground Always ground the unit Minimum 0 5 mm2 Transmission cable 0 33 mm2 22AWG LEVEL4 NEMA non polar 2 core twisted pair solid core Shielded LONWORKS compatible cable Fuse capacity 3 A SPECIFICATIONS z zMain specification Power sup...

Страница 661: ...veral functions can be controlled from outside the house SYSTEM DIAGRAM C B A Indoor unit Outdoor unit Single system WLAN adapter DIMENSIONS 38 15 71 96 12 5 12 5 Indoor unit Indoor unit WLAN adapter WLAN adapter Outdoor unit Multiple system Unit mm 05 193 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 662: ...ter may get into the adapter through the wire causing failure On the floor On a curved sueface Good Prohibited On a curved sueface On the floor Reverse direction Tapping screws Accessories Reverse direction Connect the remote controller cable to the connecting cable and insert it to the connector Set to 2WIRE the DIP switch SW1 on the PC board of the indoor unit 05 194 CONTROL SYSTEM CONTROL SYSTE...

Страница 663: ...5 50 Weight Net g 35 without cable Gross 380 Operating temperature range C 0 to 46 WIRELESS SPECIFICATIONS Communication method between wireless LAN router and WLAN adapter is as follows Wireless LAN standard IEEE802 11b g n Frequency bands 2 4 GHz 1ch 13ch Maximum radio frequency power 80 mW MAC ____________ SSID AC UTY ____________ PIN ________ Important Please do not discard 05 195 CONTROL SYST...

Страница 664: ...A B C Indoor Unit SW External input cable External switch controller Remote controller cable Remote controller cable Remote controller Use A B B C 2 wire type 50 m or less 500 m or less 3 wire type 50 m or less 25 m or less 500 m or less ELECTRICAL WIRING z zFor non polar 2 wire EXIN2 EXIN1 Remote Controller Cord REMOTE CONTROL External input cable Remote controller cable External switch controlle...

Страница 665: ...sistance R OFF 100 kΩ A twister pair cable 0 33 1 25 mm 16 22AWG should be use Maximum length of cable is 50m External switch controller DIMENSIONS For M4x16 screws Hole pitch 30 25 Hole 2 Ø5 Hole 2 Ø7 For code Ø5 For code Ø5 For code Ø7 For code Ø7 3 Ø4 5 98 2 Ø10 2 Ø8 121 10 43 Hole 2 x 8 117 140 For open case 30 25 Unit mm 05 197 CONTROL SYSTEM CONTROL SYSTEM ...

Страница 666: ...en the cables Remote controller cable Non polar 20 mm Insulated connection Red White Black Connecting cable Cut and insulate Fig 1 Fig 2 Connect the remote controller cable to the connecting cable and insert it to the connector Set to 2WIRE the DIP switch SW1 on the PCB of the indoor unit Set to 2WIRE the DIP switch SW1 Connect to earth ground screw Remote controller cable Non polar Layout of Conn...

Страница 667: ...le as shown in Fig 2 Be sure to insulate the connection between the cables Remote controller cable Insulated connection Red White Connector White Black Connecting cable Fig 1 Fig 2 Red Black Connect the remote controller cable to the connecting cable and insert it to the connector Terminal block to outdoor unit power supply Connector Indoor unit Connecting cable Remote controller cable When the bo...

Страница 668: ...al 1 Screw M4 x 16 mm 3 For installing the external switch controller Cable tie 4 For securing controller cable WIRING SPECIFICATIONS Use Size Cable type Remarks Remote controller cable 2 wire type 0 33 to 1 25 mm2 16 22AWG Sheathed PVC cable Non polar 2 core twisted pair Maximum cable length 500m Remote controller cable 3 wire type 0 33 mm2 22AWG Polar 3core twisted pair Maximum cable length 25m ...

Страница 669: ...C HEAT 20 C 30 C 16 C 26 C 30 C 20 C 16 C MODE1 P1 Arbitrary operation state P2 OFF TIMER 1 3 6 12 24hr Others setting are arbitrary Indoor unit External SW controller External contact 1 SW1 ON OFF OFF P1 ON OFF TIMER P2 Operation state P1 ON HEAT 20 C P2 16 C HEAT 20 C HEAT 16 C When operating in the state set when an external contact switch was set to ON and returning to the original operation s...

Страница 670: ...its of the same refrigerant system and cooling and heating are switched by one temperature sensor P1 ON COOL 26 C P2 ON HEAT 21 C SW1 Operation state ON OFF HEAT 21 C OFF ON P2 P1 COOL 26 C COOL 23 C When preventing chattering noise within 1 minute of the external contact switch MODE1 Delay time setting Delay P1 Arbitrary operation state P2 Arbitrary operation state Others setting are arbitrary Ex...

Страница 671: ...quipped in facilities such as hotel rooms Card key or other sensor switches are available as locally purchased parts SW1 SW2 COM Terminal Connection to external contacts Open circuit voltage 12 V 2 V Short circuit current 2 mA Short circuit detection resistance RON 1 kilo ohm Open circuit detection resistance ROFF 50 kilo ohm Dry contact External switch controller External contact 1 External conta...

Страница 672: ...rd is varies depending on the type of indoor unit Terminal block Functional earthing If necessary Remote controller cable Set to 3WIRE the DIP switch SW1 Indoor unit PC board Y1 Y2 Y3 Black White Red NOTE The equipment may fail if it is connected to the outdoor unit or the power supply terminal block z zPattern B 1 Use a tool to cut off the terminal on the end of the remote controller cable and th...

Страница 673: ...unit PC board PACKING LIST Name and shape Quantity Application Installation manual 1 Screw M4 16 mm 2 For installing the external switch controller Cable tie 5 For external switch controller and cable binding WIRING SPECIFICATIONS Use Size Wire type Remarks Remote controller cable 0 33 mm2 22AWG Polar 3 core Use sheathed PVC cable or shielded cable in accordance with the regional cable standard Ex...

Страница 674: ...al switch controller is connected to all the indoor units of the same refrigerant system and cooling and heating are switched by one temperature sensor When preventing chattering noise within 1 minute of the external contact switch MODE1 Delay time setting Delay P1 Arbitrary operation state P2 Arbitrary operation state Others setting are arbitrary Indoor unit External SW controller External contac...

Страница 675: ...e detail analysis on the cause in case an error occurs 3 Equipment Detail Status List Displays the detail information for sensor values electrical components etc of units in a specified refrigerant system in list form The information here can be used along with the detailed information in diagram form to check the operation status of units and make detail analysis on the cause in case an error occ...

Страница 676: ... the refrigerant system unit and time range 9 Operation Setting Changeable the operation status of the indoor unit individually or by group 10 Network Topology Analyzer A list of units connected to the VRF system network is displayed in network segments in tree form 11 Remote Setting Function Field Setting for indoor unit is realized remotely 12 System Time Setting An arbitrary time is set for all...

Страница 677: ...e maintenance period of indoor and outdoor units compressor FAN etc integrated time is output to a CSV file 17 Offline Data Reader Displays and compares the current data and the backup data saved in the past on dual screen 18 Version Confirm the current version of the software and if it is not the latest it can be updated to the latest version 19 Remote Operation Through the Internet Service Tool ...

Страница 678: ... with this WHITE USB KEY OTHER REQUIRED DEVICES Locally purchased Personal computer that satisfies the following system requirements Echelon U10 USB Network Interface TP FT 10 Channel Model number 75010R Required for each VRF Network VRF network system USB Adaptor Locally purchased Personal Computer Locally purchased Personal Computer Locally purchased Software protection key for Service Tool UTY ...

Страница 679: ...ace Software Adobe Reader 9 0 or later Internet transmission rate in remote access Internet environment capable for communication speed of 3 Mbps or more for uploading all the time including when accessing to oversea website For Remote Side PC Web browser Internet Explorer 11 0 or Microsoft Edge Display 1366 x 768 or higher resolution Set the resolution before use so that the resolution of Remote ...

Страница 680: ...ail analysis on the cause in case an error occurs 3 Equipment Detail List Displays the detail information for sensor values electrical components etc of units in a specified refrigerant system in list form The information here can be used along with the detailed information in diagram form to check the operation status of units and make detail analysis on the cause in case an error occurs 4 Operat...

Страница 681: ...oor unit is realized remotely 10 System Time Setting An arbitrary time is set for all the remote controllers within the system 11 Central Release The operation setting restriction function of the indoor units set from the controller can be forcibly released remote controller inhibit temperature upper lower limit setting 12 Model Name Writer An arbitrary model name can be written to the target unit...

Страница 682: ... USB Adaptor Locally purchased Personal Computer Locally purchased USB Adaptor Echelon U10 USB Network interface Easy to carry out with USB Adaptor PACKING LIST Name and shape Quantity Application DVD ROM 1 Includes the software and manuals for Service Tool WibuKey Software protection key 1 Software protection key to be connected to an USB port on the PC that the Service Tool is installed Service ...

Страница 683: ...bit Microsoft Windows 10 Pro 32 bit or 64 bit CPU 1 GHz or higher Memory 1 GB or more for Windows 7 32 bit Windows 8 1 32 bit and Windows 10 32 bit 2 GB or more for Windows 7 64 bit Windows 8 1 64 bit and Windows 10 64 bit HDD 10GB or more of free space Display 1024 768 or higher resolution Interface 2 USB ports 1 USB port is required for WibuKey connection 1 USB port is required for Echelon U10 U...

Страница 684: ...Support 4 VRF network system PC USB adaptors Max 4 adaptors per PC permit control and monitoring of up to 1 600 units Suitable for large scale buildings or hotels Max 400 indoor unit Max 400 indoor unit Max 400 indoor unit Max 400 indoor unit VRF network system 1 VRF network system 2 VRF network system 3 VRF network system 4 USB Adaptor Locally purchased Personal Computer Locally purchased Up to 2...

Страница 685: ...e Windows 7 8 1 10 32 bit 2GB or more Windows 7 8 1 10 64 bit HDD 40 GB or more of free space Display 1366 768 or higher resolution Interface USB port for U10 USB Network Interface Max 4 software protection key Either of the following interface is required for remote connection Internet using LAN Ethernet port is required Software Adobe Reader 9 0 or later Internet transmission rate in remote acce...

Страница 686: ...ration History 6 Error History 7 Graph 8 Data Buckup 9 Operation Setting 10 E mail automatic transmission of system malfunction 1 11 Network Topology Analyzer 12 Remote Setting 13 System Time Setting 14 Central Control Forced Release 15 Model Name Writer 16 Error Memory Reader 17 Time Guard Information 18 Offline Data Reader 19 Version 20 Software Update 1 Available only durring connection to the ...

Страница 687: ...et or Public Telephone LIne z zSupport 4 VRF network system PC USB adaptors Max 4 adaptors per PC permit control and monitoring of up to 1 600 units Suitable for large scale buildings or hotels Max 400 indoor unit Max 400 indoor unit Max 400 indoor unit Max 400 indoor unit VRF network system 1 VRF network system 2 VRF network system 3 VRF network system 4 USB Adaptor Locally purchased Personal Com...

Страница 688: ...soft Windows 8 1 Pro 32 bit or 64 bit Microsoft Windows 10 Pro 32 bit or 64 bit CPU 1 GHz or higher Memory 1 GB or more for Windows 7 32 bit Windows 8 1 32 bit and Windows 10 32 bit 2 GB or more for Windows 7 64 bit Windows 8 1 64 bit and Windows 10 64 bit HDD 40 GB or more of free space Display 1024 768 or higher resolution Interface Ethernet port for getting access to the Internet using LAN or M...

Страница 689: ...Monitoring of sensor data 9 Storage and CSV output of operating history sensor data 10 Indication of trend graph 11 Printing of trend graph 12 Monitoring and screen display of abnormalities 13 E mail automatic transmission of abnormalities 1 14 Setting for user level 15 Network Topology Analyzer 16 Remote Setting 17 System Time Setting 18 Central Release 19 Model Name Writer 20 Error Memory Reader...

Страница 690: ...6 SYSTEM DESIGN DTV_J3LE050E_03 CHAPTER06 2017 10 31 ...

Страница 691: ...ATING MATERIAL 06 20 2 5 ADDITIONAL CHARGE CALCULATION 06 21 2 6 EXAMPLE OF PIPING DESIGN 06 22 3 PIPING CONNECTION 06 26 3 1 CAUTION OF PIPING 06 26 3 2 PIPING TO OUTDOOR UNIT 06 28 3 3 SEPARATION TUBE 06 31 3 4 HEADER 06 34 3 5 EV KIT 06 37 4 WIRING DESIGN 06 41 4 1 ELECTRICAL WIRING 06 41 4 2 POWER SUPPLY CABLE WIRING 06 43 4 3 TRANSMISSION LINE 06 46 4 4 CONTROLLER CABLE WIRING 06 55 5 DRAIN C...

Страница 692: ... Maximum connectable indoor unit Connectable cooling capacity range 8 22 4 1 20 50 to 150 10 28 0 1 25 12 33 5 1 30 z zCaution When all indoor units are operating at maximum capacity individual indoor unit operate at a slightly lower capacity When connecting more than 100 Do not exceed both of connectable capacity range and maximum connectable indoor unit otherwise it may cause hinder the return o...

Страница 693: ... 3 Model Capacity kW Total capacity kW Connectable indoor unit capacity Judgement Min Max Outdoor unit AJ 072L 22 4 22 4 50 11 2 150 33 6 11 2 25 1 33 6 OK Indoor unit 1 AUXA30 9 0 25 1 Indoor unit 2 AUXA30 9 0 Indoor unit 3 AUXB24 7 1 z zExample 3 Prohibited Capacity ratio 175 Outdoor unit Indoor unit 1 Indoor unit 2 Indoor unit 3 Model Capacity kW Total capacity kW Connectable indoor unit capaci...

Страница 694: ...oor unit Indoor unit 1 Model Capacity kW Total capacity kW Connectable indoor unit capacity Judgement Min Max Outdoor unit AJ 072L 22 4 22 4 50 11 2 150 33 6 11 2 14 0 33 6 OK Indoor unit 1 AUXK54 14 0 14 0 06 03 SYSTEM DESIGN SYSTEM DESIGN ...

Страница 695: ...tal wiring length in 1 segment 500m VRF network system segment Wiring length 3600m 500m Number of unit 400 64 Segment Please refer to MAXIMUM CONNECTION OF NETWORK SEGMENT for network segment figure and explanation THE MAXIMUM CONNECTABLE UNIT z zOutdoor unit and indoor unit Maximum connectable units in one VRF network system Outdoor unit 100 Indoor unit 400 06 04 SYSTEM DESIGN SYSTEM DESIGN ...

Страница 696: ...oller is used Network Convertor UTY VGGXZ1 is required Max controllable remote controller groups 8 Max controllable indoor units 60 Individual Control Wired Remote Controller UTY RNR Z2 Max controllable indoor units 16 UTY RLR Max controllable indoor units 16 UTY RNK Max controllable indoor units 16 Simple Remote Controller with master control UTY RSR UTY RSK Max controllable indoor units 16 Simpl...

Страница 697: ...controllable remote controller groups 1600 per 4 VRF network system Max controllable indoor unit 1600 per 4 VRF network system Max controllable groups 1600 per 4 VRF network system Wireless LAN Adaptor UTY TFSXZ1 Connected to each indoor unit External Switch Controller UTY TERX UTY TEKX Max connectable indoor units 16 Service Maintenance Service Tool UTY ASGXZ1 1 1 Service Tool or 1 Web Monitoring...

Страница 698: ...ifier have to keep the following limitation Segment inside Limitation Transmission line 500m or less Number of unit 1 See the next page 64 or less Terminal resistor 1 1 2 3 4 5 6 25 1 2 3 4 1 2 3 1 2 3 4 5 62 4 62 62 64 64 64 63 63 63 34 26 27 28 29 30 31 32 33 Network segment 1 Signal Amplifier Signal Amplifier Transmission line within 500m 64units 64units 64units Signal Amplifier Network segment...

Страница 699: ...unit for Duct UTB WC IR receiver unit for Cassette UTY LRHYB1 IR receiver unit for Cassette Circular flow UTY LBHXD Human Sensor Kit UTY SHZXC Adaptor Convertor External switch controller UTY TERX UTY TEKX Network convertor UTY VTGX UTY VGGXZ1 Network convertor for LONWORKS UTY VLGX Network Convertor AC power supply UTY VTGXV KNX Convertor for VRF UTY VKGX KNX Convertor for Indoor Unit UTY VKSX Mo...

Страница 700: ...o Network convertor 100m Network Convertor for LONWORKS UTY VLGX In each network segment 500m KNX Convertor UTY VKGX Modbus convertor UTY VMGX Signal amplifier UTY VSGXZ1 External switch controller UTY TERX UTY TEKX External switch to UTY TERX UTY TEKX 50m Max connectable 16 indoor units 2 Remote controllers can be used jointly Indoor unit to UTY TERX UTY TEKX 25m Wired Simple remote controller UT...

Страница 701: ...of reach of children A position where there is no danger of the generation influx or accumulation of flammable gas A position that does not have a special environment such as large amounts of oil vapor or sulfide gas z zPrecaution for outdoor unit mounting position Do not tilt the outdoor unit more than 5mm 0 3 degrees However do not install the unit with it tilted towards the side containing the ...

Страница 702: ...e preventive measures so that they cannot reach the unit Do not install where there is oily smoke machine oil i e factory salty environment with direct sea breeze and too much of dust Install the unit where drainage does not cause any trouble Welding parts may be fretted if the unit is installed where corrosive gas such as sulphurous acid gas is generated Control may not operate correctly if the u...

Страница 703: ... Endurance pressure of the pipe must be 4 2 MPa Please select the pipe size in accordance with regional standard LUBRICANT Refrigerant R410A Mixed refrigerant Lubricant FVC68D TOOLS R410A work requires a number of special tools Since the tools with 4 symbol for R22 work cannot be used for R410A prepare them beforehand Tool name Process and application Pipe cutter Pipe cutting Refrigerant piping wo...

Страница 704: ...frigerant to be used Always use the specified refrigerant Prepare materials tools matched to the refrigerant Air purging by refrigerant gas is strictly prohibited Use a special vacuum pump with reverse check mechanism Seal with nitrogen up to 4 2 MPa After 24 hours check wether the pressure in piping has not descended Calculate the refrigerant additional charging amount and charge a suitable amoun...

Страница 705: ...oor unit and the nearrest indoor unit 5m or more a c Between outdoor unit and the first seperation tube 3m or more a Maximum allowable height difference Between outdoor unit and indoor unit Outdoor unit is higher than indoor unit 50m or less H1 Outdoor unit is lower than indoor unit 2 O T 5 C 40m or less 2 O T 5 C 5m or less Between indoor unit 3 Outdoor unit is higher than indoor unit 50m or less...

Страница 706: ...pe size is larger than designated size The refrigerant flow velocity will drop Refrigerant oil will not return to the outdoor unit Insufficient refrigerant oil resulting in compressor damage The refrigerant in liquid pipe will flush easily Insufficient cooling and heating If the pipe size is smaller than designated size The refrigerant circulation volume will drop Insufficient cooling and heating ...

Страница 707: ...e B Pipe size table C PIPE SIZE SELECTION Caution After referring to COOLING CAPACITY TABLE followed select each Pipe size Separation tube and Header from COOLING CAPACITY TABLE of outdoor unit and Indoor unit connected in the system z zPipe size table A Between outdoor unit and the first seperation tube header HP Model code Outdoor unit cooling capacity kW Outside diameter mm in Liquid pipe Gas p...

Страница 708: ... capacity of indoor unit connected downstream z zPipe size table C Between separation tube header to indoor unit Model code Cooling capacity of indoor unit kW Outside diameter mm in Liquid pipe Gas pipe 04 07 09 1 1 2 2 2 8 6 35 1 4 9 52 3 8 1 12 14 18 3 6 4 5 5 6 6 35 1 4 12 70 1 2 24 30 34 36 45 54 60 7 1 9 0 10 0 11 2 12 5 14 0 18 0 9 52 3 8 15 88 5 8 72 90 22 4 25 0 9 52 3 8 19 05 3 4 96 28 0 ...

Страница 709: ...g capacity of indoor unit kW 3 6 Branches 3 8 Branches 28 0 or less UTR H0906L UTR H0908L 28 1 to 56 0 UTR H1806L UTR H1808L z zEV kit These models are used for EEV external models Application model Model AS E004GTAH AS E007GTAH AS E009GTAH AG E004GCAH AG E007GCAH AG E009GCAH UTR EV09XB AS E12GACH AS E14GACH AS E012GCAH AS E014GCAH AG E012GCAH AG E014GCAH UTR EV14XB 06 18 SYSTEM DESIGN SYSTEM DESI...

Страница 710: ...RXD24GALH Medium static pressure duct 7 1 ARXA24GBLH 9 0 ARXA30GBLH 11 2 ARXA36GBLH 12 5 ARXA45GBLH Type Cooling capacity kW Model name High static pressure duct 11 2 ARXC36GBTH 12 5 ARXC45GATH 18 0 ARXC60GATH 22 4 ARXC72GBTH 25 0 ARXC90GBTH 28 0 ARXC96GBTH Large Airflow Duct 5 6 ARXN018GLBH 7 1 ARXN024GTBH 9 0 ARXN030GTBH Compact floor 1 1 AG A004GCAH 2 2 AG A007GCAH 2 8 AG A009GCAH 3 6 AG A012GC...

Страница 711: ...ess than 0 040 W m k is used Recommended minimum thickness for heat insulating material mm Relative humidity 70 75 80 85 Refrigerant pipe Outside diameter mm in 6 35 1 4 8 10 13 17 9 52 3 8 9 11 14 18 12 70 1 2 10 12 15 19 15 88 5 8 10 12 16 20 19 05 3 4 10 13 16 21 22 22 7 8 11 13 17 22 28 58 1 1 8 11 14 18 23 When an ambient temperature and relative humidity exceed 32 C DB and 85 respectively pl...

Страница 712: ...35 0 021 ø9 52 0 058 ø12 70 0 114 2 Calculation of additional amount for pipe length Total length of ø9 52mm liquid pipe a x 0 058 kg m m kg Total length of ø12 70mm liquid pipe a x 0 114 kg m m kg Total length of ø6 35mm liquid pipe a x 0 021 kg m m kg A Total kg 3 Calculation of additional charge refrigerant A kg Round up A to 2 decimal place 4 Factory charged amount b Outdoor unit factory charg...

Страница 713: ... unit z zSystem configuration Indoor units 1 2 3 4 5 6 7 8 Total Capacity kW Model name ARXD12 ARXD12 ARXD12 ARXD12 ARXD12 ARXD12 ARXD12 ARXD09 28 0 Capacity kW 3 6 3 6 3 6 3 6 3 6 3 6 3 6 2 8 z zSystem configuration Outdoor unit Outdoor unit Model name AJ 072 Capacity kW 22 4 z zCapacity ratio Total indoor unit capacity Total outdoor unit capacity 28 0 22 4 125 0 Within 50 to 150 z zSelection of ...

Страница 714: ...ube and the farthest indoor unit b c d e f g h 37 90m or less OK Between outdoor unit and the nearest indoor unit a a1 55 5m or more OK Between outdoor unit and the first seperation tube a 40 3m or more OK z zCalculation of additional charge refrigerant 1 Calculation of additional amount for pipe length Liquid pipe size 12 70 9 52 6 35 Additional refrigerant kg m 0 114 0 058 0 021 Liquid pipe leng...

Страница 715: ...tem configuration Indoor units 1 2 3 4 5 6 Total Capacity kW Model name ARXD24 ARXD18 ARXD14 ARXD09 ARXD09 ARXD09 25 6 Capacity kW 7 1 5 6 4 5 2 8 2 8 2 8 z zSystem configuration Outdoor unit Outdoor unit 1 Model name AJ 090 Capacity kW 28 0 z zCapacity ratio Total indoor unit capacity Total outdoor unit capacity 25 6 28 0 91 4 Within 50 to 150 z zSelection of branch kit Branch point No Model BP1 ...

Страница 716: ... less OK Between the first separation tube and the farthest indoor unit b c f3 30 90m or less OK Between outdoor unit and the nearest indoor unit a b1 90 5m or more OK Between outdoor unit and the first seperation tube a 75 3m or more OK z zCalculation of additional charge refrigerant 1 Calculation of additional amount for pipe length Liquid pipe size 12 70 9 52 6 35 Additional refrigerant kg m 0 ...

Страница 717: ...ither cut it out or use the reducer z zBrazing While Brazing the pipes be sure to blow dry nitrogen gas through them If nitrogen gas is not blown through the pipes while they are being brazed an oxidized layer may form on the inside of the pipes If this occurs the cooling efficiency may decrease and the air conditioner unit compressor valves etc cause malfunction 0 02MPa Pressure hose Rubber stopp...

Страница 718: ...not used it will be caused to damage for compressor and clog the strainer and electronic expansion valve Example Inside state of brazing pipe section Nitrogen gas used Nitrogen gas does not used Nitrogen gas used but not sufficient Oxygen gas still inside the pipe 06 27 SYSTEM DESIGN SYSTEM DESIGN ...

Страница 719: ...ateral side and bottom Fig A When connecting at the bottom remove the service panel and piping cover on the front of the outdoor unit and open the knock out hole provided at the bottom corner of the piping outlet It can be installed as shown on Fig B cutting out the 2 slits as indicated on Fig C When cutting slits use a steel saw Service panel Front Lateral 92 21 61 100 94 21 61 94 60 13 15 90 Top...

Страница 720: ...ve the pinch pipe in accordance with the following instructions 1 Verify that the liquid side and gas side 3 way valves are closed Fig A 2 Cut the end of the liquid side and gas side pinch pipe and vent the gas inside the pinch pipe Fig B 3 After all the gas is vented melt the brazing filter metal on connecting part using a burner and remove the pinch pipe Fig C 3 way valves Pinch pipes End of pin...

Страница 721: ...joint When removing the pinch pipe or brazing the joint pipe carry out the work while coolingdown the 3 way valve sufficiently 1 Braze the joint pipe onto the 3 way valves at the liquid and gas side Install the joint pipe appropriately so that it can be connected easily with the main pipe 2 Braze the joint pipe at the liquid and gas side with the main pipe Be sure to supply nitrogen when brazing J...

Страница 722: ... the connections with the pipe diameters that match the selected pipe sizes from the separation tubes and cut them with a pipe cutter When the pipe size of the separation tube itself does not match or when piping sizes differ even if it cuts the pipe use attached Reducer or attached Expander Standard cutting position 1 2L 3 0 mm NOTE Insert the field pipe firmly until it touches the joint pipe Sep...

Страница 723: ...ation Manual supplied with the outdoor unit for airtightness test and evacuation procedures 2 Straight pipe length A straight pipe minimum length 0 5m before separation tube is necessary in order to separation the refrigerant exactly Main pipe 0 5m or more 0 5m or more To indoor unit To indoor unit To indoor unit or to separation tube or to header To indoor unit or to separation tube or to header ...

Страница 724: ...he aforementioned heat insulation and the heat insulation on the local piping Insulations locally purchased Contact each other Tapes locally purchased Caution Insulate the liquid and gas pipe completely If not it may cause the water condensation or performance reduction Wrap the heat insulation with tape or pipe cover in order to extend the life time of heat insulation Take proper measurement to s...

Страница 725: ...ed to the port furthest opposite the outdoor unit side Always have at least one indoor unit connected to the port furthest opposite the outdoor unit side You can connect the indoor unit to any branch You can connect the indoor unit to any branch 2 Use a pipe cutter to cut at the location that matches the piping size or use expanders as necessary Joint pipe Connections Field pipe Expander Cut in th...

Страница 726: ...owing restriction 1 Installation angle Install the header so that it branches horizontally Gas pipe Good Prohibited Prohibited Liquid pipe Horizontal Horizontal Use a level to make sure that the header is positioned as shown in following figure and then secure it in place A H1 1 1 B H2 2 2 Gas pipe View from A View from B H1 0mm to 10mm α1 0 to 1 β1 10 to 10 H2 0mm to 10mm α2 0 to 1 β2 10 to 10 Li...

Страница 727: ...der and attach it Tighten by using binders at five locations Binder Cover the plugging pipe with heat insulation and seal with tape Plugging pipe Heat insulation for plugging pipe Heat insulation for plugging pipe Heat insulation for header Tape Locally purchased z zCaution Separation tube is not allowed to install header kit Outdoor unit Header Header Outdoor unit Indoor unit Indoor unit Indoor u...

Страница 728: ...nd wiring length less than 5m EV kit should be considered to install away from the living quarters such as above the ceiling Install the EV kit where it can be accessed for servicing EV Kit Service hole Indoor unit 5m Max Piping and wiring length Ceiling CAUTION Do not install EV kit in a location with any of the following conditions Do not install the kit outdoor Do not install the kit where the ...

Страница 729: ...0mm or more INSTALLATION METHOD CAUTION The installation direction can be selected either horizontal Pattern A or vertical Pattern B but keep the inclination within 5º Pattern A Horizontal installation Level Wire Wire Level Vertical installation Pattern B Incorrect installation direction or angle may cause improper operation z zSuspended installation 1 Remove the 2 screws and replace them with the...

Страница 730: ...to fasten the unit to the wall Screw Accessory Wall Screw Screw CONNECT THE PIPES Connect EV kit to liquid pipe of EEV external models indoor unit Pipe size Indoor unit side ø 6 35mm Flare connection Outdoor unit side ø 6 35mm Use a toruque wrench to tighten the flare nut Pipe Tightening torque ø 6 35 1 4 16 0 to 18 0 N m Holding spanner Torque wrench Body side 90o 06 39 SYSTEM DESIGN SYSTEM DESIG...

Страница 731: ...or unit 2 Wrap the tube arround the connection and fasten both ends binders 3 Connect the ground to the indoor unit CAUTION Never bundle the wire with power supply Indoor unit Connect Tube short Wire indoor unit Binder small Ground EV kit wire SPECIFICATIONS Model name UTR EV09XB UTR EV14XB Dimensions mm H x W x D 121 x 416 x 65 Weight g 1500 Connection wire length m 5 06 40 SYSTEM DESIGN SYSTEM D...

Страница 732: ...circuit breaker could result in electrical shock or fire Before starting work check that power is not being supplied to the unit Connect the connection cable firmly to the terminal board Imperfect installation may cause a fire Always fasten the outside covering of the connection cable with the cord clamp If the insulator is chafed electric leakage may occur Always connect the ground wire Never ins...

Страница 733: ...g length Max 500m Group Remote Controller connection cable Polar 3 core shielded 0 33mm2 Max length total 100m Touch Panel Controller System Controller IR receiver unit Duct type indoor unit can be controlled with wireless remote controller Service Tool Multi system Card key Single system Outdoor unit Indoor unit Cassette Indoor unit Duct Touch Panel Controller Group Remote Controller Wired Remote...

Страница 734: ...erant system When the crossover wiring is done make a connection for indoor unit to satisfy conditions Table A and Table B below Table A Current breaker requirements Model MCA A Fuse capacity A All models 1 20 MCA Minimum Circuit Ampacity 1 Refer chapter4 2 ELECTRIC CHARACTERISTICS When the power crossover wiring is done make it so that the total of the MCA of the connected indoor units does not e...

Страница 735: ...l standard Specific wiring requirement should be applied Type 60245 IEC66 or equivalent To prevent the electrical noise malufunction and hazards from insulation failure the unit should be connected to ground A disconnect switch may be required for ease of maintenance in accordance with the regional standard for each unit Please check the regional standard Make the wire length between disconnect sw...

Страница 736: ...aker is designed locate it at a place where the users cannot start and stop in the daily work Regulation of wire size and circuit breaker differs from each locality please refer in accordance with regional standard AJ 072LE AJ 090LE AJ 108LE Sub Breaker Sub Breaker Sub Breaker 20A 20A 25A Power cable 6 mm2 Power cable 6 mm2 Power cable 6 mm2 Sub Breaker Terminal board Terminal board Sub Breaker 20...

Страница 737: ...nced Static Capacitance To Ground 1KHz nF km Less than 3 28 9 Characteristic Impedance 772KHz Ohm 102 15 87 to 117 1MHz 100 15 85 to 115 4MHz 100 15 85 to 115 8MHz 100 15 85 to 115 10MHz 100 15 85 to 115 16MHz 100 15 85 to 115 20MHz 100 15 85 to 115 10 Attenuation 772KHz dB km Less than 15 1MHz Less than 18 4MHz Less than 36 8MHz Less than 49 10MHz Less than 56 16MHz Less than 72 20MHz Less than 7...

Страница 738: ... MAX 3600 m AB BC BD DE EF EG GH 3600 m Fig 2 A B C D E F A B C D NS 1 NS 2 NS 4 NS 3 E F G H Transmission line Transmission line System Controller System Controller Touch Panel Controller Touch Panel Controller Signal Amplifier Outdoor unit Outdoor unit Fig 2 Fig 1 Indoor unit Indoor unit Terminal resistor Terminal resistor Terminal resistor When AB BC BD DE EF 500m Signal Amplifier is required 1...

Страница 739: ...ssion cable like as Fig 3 1 3 2 Transmission line Refrigerant system 1 Refrigerant system 2 Refrigerant system 3 Transmission line Transmission line Fig 3 1 Fig 3 2 Indoor unit Indoor unit Indoor unit Outdoor unit Outdoor unit Outdoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Refrigerant system 1 Refrigerant system 2 Refrigerant system 3 X...

Страница 740: ...unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Refrigerant system 1 Refrigerant system 2 Refrigerant system 3 Outdoor unit Outdoor unit Outdoor unit X1 X2 Indoor units to outdoor unit Z1 Z2 Connection for different refrigerant circuit of outdoor unit z zStep 3 Check Transmission wiring rule Confirm transmission wiring rule above 06 ...

Страница 741: ...roller Touch Panel Controller When AB BC BD DE EF 500m Signal Amplifier is required Signal Amplifier Outdoor unit Outdoor unit Fig 2 Fig 1 Indoor unit Indoor unit Terminal resistor Terminal resistor Terminal resistor z zStep 5 Confirm how to wire transmission line Confirm how to connect transmission line between indoor units Arrange so that there is one terminal resistor for each network segment A...

Страница 742: ...e lines may cause poor communication for one terminal In this case please use a terminal box Note Do not loop Example 1 Connecting each outdoor and indoor unit with one connection wiring Refrigerant system 1 Refrigerant system 2 Refrigerant system 3 Signal Amplifier Example 2 Separating transmission line Refrigerant system 1 Separate on the terminal for transmission line Separate using terminal bo...

Страница 743: ...frigerant system 1 System controller Terminal board Refrigerant system 2 Refrigerant system 3 Example 4 Combination of example 2 and 3 Refrigerant system 1 System controller Terminal board Refrigerant system 2 Refrigerant system 3 06 52 SYSTEM DESIGN SYSTEM DESIGN ...

Страница 744: ...it Breaker Breaker Transmission Transmission Remote control Remote control Remote control Transmission Transmission Breaker Breaker Breaker Indoor unit Indoor unit Power supply Power supply Power supply 1 2 2 2 1 1 X1 X2 Indoor units to outdoor unit Z1 Z2 Connection for different refrigerant circuit of outdoor unit 1 The number of power supply terminals is different depending on the indoor unit mo...

Страница 745: ...Example Circuit breaker Circuit breaker Outdoor unit power supply cable Indoor unit power supply cable Remote controller cable Transmission cable 230V 1ø 50Hz 400V 3ø 50Hz 06 54 SYSTEM DESIGN SYSTEM DESIGN ...

Страница 746: ...2 to 1 25mm2 Sheathed Non polar 2core Twisted pair 1 External input 0 33mm2 Shielded Polar 2core Twisted pair IR Receiver Unit UTB WC Indoor unit Connection cable 5m cable attached IR Receiver Unit UTY LRH B1 UTY LBHXD Indoor unit Connection cable Human Sensor Kit UTY SHZXC Indoor unit Connection cable Remote Sensor Indoor unit Connection cable 10m cable attached EV Kit Indoor unit Connection cabl...

Страница 747: ...mber of remote controllers by cable size and the length Cable size Max connectable number of remote controllers AWG mm2 L 100 m 100 m L 250 m 250 m L 500 m 16 1 25 4 4 4 18 0 75 1 25 S 0 75 4 4 2 20 0 5 0 75 S 0 5 4 2 2 22 0 3 0 5 S 0 3 4 1 1 L Total cable length S Cable size 06 56 SYSTEM DESIGN SYSTEM DESIGN ...

Страница 748: ... and drain cap are used the drain water in the pipe may freeze in extremely cold weather As the drain water flows out of the outdoor unit during heating operation install the drain pipe and connect it to a commercial 16 mm hose When installing the drain pipe plug all the holes other than the drain pipe mounting hole in the bottom of the outdoor unit with drain cap so there is no water leakage 446 ...

Страница 749: ...ng the drain hose to the indoor unit use the accessory band Except compact wall mounted type and wall mounted type COMPACT CASSETTE TYPE 300mm or less Max 700mm Attached band drain hose accessory Downward gradient 1 100 or more Horizontal or upward gradient VP25 Local arrangement 1 5m to 2 0m Hanging fitting Downward gradient 1 100 or more Air bleeding Rise Trap Prohibited Drain lift up pipe restr...

Страница 750: ...t VP25 1 5m to 2 0m Hanging fitting Downward gradient 1 100 or more drain hose accessory Air bleeding Rise Trap Prohibited Drain lift up pipe restrictions 1 Lift up height 850mm from ceiling 2 Drain hose pipe length 300mm between indoor unit and lift up pipe When a dimensions exceed the above restrictions will cause water leakage 06 59 SYSTEM DESIGN SYSTEM DESIGN ...

Страница 751: ...d gradient 1 100 or more 700 mm or less Use general hard polyvinyl chloride pipe VP25 outside diameter 32 mm Do not perform a rise trap and air bleeding Provide a downward gradient 1 100 or more Provide supporters when long pipes are installed Use an insulation material as needed to prevent the pipes from freezing Install the pipes in a way that allows for the removal of the control box 06 60 SYST...

Страница 752: ... 2 m Prohibited Air bleeding Rise Trap z zFloor standing concealed setting Prohibited Trap Drain cap Rise Install the drain pipe with downward gradient 1 50 to1 100 and so there are no rises or traps in the pipe Use general hard polyvinyl chloride pipe VP25 outside diameter 32 mm and connect it with adhesive polyvinyl chloride so that there is no leakage When the pipe is long Install supporters Do...

Страница 753: ...s a drain port on the left and right sides Select the drain port to match the local conditions Nylon fastener Drain port Drain cap CAUTION Always check that the drain cap is installed to the unused drain port and is fastened with the nylon fastener If the drain cap is not installed or is not sufficiently fastened by the nylon fastener water may drip during the cooling operation 06 62 SYSTEM DESIGN...

Страница 754: ... Make the trap near to the indoor unit Position the trap in a location where it can be cleaned z zSafety drain pipe There is no need to provide a trap for the safety drain pipe If the safety drain pipe is connected to the main drain pipe make the connection below the trap on the main drain pipe Once installation is complete check the flow of the drain water Unit Drain hose main Drain hose safety D...

Страница 755: ... is a drain port on the left and right sides Select the drain port to match the local conditions Nylon fastener Drain port Drain cap CAUTION Always check that the drain cap is installed to the unused drain port and is fastened with the nylon fastener If the drain cap is not installed or is not sufficiently fastened by the nylon fastener water may drip during the cooling operation 06 64 SYSTEM DESI...

Страница 756: ...ore O D 38 mm or more Downward gradient 1 100 or more Use general hard polyvinyl chloride pipe VP25 outside diameter 32 mm Do not perform a rise trap and air bleeding Provide a downward gradient 1 100 or more Provide supporters when long pipes are installed Use an insulation material as needed to prevent the pipes from freezing Install the pipes in a way that allows for the removal of the control ...

Страница 757: ...hat the drain hose side is too high Height A should be less than 5mm Remove the hole cover Arrange the drain hose lower than this position Arrange the drain hose lower than this position Prohibited Prohibited Prohibited OK OK Drain hose Drain hose VT wire Base Bottom Intake grille Cut the grille Pass the drain hose through here Piping hole 06 66 SYSTEM DESIGN SYSTEM DESIGN ...

Страница 758: ...e so that the pipe slopes correctly within the indoor unit Arrange the drain hose lower than this position Prohibited Drain hose Drain hose Indoor unit rear view VT wire End in water Supporter 1 5m to 2 0m Rise Trap 06 67 SYSTEM DESIGN SYSTEM DESIGN ...

Страница 759: ... pipe drain holder Screw drain pan drain hose drain pan drain cap Left piping Pipe Cable Drain hose Cable For connection from the left rear Putty Putty No upward slope Accumulated drain water Air No upward slope End of drain hose is immersed in water 50 mm or less from ground No gap Drain cock Drain cap Hexagon wrench 06 68 SYSTEM DESIGN SYSTEM DESIGN ...

Страница 760: ...ht side Left side Drain hose Drain hose Saddle Saddle No gap No gap Drain cap Drain Cock End in water End in water Wave Wave Liftted up Liftted up Insulation Insulation Indoor unit drain hose Hexagonal wrench Installation method of Drain cap For left outlet piping cut off the piping outlet cutting groove with a hacksaw Insert the drain cap until it butts against the drain port Insert the drain hos...

Страница 761: ...e type z zFor High static pressure duct type z zFor Slim duct type Select converging drain pipes whose diameter is suitable for the operating capacity of the unit 100 mm or more 100 mm or more 100 mm or more 850 mm or less 700 mm or less T joint converging drain pipes VP30 O D 38 mm or more Downward gradient 1 100 to 1 50 06 70 SYSTEM DESIGN SYSTEM DESIGN ...

Страница 762: ...eat by the heat insulator of enough thickness so that there is no dewy when the confirmation ends Fix the drain pipe on to the wall with saddle Pipe Saddle Wall Outside wall cap Sealer putty Outdoors After put out Drain hose from the wall please cover the space with the putty etc Silicone sealant Heat insulation adhesive tape Be sure to coat the entire end surface If there is a gap it could cause ...

Страница 763: ...or outdoor unit drain piping work Drain pipe 1 For outdoor unit drain piping work Joint pipe A 1 090 108 model only For connecting gas pipe L type Joint pipe B 1 090 108 model only For connecting gas pipe Straight type Joint pipe C 1 090 model only For connecting liquid pipe Pipe reducer Push mount cable tie 2 For binding transmission cable Grommet edging 2 For power supply cable and connection ca...

Страница 764: ...joint Gas pipe Special nut A Large flange 4 For installing indoor unit Special nut B Small flange 4 For installing indoor unit Template Carton top 1 For ceiling openings cutting Also used as packing Drain hose 1 For installing drain pipe Hose band 1 For installing drain hose Drain hose insulation 1 For installing drain pipe Name and shape Q ty Application Connector cover 1 For covering connector T...

Страница 765: ...heat insulation Small 1 For indoor side pipe joint Liquid pipe Coupler heat insulation Large 1 For indoor side pipe joint Gas pipe Name and shape Q ty Application Template Carton top 1 For installing indoor unit Washer 8 For installing indoor unit Insulation 1 For installing drain pipe Drain hose assy 1 For installing drain pipe Hose band 1 For installing drain hose Drain pipe insulation 1 For ins...

Страница 766: ...lation Small 1 For indoor side pipe joint Liquid pipe Coupler heat insulation Large 1 For indoor side pipe joint Gas pipe Name and shape Q ty Application Template Carton top 1 For installing indoor unit Washer 8 For installing indoor unit Insulation 1 For installing drain pipe Drain hose assy 1 For installing drain pipe Hose band 1 For installing drain hose Drain pipe insulation 1 For installing d...

Страница 767: ...joint Large pipe Coupler heat insulation Small 1 For indoor side pipe joint Small pipe Cable tie Medium 2 For transmission and remote control cable binding Large 4 For fixing the coupler heat insulation Name and shape Q ty Application Filter Small 2 AR04 07 09 12 14 24 Filter Big 2 AR18 1 AR24 Drain hose 1 For installing drain hose Band 1 For installing drain hose Drain hose insulation B 1 Insulat...

Страница 768: ...joint Large pipe Coupler heat insulation Small 1 For indoor side pipe joint Small pipe Cable tie Medium 2 For transmission and remote controller cable binding Large 4 For fixing the coupler heat insulation Name and shape Q ty Application Filter Small 2 AR07 09 12 14 24 Filter Big 2 AR18 1 AR24 Drain hose 1 For installing drain hose Hose band 1 For installing drain hose Drain hose insulation B 1 In...

Страница 769: ...ion Small 1 For indoor side pipe joint Liquid pipe Coupler heat insulation Large 1 For indoor side pipe joint Gas pipe Name and shape Q ty Application Special nut A Large flange 4 For suspending the indoor unit from ceiling Special nut B Small flange 4 Hanger 4 For suspending the indoor unit from ceiling Drain hose 1 For installing drain hose Hose band 1 For installing drain hose Drain hose insula...

Страница 770: ... Coupler heat insulation Small 1 For indoor side pipe joint Liquid pipe Coupler heat insulation Large 1 For indoor side pipe joint Gas pipe Name and shape Q ty Application Special nut A Large flange 4 For suspending the indoor unit from ceiling Special nut B Small flange 4 Drain hose 2 For installing drain hose Hose band 2 For installing drain hose Drain hose insulation 2 For installing drain hose...

Страница 771: ...nsulation Small 1 For indoor side pipe joint Liquid pipe Coupler heat insulation Large 1 For indoor side pipe joint Gas pipe Name and shape Q ty Application Special nut A Large flange 4 For suspending the indoor unit from ceiling Special nut B Small flange 4 Hanger 4 For suspending the indoor unit from ceiling Drain hose 1 For installing drain hose Hose band 1 For installing drain hose Drain hose ...

Страница 772: ...lation Small 1 For indoor side pipe joint Liquid pipe Coupler heat insulation Large 1 For indoor side pipe joint Gas pipe Name and shape Q ty Application Special nut A Large flange 4 For suspending the indoor unit from ceiling Special nut B Small flange 4 Washer 8 Drain hose 1 For installing drain hose Hose band 1 For installing drain hose Drain hose insulation 1 Insulates the drain hose and drain...

Страница 773: ...or fixing the wall bracket Coupler heat insulation 2 For indoor side pipe joint Cable tie Large 4 For fixing the coupler heat insulation Medium 2 For transmission and remote controller cable binding Drain hose 1 For installing drain hose Hose band 1 For installing drain hose Drain hose insulation 1 Adhesive type 100 x 220 mm VT wire 1 For fixing the drain hose L 280 mm Insulation pipe 1 Adhesive t...

Страница 774: ...pipe joint Gas pipe Coupler heat insulation Small 1 For indoor side pipe joint Liquid pipe Name and shape Q ty Application Cable tie Extra large 4 For fixing the coupler heat insulation Large 2 Medium 2 For transmission and remote controller cable binding Special nut A Large flange 4 For installing indoor unit Special nut B Small flange 4 For installing indoor unit Installation template 1 For posi...

Страница 775: ...or unit installation Name and shape Q ty Application Tapping screw 8 For wall hook bracket installation Cloth tape 1 For indoor unit installation Push mount cable tie 1 For transmission and remote controller cable binding Air cleaning filter 2 For installation refer to the CLEANING AND CARE in the operating manual 06 84 SYSTEM DESIGN SYSTEM DESIGN ...

Страница 776: ...Application Operating manual 1 Installation manual 1 Wall hook bracket 1 For indoor unit installation Cable tie 1 For remote control cable binding Cloth tape 1 For indoor unit installation Name and shape Q ty Application Tapping screw 8 For wall hook bracket installation Connecting cable 1 For wired remote controller installation Air cleaning filter 2 For installation refer to the CLEANING AND CAR...

Страница 777: ...ng filter 2 For installation refer to the CLEANING AND CARE in the operating manual Air cleaning filter frame 2 z zModels AS A012 014GCAH AS E012 014GCAH Name and shape Q ty Application Operating manual 1 Installation manual 1 Operating Manual CD ROM 1 Wall hook bracket 1 For indoor unit installation Tapping screw 5 For wall hook bracket installation 06 86 SYSTEM DESIGN SYSTEM DESIGN ...

Страница 778: ... Insulation 1 For drain hose installation Connecting cable 1 For wired remote controller installation z zModels AS A30 34GTAH Name and shape Q ty Application Operating manual 1 Installation manual 1 Operating Manual CD ROM 1 Wall hook bracket 1 For indoor unit installation Tapping screw 8 For wall hook bracket installation Name and shape Q ty Application Drain hose Insulation 1 For installing drai...

Страница 779: ...7 FUNCTION SETTING DTV_VR2E018E_14 CHAPTER07 2017 10 31 ...

Страница 780: ...R AUTOMATIC ADDRESS SETTING 07 52 1 5 2 INDOOR UNIT AUTOMATIC ADDRESS SETTING 07 54 1 5 3 RB UNIT AUTOMATIC ADDRESS SETTING 07 56 1 5 4 EXAMPLE FLOW 07 58 1 6 TERMINAL RESISTOR SETTING 07 61 1 7 INDOOR UNIT CONNECTION CHECK 07 62 2 FUNCTION SETTING 07 65 2 1 OUTDOOR UNIT 07 65 2 1 1 VR II series 07 68 2 1 2 V III series 07 73 2 1 3 V II series 07 78 2 1 4 J IIIL J III J II series 07 82 2 1 5 J IIS...

Страница 781: ...TION 07 147 2 17 SIMPLE REMOTE CONTROLLER UTY RSR UTY RHR 07 148 2 17 1 REMOTE CONTROLLER ADDRESS SETTING 07 148 2 17 2 REMOTE CONTROLLER MASTER SLAVE SETTING 07 150 2 17 3 INDOOR UNIT ADDRESS VERIFICATION 07 151 2 18 NETWORK CONVERTOR 07 152 2 18 1 MODELS UTY VTGX UTY VTGXV 07 152 2 18 2 MODEL UTY VGGXZ1 07 153 2 19 SIGNAL AMPLIFIER 07 154 2 20 KNX CONVERTOR FOR VRF 07 156 2 21 KNX CONVERTOR FOR ...

Страница 782: ...of 1 2 SET5 1 OFF SET5 2 ON Number of 2 3 SET5 1 ON SET5 2 OFF Number of 3 Set the DIP SW SET3 1 3 2 Master SET3 1 OFF SET3 2 OFF Slave 1 SET3 1 OFF SET3 2 ON Slave 2 SET3 1 ON SET3 2 OFF SETTING FOR MASTER UNIT SLAVE UNIT SETTING FOR MASTER UNIT SLAVE UNIT SETTING FOR MASTER UNIT SLAVE UNIT SETTING FOR MASTER UNIT SLAVE UNIT step 1 step 2 step 3 step 4 step 5 step 7 SETTING FOR MASTER UNIT ONLY F...

Страница 783: ... UNIT SETTING Please refer to the correct SW position for 2 Function Setting This function is available VR II series Refrigerant circuit address setting RB unit address setting Set the Rotary SW REF AD x10 x1 See the detail for 1 2 Address setting Set the Rotary SW RB AD x10 x1 See the detail for 1 2 Address setting step 1 step 2 REMOTE CONTROLLER SETTING In case of Wired remote controller Simple ...

Страница 784: ... the setting method 1 4 3 n Wired R C 2 wire type Set this switch to 00 at factory setting See the setting method 1 4 4 n Automatic address setting Set this switch to 00 at factory setting See the setting method 1 5 2 E Indoor unit address 00 63 n Manual address setting Setting example 12 Arbitrary numbers can be set in range of 00 63 n Wireless R C Set this switch to 00 at factory setting See the...

Страница 785: ...ch 1 See the setting method 2 10 Signal amplifier K Signal amplifier address 1 8 n Manual address setting See the setting method 2 18 n Automatic address setting Set to 1 at factory setting See the setting method 1 5 1 Modbus convertor Q Controller Convertor address 00 15 1 See the setting method 2 19 Network convertor for LONWORKS M See the setting method 2 20 Central remote controller N See the ...

Страница 786: ...D SetE SetF SetD SetE SetF SetD SetE SetF SetD SetE SetF SetD SetE SetF SetD SetE SetF SetD SetE SetF SetD SetE SetF SetD SetE SetF SetD SetE SetF SetD SetE SetF 03 02 01 00 SetI SetI SetI SetI 01 SetH SW2 of DIP Switch1 ON OFF SetJ SW2 of DIP Switch1 ON OFF SetJ 00 SetG 1 SetK Signal amplifier R C line 3 wire R C line 3 wire R C line 3 wire 05 12 SetO SetP 01 12 SetO SetP 00 SetA 0 SetB 2 SetC 3 ...

Страница 787: ...er address REF AD X10 REF AD X1 IU AD X10 IU AD X1 RC AD SetO SetP Refrigerant circuit address RB unit address REF AD X10 REF AD X1 RB AD X10 RB AD X1 00 SetA 0 SetB 2 SetC 3 SetL Instructions for setting up the address 1 The refrigerant circuit address of the indoor units outdoor units and RB units can be set to arbitrary numbers in the range of 0 to 99 2 The Indoor unit address and RB unit addre...

Страница 788: ...r unit by piping 00 01 02 00 01 02 01 01 01 0 1 0 02 02 02 0 1 2 00 01 02 25 25 25 0 1 2 00 01 01 01 2 3 0 01 0 25 2 01 1 01 3 3 1 2 2 1 25 02 Refrigerant system 1 Refrigerant system 2 Refrigerant system 25 z z Example Outdoor unit Set A Indoor unit Set D RB unit Set O Refrigerant circuit address Rotary SW setting REF AD x10 REF AD x1 01 0 1 11 1 1 25 2 5 50 5 0 Setting range 00 99 Arbitrary numbe...

Страница 789: ...SW SET3 1 OFF SW SET3 2 OFF SW SET3 1 OFF SW SET3 2 ON SW SET3 1 ON SW SET3 2 OFF Outdoor unit address 0 1 2 DIP SW SET3 1 OFF OFF ON SET3 2 OFF ON OFF z z Number of slave unit Set C This function is available VR II V II and V III series Set at Master unit PCB only Please set the number of slave unit on Master unit PCB Number of slave unit 0 SW SET3 3 OFF SW SET3 4 OFF Master SW SET3 3 OFF SW SET3...

Страница 790: ... set Set for all outdoor units 1 2 3 2 3 3 Number of outdoor unit 1 Number of outdoor unit 2 Number of outdoor unit 3 SW SET5 1 OFF SW SET5 2 OFF SW SET5 1 OFF SW SET5 2 ON SW SET5 1 ON SW SET5 2 OFF Master Master Master Slave 1 Slave 1 Slave 2 Number of outdoor unit 1 2 3 DIP SW SET5 1 OFF OFF ON SET5 2 OFF ON OFF Factory Setting 07 09 FUNCTION SETTING FUNCTION SETTING ...

Страница 791: ...4 15 00 00 00 0 1 0 00 00 01 00 0 00 2 3 1 00 3 2 00 3 Indoor unit address Rotary SW setting IU AD x10 IU AD x1 03 0 3 11 1 1 30 3 0 47 4 7 Setting range 00 63 Arbitrary numbers can be set Do not set indoor unit address to the range of 64 from 99 Do not set the same address number to two or more indoor units 07 10 FUNCTION SETTING FUNCTION SETTING ...

Страница 792: ... 0 1 2 03 04 05 00 00 00 3 0 0 1 3 wire type R C R C line 3 wire 3 wire type R C 2 2 0 00 2 3 1 00 3 2 00 3 Remote controller address Rotary SW setting RC AD 0 0 1 1 11 B 15 F 1 Set the remote controller address in the order of 0 1 2 15 Blank is not allowed 2 When remote controller group is not constructed 1 1 connection of indoor unit and remote controller be sure to set the remote controller add...

Страница 793: ...roller address in the 0 only Factory setting is 0 00 01 02 00 00 00 0 0 0 03 04 05 00 00 00 0 0 0 1 2 wire type R C R C line 2 wire 2 wire type R C 0 00 2 3 1 00 3 2 00 3 1 Set the remote controller address in the 0 only Address is automatically assigned from Remote controller 07 12 FUNCTION SETTING FUNCTION SETTING ...

Страница 794: ...3 14 15 00 00 0 1 0 00 00 00 01 0 00 2 3 1 00 3 2 00 3 RB unit address Rotary SW setting RB AD x10 RB AD x1 03 0 3 11 1 1 30 3 0 47 4 7 Setting range 00 63 Arbitrary numbers can be set Do not set RB unit address to the range of 64 from 99 Do not set the same address number to two or more RB units 07 13 FUNCTION SETTING FUNCTION SETTING ...

Страница 795: ...ingle split AC Max 100 4 1 Set the Rotary SW 110 and SW 111 on network convertor PCB 2 The sum total of the Touch panel controller Central remote controller Network convertor for Group remote controller and Network convertor for LONWORKS is a maximum of 16 3 Up to 64 Group remote controllers are able to connect with one VRF Network system 4 When connecting the Network convertor for Single split AC...

Страница 796: ...rollers are able to connect with one VRF Network system z z Dual remote control switch Set J When 2 wired remote controllers are connected to the remote control group turn the SW 2 of DIP Switch 1 of Slave Remote Controller ON Slave remote controller will not be valid for timer setting Last command is priority Master Slave Master SW2 OFF ON of DIP Switch 1 SW2 OFF of DIP Switch 1 Remote controller...

Страница 797: ...ller and Network convertor for LONWORKS is a maximum of 16 z z Central remote controller setting Set N 00 01 02 03 Central remote controller Max 16 2 1 Set Central remote controller address first to conduct the initial setting of it Refer to the setting manual for details 2 The sum total of the Touch panel controller Central remote controller Network convertor for Group remote controller and Netwo...

Страница 798: ...s PCB PREPARATION 1 Set the switch on the indoor unit s PCB that is used for manual address setting is set to 00 at factory setting This process is unnecessary for newly installed and not yet set the SW Rotary switch type A SW601 SW602 SW604 SW605 SW606 SW607 SW608 Check the position 0 Factory setting IU AD x10 IU AD x1 REF AD x10 REF AD x1 If any of the switches is positioned at a value other tha...

Страница 799: ...error will be displayed by continuously pressing the MANUAL AUTO for 10 sec or more In this case release the button or turn off the power An explanation of the displayed information as shown below SELECTION AND CONFIRMATION OF CUSTOM CODE 5 Press the SET TEMP p or SET TEMP q buttons to select the custom code that matches the setting with the indoor unit By selecting the appropriate custom code the...

Страница 800: ...ut address valid range 00 99 Switches between the setting number bottom line and function number top line Increases and decreases the displayed number Start the address setting mode Changes the address display digits Transmits address setting Reconfirmation of address setting Confirmation of address setting Indication of address code Indication of address data number the ten s place Indication of ...

Страница 801: ... command is accepted Pi Pi Pi PiPiPi In the following cases the setting signal is not read and a buzzer sounds The indoor unit address No is set out of range 64 or more Pi Pi Pi Pi Pi The setting of the rotary switch on the PCB is not 00 Pi Pi Pi Pi Pi 12 Indoor unit will display the indoor unit address data number on TIMER ORANGE and FILTER RED light OPERATION GREEN TIMER ORANGE continuously Flas...

Страница 802: ...e will be heard if the command is accepted Pi Pi Pi PiPiPi In the following cases the setting signal is not read and a buzzer sounds The setting of the rotary switch on the PCB is not 00 Pi Pi Pi Pi Pi 19 Indoor unit will display the refrigerant circuit address data number on TIMER ORANGE and FILTER RED light 5 times Example ADDRESS 25 OPERATION LAMP GREEN TIMER LAMP ORANGE FILTER LAMP RED 0 5sec ...

Страница 803: ...ADDRESS SETTING 23 Press and hold the FAN and the SET TEMP p buttons Whilst holding these 2 buttons press the RESET button SET TEMP RESET FAN Function setting mode display z zIndoor unit address setting 24 Make sure the function number is 01 Refer to 8 Press the TIMER set button TIMER set z zRefrigerant circuit address setting 25 Make sure the function number is 02 Refer to 15 Press the TIMER set ...

Страница 804: ...and will remain in memory even when the power is turned off However setting address is effective after power reset Record the address set in the indoor unit on a label etc and affix the label to the unit so it can be used for after sales service operations Address 0 setting will not indicate TIMER LAMP and FILTER LAMP Once the RESET button is pressed on the remote controller the OPERATION MODE wil...

Страница 805: ... switch type A SW601 SW602 SW604 SW605 SW606 SW607 SW608 Check the position 0 Factory setting IU AD x10 IU AD x1 REF AD x10 REF AD x1 If any of the switches is positioned at a value other than 0 this function will not activate The layout of the switches differs depending on the type of the indoor unit Refer to 2 2 2 If multiple indoor units are connected to a single wired remote controller make su...

Страница 806: ...oor unit address first During address setting mode indoor unit reject the any operation command from remote controller Function number 01 Indoor unit address 02 Refrigerant circuit address Remote controller address Remote controller address setting number 00 15 SET BACK button Switches the remote controller address setting number SET TIME and button Switches the function number Setting number Sett...

Страница 807: ...set up the indoor unit address The setting range is from 00 to 63 Ex When indoor unit address data 12 is set up Indoor unit address data 8 Pressing the TIMER SET button confirm the selected indoor unit address data The data will be transferred to the indoor unit ERROR When indoor unit address data was not set up on the indoor unit is displayed Set up indoor unit address data again according to the...

Страница 808: ... TEMP Λ button set up the refrigerant circuit address data The setting range is from 00 to 99 Refrigerant circuit address data Ex When refrigerant circuit address data 18 is set up 12 Pressing the TIMER SET button confirm the selected refrigerant circuit address data The data will be transferred to the indoor unit GOOD ERROR When refrigerant circuit address data was normally set up on the indoor u...

Страница 809: ...ndoor unit Indoor unit Repeat the procedures in steps 1 through 13 and set up the indoor units requiring address setting Wired remote controller Wired remote controller Wired remote controller RESET THE POWER AFTER SETTING UP ADDRESS OF ALL INDOOR UNITS Important If the reset is not performed address can not be read in normally After all the addresses have been set the circuit breaker needs to be ...

Страница 810: ...at 0 factory setting Rotary switch type A SW601 SW602 SW604 SW605 SW606 SW607 SW608 Check the position 0 Factory setting IU AD x10 IU AD x1 REF AD x10 REF AD x1 If any of the switches is positioned at a value other than 0 this function will not activate The layout of the switches differs depending on the type of the indoor unit Refer to 2 2 2 When multiple indoor units are connected to a single wi...

Страница 811: ...ld the SET TEMP button and FAN button simultaneously for at least 2 seconds 5 The Menu 1 screen is displayed Press and hold the FAN button for at least 2 seconds Setting mode selection screen is displayed 6 Press the SET TEMP or SET TEMP button to select F1 Menu 2 F1 settings mode or F2 Menu 2 F2 settings mode F1 Initial settings mode F2 Maintenance settings mode 7 Press the button Setting item se...

Страница 812: ...e SET TEMP or SET TEMP button Then press the button Select the 2 wire remote controller address Ex Select the 002 01 11 Set the function number with the SET TEMP or SET TEMP button Then press the button Function number 12 Set the setting number with the SET TEMP or SET TEMP button Then press the button Indoor unit address 07 31 FUNCTION SETTING FUNCTION SETTING ...

Страница 813: ...utton to return to the 2 wire remote controller address selection screen of 2 If setting has been completed press the FAN button to return to the Menu 2 F1 item selection screen Note This item cannot be set from slave remote controllers z zRefrigerant circuit address setting 15 Select the 2 wire remote controller address with the SET TEMP or SET TEMP button Then press the button Select all 16 Set ...

Страница 814: ...displayed Set up refrigerant circuit address data again 19 Press the button to return to the 2 wire remote controller address selection screen of 2 If setting has been completed press the FAN button to return to the Menu 2 F1 item selection screen Note This item cannot be set from slave remote controllers COMPLETION OF ADDRESS SETTING MODE 20 Press and hold the FAN button for at least 2 seconds to...

Страница 815: ...R UNITS Important If the reset is not performed address can not be read in normally After all the addresses have been set the circuit breaker needs to be switched off for at least 2 minutes After the 2 minutes has passed power can be restored The set address is stored in the PCB and will remain in memory even when the power is turned off However setting address is effective after power reset Recor...

Страница 816: ... type A SW601 SW602 SW604 SW605 SW606 SW607 SW608 Check the position 0 Factory setting IU AD x10 IU AD x1 REF AD x10 REF AD x1 If any of the switches is positioned at a value other than 0 this function will not activate The layout of the switches differs depending on the type of the indoor unit Refer to 2 2 2 If multiple indoor units are connected to a single simple remote controller make sure to ...

Страница 817: ...this button is pressed the fan setting changes among Remote controller address Function number and Setting number Setting number Setting number Indoor unit address valid range 00 63 Refrigerant circuit address valid range 00 99 START STOP button Transmits address setting SET TEMP p and q button Switches the various numbers UTY RSK With operation mode Function number 01 Indoor unit address 02 Refri...

Страница 818: ...so that the Setting number display flashes Then press either the SET TEMP p button or the SET TEMP q button to set up the indoor unit address data The setting range is from 00 to 63 Ex When indoor unit address data 12 is set up Indoor unit address data 8 Pressing the START STOP button confirm the selected indoor unit address data The data will be transferred to the indoor unit ERROR When indoor un...

Страница 819: ...utton so that the Setting number display flashes Then press either the SET TEMP p button or the SET TEMP q button to set up the refrigerant circuit address data The setting range is from 00 to 99 Refrigerant circuit address data Ex When refrigerant circuit address data 18 is set up 12 Pressing the START STOP button confirm the selected refrigerant circuit address data The data will be transferred ...

Страница 820: ...it Indoor unit Indoor unit Indoor unit Repeat the procedures in steps 1 through 13 and set up the indoor units requiring address setting Simple remote controller Simple remote controller Simple remote controller RESET THE POWER AFTER SETTING UP ADDRESS OF ALL INDOOR UNITS Important If the reset is not performed address can not be read in normally After all the addresses have been set the circuit b...

Страница 821: ...each indoor unit are set at 0 factory setting Rotary switch type A SW601 SW602 SW604 SW605 SW606 SW607 SW608 Check the position 0 Factory setting IU AD x10 IU AD x1 REF AD x10 REF AD x1 If any of the switches is positioned at a value other than 0 this function will not activate The layout of the switches differs depending on the type of the indoor unit Refer to 2 2 2 When multiple indoor units are...

Страница 822: ...eaker ON SWITCHING SELECTION OF ADDRESS SETTING MODE 4 When the Function Setting on the Maintenance screen is touched the Installer Password Verification screen is displayed Enter the Installer Password and touch the OK Function Setting screen is displayed Previous Page Back Next Page Page 2 3 Maintenance Test Run R C Address Setting Function Setting I U Address Setting 002 01 00 00 Address Functi...

Страница 823: ...01 with the or 01 Function No Cancel OK When the OK is touched the display returns to the Function Setting screen 9 Touch the Setting on the Function Setting screen 002 01 01 00 Address Function No Setting No Function Setting Back Setting 10 Setting screen of Setting No is displayed Set the Setting No with the or The setting range is from 00 to 63 12 002 01 01 Function Setting Cancel OK Address Fu...

Страница 824: ...the Function No 02 with the or 02 Function No Cancel OK When the OK is touched the display returns to the Function Setting screen 16 Touch the Setting on the Function Setting screen 002 01 02 00 Address Function No Setting No Function Setting Back Setting 17 Setting screen of Setting No is displayed Set the Setting No with the or The setting range is from 00 to 99 18 002 01 02 Function Setting Can...

Страница 825: ...ired remote controller Touch panel Wired remote controller Touch panel RESET THE POWER AFTER SETTING UP ADDRESS OF ALL INDOOR UNITS Important If the reset is not performed address can not be read in normally After all the addresses have been set the circuit breaker needs to be switched off for at least 2 minutes After the 2 minutes has passed power can be restored The set address is stored in the ...

Страница 826: ...tary switch type A SW601 SW602 SW604 SW605 SW606 SW607 SW608 Check the position 0 Factory setting IU AD x10 IU AD x1 REF AD x10 REF AD x1 If any of the switches is positioned at a value other than 0 this function will not activate The layout of the switches differs depending on the type of the indoor unit Refer to 2 2 2 When multiple indoor units are connected to a single wired remote controller 2...

Страница 827: ...ain to make sure no wiring mistakes were made before turning on the power Breaker ON Indoor units Indoor units SWITCHING SELECTION OF ADDRESS SETTING MODE 4 To activate the address setting mode hold down the three buttons of MENU and ENTER at the same time for 2 seconds or longer Address setting mode initial display 5 Select the 13 in Menu 2 Settings Then press the ENTER button 07 46 FUNCTION SETT...

Страница 828: ...ssing the or button set up the indoor unit address The setting range is from 00 to 63 Ex When indoor unit address data 12 is set up Indoor unit address ERROR GOOD When indoor unit address data was not set up on the indoor unit is displayed Set up indoor unit address data again When indoor unit address data was normally set up on the indoor unit 9 Pressing the ENTER button to return to the address ...

Страница 829: ...efrigerant circuit address The setting range is from 00 to 99 Ex When refrigerant circuit address data 18 is set up Refrigerant circuit address GOOD ERROR When refrigerant circuit address data was not set up on the indoor unit is displayed Set up refrigerant circuit address data again When refrigerant circuit address data was normally set up on the indoor unit 13 Pressing the ENTER button to retur...

Страница 830: ...tting Wired remote controller RESET THE POWER AFTER SETTING UP ADDRESS OF ALL INDOOR UNITS Important If the reset is not performed address can not be read in normally After all the addresses have been set the circuit breaker needs to be switched off for at least 2 minutes After the 2 minutes has passed power can be restored The set address is stored in the PCB and will remain in memory even when t...

Страница 831: ...r units and RB units automatically be sure to always set the addresses of signal amplifiers first set the addresses of indoor units second set the addresses of RB units last AUTOMATIC ADDRESS SETTING METHOD Manual setting of Outdoor unit Please set up 1 3 Set A Set B Set C Set L and 1 8 terminal resister setting This function is available VR II series Step 1 Turn Power ON of all units Step 2 Autom...

Страница 832: ... the operation of the outdoor unit has stopped be sure to stop the operation if it is still running and turn off the power 2 Remove the front panel of the outdoor unit and remove the lid of the electrical component box in order to expose the printed circuit board 3 Turn on the power of the outdoor unit LED101 GREEN POWER MODE LED105 LED104 LED102 RED ERROR When the system is normal Off On Off Off ...

Страница 833: ...tton SW107 once LED105 LED104 LED105 LED104 2 Press the SELECT button SW108 to display F3 on the LED104 The display of the LED104 changes each time the SELECT button is pressed LED105 LED104 LED105 LED104 LED105 LED104 LED105 LED104 1 1 Monitoring mode Setting mode Function mode Error history mode 1 The F1 and F9 modes are used for maintenance so do not set them in regular 3 When F3 appears on the...

Страница 834: ...ng installed LED105 LED104 LED105 LED104 Ex When eight signal amplifiers are being connected 7 To exit automatic address setting press the ENTER button SW109 in the setting completed status shown in step 6 above LED105 LED104 LED105 LED104 Next press the MODE EXIT button SW107 to exit the Function mode LED105 LED104 LED105 LED104 07 53 FUNCTION SETTING FUNCTION SETTING ...

Страница 835: ... same time The refrigerant circuit address of an outdoor unit being connected within the same refrigerant system is set up 1 After verifying that the system is operating normally press the MODE EXIT button SW107 once LED105 LED104 LED105 LED104 2 Press the SELECT button SW108 to display F3 on the LED104 LED105 LED104 LED105 LED104 LED105 LED104 LED105 LED104 1 1 The display of the LED104 changes e...

Страница 836: ...units of which automatic address setting succeeded LED104 The number of indoor units of which automatic address setting failed Ex When 25 indoor units are connected and the automatic setting of the addresses of three indoor units failed LED105 LED104 LED105 LED104 LED105 The number of indoor units of which automatic address setting succeeded LED104 The number of indoor units of which automatic add...

Страница 837: ...circuit address of an outdoor unit being connected within the same refrigerant system is set up 1 After verifying that the system is operating normally press the MODE EXIT button SW107 once LED105 LED104 LED105 LED104 2 Press the SELECT button SW108 to display F3 on the LED104 LED105 LED104 LED105 LED104 LED105 LED104 LED105 LED104 1 1 The display of the LED104 changes each time the SELECT button ...

Страница 838: ... units of which automatic address setting succeeded LED104 The number of RB units of which automatic address setting failed Ex When 25 RB units are connected and the automatic setting of the addresses of three RB units failed LED105 LED104 LED105 LED104 LED105 The number of RB units of which automatic address setting succeeded LED104 The number of RB units of which automatic address setting failed...

Страница 839: ...amplifiers again on the master units of Refrigerant Systems 2 and 3 Step 2 Activate the Indoor Unit Automatic Address Setting function on the master unit of Refrigerant System 1 An indoor unit address and a refrigerant circuit address are automatically set up for all indoor units being connected in Refrigerant System 1 Step 3 Activate the Indoor Unit Automatic Address Setting function on the maste...

Страница 840: ...ave been assigned to individual indoor units it is necessary to perform a separate address check operation When setting addresses of signal amplifiers indoor units and RB units automatically be sure to always set the addresses of signal amplifiers first set the addresses of indoor units second set the addresses of RB units last Please be sure to finish address setting of outdoor unit and indoor un...

Страница 841: ...aster unit of Refrigerant System 1 An address is automatically assigned to all signal amplifiers on the network Caution When indoor units are being connected via different refrigerant systems never activate the Indoor Unit Automatic Address Setting function As long as master units are on the same network any master unit can set the addresses of signal amplifiers automatically Perform the automatic...

Страница 842: ...rminal resistors in a network segment Condition for 1 segment Total number of outdoor and indoor units and signal amplifiers is less than 64 or the total length of the transmission line is less than 500m How many outdoor units are connected in 1 Refrigerant system From conditions set outdoor unit DIP switch SET5 4 in accordance with the table below DIP SW SET5 4 Terminal resistor Remarks OFF Disab...

Страница 843: ...4 press the ENTER button SW109 LED105 LED104 LED105 LED104 A flashing display appears on the LED105 4 Press the SELECT button SW108 to display 12 on the LED105 LED105 LED104 LED105 LED104 5 When 12 appears on the LED105 hold down the ENTER button SW109 for at least 3 seconds Unless it is held down for at least 3 seconds the selection will not be confirmed When the Indoor Unit Connection Check func...

Страница 844: ...4 LED105 LED104 Ex Shown numbers of error are three When confirm the contents of the error push the ENTER button SW109 When there are some errors display change by push the SELECT button SW108 Number of indoor unit connection is error Volume ratio of the indoor units connection is error Overlap address of the indoor unit is error Display the address of the overlap indoor unit hold down the ENTER b...

Страница 845: ...connected 1 1 kW cooling capacity indoor unit is connected 9 0 kW or larger cooling capacity AU or AR is NOT connected 9 0 kW or larger cooling capacity AU or AR is connected J IIIL 8HP 50 to 150 10HP 12HP J III 4HP 50 to 150 5HP 6HP J II 4HP 46 to 130 46 to 120 1 46 to 110 1 5HP 50 to 130 50 to 120 1 50 to 110 1 6HP J IIS 4HP 50 to 130 50 to 117 1 50 to 110 1 5HP 6HP 1 Keep the volume ratio withi...

Страница 846: ...n of the outdoor unit has stopped be sure to stop the operation if it is still running and turn off the power 2 Remove the front panel of the outdoor unit and remove the lid of the electrical component box in order to expose the printed circuit board 3 Turn on the power of the outdoor unit LED101 GREEN POWER MODE LED105 LED104 LED102 RED ERROR When the system is normal Off On Off Off As shown in t...

Страница 847: ...he ENTER button SW109 A flashing display appears on the LED105 and the flashing display of F2 on the LED104 changes to the illuminated display of a number LED105 LED104 LED105 LED104 4 Referring to the Settings List shown below press the SELECT button SW108 and display the code number of the mode you want to set on the LED105 Ex To select switching between Batch Stop and Emergency Stop LED105 LED1...

Страница 848: ...t FUNCTION SETTING press the ENTER button SW109 in the setting completed status shown in step 5 above 2 5 seconds after even if ENTER button SW109 is not pressed LED105 changes to a flashing display automatically LED105 LED104 LED105 LED104 2 Then press the MODE EXIT button SW107 to exit FUNCTION SETTING MODE LED105 LED104 LED105 LED104 7 To set another function press the ENTER button SW109 in the...

Страница 849: ...er of outdoor units are installed and turned on at the same time to limit the starting current 0 1 21sec Delay 0 2 42sec Delay 0 3 63sec Delay 1 1 Cooling capacity shift 0 0 Normal mode l 1 0 1 Save energy mode 1 0 2 High power mode 1 0 3 High power mode 2 0 4 Prohibited 1 2 Heating capacity shift 0 0 Normal mode l 1 0 1 Save energy mode 0 2 High power mode 1 0 3 High power mode 2 1 3 Prohibited 0...

Страница 850: ... from stopping operation when they are covered by snow 0 1 Disable 2 3 Interval setting for snow falling protection fan mode 0 0 Standard 30minutes l 1 When the snow falling protection fan mode is set the operation interval of the fans of outdoor units can be selected 0 1 Short1 5minutes 0 2 Short2 10minutes 0 3 Short3 20minutes 2 4 High static pressure mode 0 0 Standard l When installing a duct t...

Страница 851: ...ted 0 0 Prohibited l Setting prohibited 0 1 Prohibited 0 2 Prohibited 3 3 Prohibited 0 0 Prohibited l Setting prohibited 0 1 Prohibited 4 0 Capacity priority setting in low noise mode 0 0 Off quiet priority l 1 If the cooling heating performance becomes insufficient when the low noise mode is set it is possible to set capacity priority that automatically cancels the low noise mode once performance...

Страница 852: ...r Slave 6 0 Recovery operation 0 0 On l 1 0 1 Off 6 1 Prohibited 0 0 On l 1 Setting prohibited 0 1 Off 6 2 Prohibited 0 0 On l 1 Setting prohibited 0 1 Off 6 3 Prohibited 0 0 On l 1 Setting prohibited 0 1 Off 1 Do not set this for outdoor units with Slave setting 07 71 FUNCTION SETTING FUNCTION SETTING ...

Страница 853: ...Setting number xx00 l Set the ones digit and tens digit of the No of the electricity meter pulse setting connected to CN135 0 1 Setting number xx01 9 8 Setting number xx98 9 9 Setting number xx99 7 3 Electricity meter pulse setting 2 3 0 0 Setting number 00xx l Set the hundreds digit and thousands digit of the electricity meter pulse setting connected to CN135 0 1 Setting number 01xx 9 8 Setting n...

Страница 854: ... starting current 0 1 21sec Delay 0 2 42sec Delay 0 3 63sec Delay 1 1 Cooling capacity shift 0 0 Normal mode l 1 0 1 Save energy mode 1 0 2 High power mode 1 0 3 High power mode 2 0 4 Prohibited 1 2 Heating capacity shift 0 0 Normal mode l 1 0 1 Save energy mode 0 2 High power mode 1 0 3 High power mode 2 1 3 Prohibited 0 0 Prohibited l Setting prohibited 0 1 Prohibited 1 7 Height difference betwe...

Страница 855: ...ven to administrative indoor unit Priority is given to the operation mode of the administrative indoor unit which is set by the wired remote controller 0 1 Priority given to external input of outdoor unit 0 2 Priority given to administrative indoor unit 2 2 Snow falling protection fan mode 0 0 Enable l 1 This mode operates the fans of outdoor units in order to prevent the units from stopping opera...

Страница 856: ...ed at 80 capacity 0 4 Level 5 operated at 100 capacity 3 2 Prohibited 0 0 Prohibited l Setting prohibited 0 1 Prohibited 0 2 Prohibited 3 3 Prohibited 0 0 Prohibited l Setting prohibited 0 1 Prohibited 4 0 Capacity priority setting in low noise mode 0 0 Off quiet priority l 1 If the cooling heating performance becomes insufficient when the low noise mode is set it is possible to set capacity prior...

Страница 857: ...or unit Remarks Master Slave 6 1 Prohibited 0 0 On l 1 Setting prohibited 0 1 Off 6 2 Prohibited 0 0 On l 1 Setting prohibited 0 1 Off 6 3 Prohibited 0 0 On l 1 Setting prohibited 0 1 Off 1 Do not set this for outdoor units with Slave setting 07 76 FUNCTION SETTING FUNCTION SETTING ...

Страница 858: ...Setting number xx00 l Set the ones digit and tens digit of the No of the electricity meter pulse setting connected to CN135 0 1 Setting number xx01 9 8 Setting number xx98 9 9 Setting number xx99 7 3 Electricity meter pulse setting 2 3 0 0 Setting number 00xx l Set the hundreds digit and thousands digit of the electricity meter pulse setting connected to CN135 0 1 Setting number 01xx 9 8 Setting n...

Страница 859: ...de 1 0 2 High power mode 1 0 3 High power mode 2 0 4 Prohibited 1 2 Heating capacity shift 0 0 Normal mode l 1 0 1 Save energy mode 0 2 High power mode 1 0 3 High power mode 2 1 3 Prohibited 0 0 Prohibited l Setting prohibited 0 1 Prohibited 2 0 Switching between batch stop or emergency stop 0 0 Batch stop l 1 This mode selects the pattern of the stop function to be operated by the external input ...

Страница 860: ...rotection fan mode 2 3 Interval setting for snow falling protection fan mode 0 0 Standard 30minutes l 1 When the snow falling protection fan mode is set the operation interval of the fans of outdoor units can be selected 0 1 Short1 5minutes 0 2 Short2 10minutes 0 3 Short3 20minutes 2 4 High static pressure mode 0 0 Standard l When installing a duct to the blow off outlet of an outdoor unit set the...

Страница 861: ... noise mode 0 1 On capacity priority 4 1 Low noise mode setting 0 0 Off Normal l 1 0 1 On Low noise mode 4 2 Low noise mode operation level setting 0 0 Level 1 55dB l 1 The noise level when operating in the low noise mode can be set 0 1 Level 2 50dB 6 0 Recovery operation 0 0 On l 1 If one of compressor fails backup operation will be performed by the remaining compressors as emergency 2 0 1 Off 1 ...

Страница 862: ...nected to CN135 0 1 Setting number xx01 9 8 Setting number xx98 9 9 Setting number xx99 7 3 Electricity meter pulse setting 2 3 0 0 Setting number 00xx l Set the hundreds digit and thousands digit of the electricity meter pulse setting connected to CN135 0 1 Setting number 01xx 9 8 Setting number 98xx 9 9 Setting number 99xx 9 0 Prohibited 0 0 Prohibited l Setting prohibited 0 1 Prohibited 0 2 Pro...

Страница 863: ...High power mode 2 1 3 Prohibited 0 0 Prohibited l Setting prohibited 0 1 Prohibited 1 4 Prohibited 0 0 Prohibited l Setting prohibited 0 1 Prohibited 0 2 Prohibited 0 3 Prohibited 0 4 Prohibited 2 0 Switching between batch stop or emergency stop 0 0 Batch stop l This mode selects the pattern of the stop function to be operated by the external input terminal CN134 Batch stop The stop of all indoor ...

Страница 864: ...e wired remote controller 0 1 Priority given to external input of outdoor unit 0 2 Priority given to administrative indoor unit 2 2 Prohibited 0 0 Prohibited l Setting prohibited 0 1 Prohibited 2 3 Prohibited 0 0 Prohibited l Setting prohibited 0 1 Prohibited 0 2 Prohibited 0 3 Prohibited 2 4 Prohibited 0 0 Prohibited l Setting prohibited 0 1 Prohibited 0 2 Prohibited 0 3 Prohibited 2 5 Prohibited...

Страница 865: ... 0 0 Prohibited l Setting prohibited 0 1 Prohibited 4 0 Capacity priority setting in low noise mode 0 0 Off quiet priority l If the cooling heating performance becomes insufficient when the low noise mode is set it is possible to set capacity priority that automatically cancels the low noise mode once performance is restored the mode will automatically return to the low noise mode 0 1 On capacity ...

Страница 866: ...35 0 1 Setting number xx01 9 8 Setting number xx98 9 9 Setting number xx99 7 3 Electricity meter pulse setting 2 2 0 0 Setting number 00xx l Set the hundreds digit and thousands digit of the electricity meter pulse setting connected to CN135 0 1 Setting number 01xx 9 8 Setting number 98xx 9 9 Setting number 99xx 9 0 Prohibited 0 0 Prohibited l Setting prohibited 0 1 Prohibited 0 2 Prohibited 0 3 P...

Страница 867: ...Prohibited 0 0 Prohibited l Setting prohibited 0 1 Prohibited 0 2 Prohibited 0 3 Prohibited 1 1 Cooling capacity shift 0 0 Normal mode l 0 1 Save energy mode 1 0 2 High power mode 1 0 3 High power mode 2 0 4 Prohibited 1 2 Heating capacity shift 0 0 Normal mode l 0 1 Save energy mode 0 2 High power mode 1 0 3 High power mode 2 1 3 Prohibited 0 0 Prohibited l Setting prohibited 0 1 Prohibited 07 86...

Страница 868: ...ohibited 0 2 Prohibited 0 3 Prohibited 0 4 Prohibited 1 7 Height difference between indoor units 0 0 Standard l If installing the indoor units even only one set to a lower floor than the outdoor unit and the height difference between the indoor units is 3m or greater i e if installing the indoor units on separate floors set 02 height difference 0 1 Prohibited 0 2 Height difference 0 3 Prohibited 0...

Страница 869: ... the first command l Select the priority setting of the operation mode Priority given to the first command Priority is given to the operation mode which is set first Priority given to external input of outdoor unit Priority is given to the operation mode which is set by the external input terminal CN132 Priority given to administrative indoor unit Priority is given to the operation mode of the adm...

Страница 870: ...g heating performance will also drop 0 1 Level 2 0 2 Level 3 0 3 Level 4 0 4 Level 5 3 1 Prohibited 0 0 Prohibited l Setting prohibited 0 1 Prohibited 4 0 Capacity priority setting in low noise mode 0 0 Off quiet priority l If the cooling heating performance becomes insufficient when the low noise mode is set it is possible to set capacity priority that automatically cancels the low noise mode onc...

Страница 871: ...35 0 1 Setting number xx01 9 8 Setting number xx98 9 9 Setting number xx99 7 3 Electricity meter pulse setting 2 2 0 0 Setting number 00xx l Set the hundreds digit and thousands digit of the electricity meter pulse setting connected to CN135 0 1 Setting number 01xx 9 8 Setting number 98xx 9 9 Setting number 99xx 9 0 Prohibited 0 0 Prohibited l Setting prohibited 0 1 Prohibited 0 2 Prohibited 0 3 P...

Страница 872: ...4 30 Type 3 Wall mounted AS A04 07 09 12 14 AS E04 07 09 12 14 Type 4 Circular flow AUXM018 024 030 AUXK018 024 030 034 036 045 054 Type 5 Wall mounted AS A004 007 009 AS E004 007 009 Type 6 Wall mounted AS A030 034 Type 7 Compact floor AG A004 007 009 012 014 AG E004 007 009 012 014 z zType 1 SET1 SET2 DIP switch type A SW1 Main PCB DIP switch type B Rotary switch type C Rotary switch type D DIP ...

Страница 873: ...W602 SW604 SW605 SW606 SW607 SW608 SW PCB SET1 SET2 DIP switch type A SW1 Main PCB DIP switch type B z zType 3 SET2 SET1 SET3 SET4 DIP switch type A DIP switch type A Rotary switch type C Rotary switch type D SW1 Main PCB DIP switch type B 07 92 FUNCTION SETTING FUNCTION SETTING ...

Страница 874: ... DIP switch type A Main PCB DIP switch type A Rotary switch type C Rotary switch type C DIP switch type A SET2 SET1 DIP switch type A DIP switch type A Rotary switch type C SET2 SET1 DIP switch type A 07 93 FUNCTION SETTING FUNCTION SETTING ...

Страница 875: ...SWITCH TYPE DIP switch type A ON DIP switch type B 2WIRE 3WIRE Rotary switch type C Rotary switch type D Rotary switch type C DIP switch type A SET1 SET2 DIP switch type A 07 94 FUNCTION SETTING FUNCTION SETTING ...

Страница 876: ... switch 1 2 Wireless remote controller custom code switch 2 3 Prohibited 4 Prohibited SET4 1 Drainage function switch Slim Duct type only 2 Auto louver grille setting switch Mini duct type and Slim duct type only 3 Prohibited 4 Prohibited type B SW1 Remote controller wire type switch Rotary SW type C IU AD x 1 Indoor unit address switch 1 IU AD x 10 Indoor unit address switch 2 REF AD x1 Refrigera...

Страница 877: ...F 2 2kW ON OFF OFF OFF OFF 2 8kW OFF ON OFF OFF OFF 3 6kW ON ON OFF OFF OFF 4 0kW OFF OFF ON OFF OFF 4 5kW ON OFF ON OFF OFF 5 6kW OFF ON ON OFF OFF 7 1kW ON ON ON OFF OFF 8 0kW OFF OFF OFF ON OFF 9 0kW OFF ON ON OFF ON 10 0kW ON OFF OFF ON OFF 11 2kW OFF ON OFF ON OFF 12 5kW ON ON OFF ON OFF 14 0kW OFF OFF ON ON OFF 18 0kW ON OFF ON ON OFF 22 4kW OFF ON ON ON OFF 25 0kW 07 96 FUNCTION SETTING FUN...

Страница 878: ...e stop of cooling fan when the air conditioner is stopped When auxiliary heater is connected please turn ON this switch When you connect auxiliary heater be careful enough u Factory setting SET2 3 Fan delay u OFF Disable ON Enable SET2 4 setting prohibited u Factory setting SET2 4 u OFF Fixed at OFF ON Setting prohibited 07 97 FUNCTION SETTING FUNCTION SETTING ...

Страница 879: ...e sure to also switch the code setting on the paired wireless remote controller side at the same time u Factory setting SET3 1 SET3 2 Custom code u OFF OFF Type A ON OFF Type B OFF ON Type C ON ON Type D 1 3 2 How to switch the code on the wireless remote controller side 1 Press the MODE button for more than five seconds to start the code change 2 Press the SET TEMP p or q button to select the des...

Страница 880: ...t while changing setting Auto louver grille setting switch Mini duct type and Slim duct type only When Auto louver grille kit optional parts is attached set the Auto louver grille setting Enable u Factory setting SET4 2 Auto louver grille setting u OFF Disable ON Enable SET4 3 setting prohibited u Factory setting SET4 3 u OFF Fixed at OFF ON Setting prohibited SET4 4 setting prohibited u Factory s...

Страница 881: ... address Switch 1 Indoor unit address the first digit IU AD x 10 Indoor unit address Switch 2 Indoor unit address the second digit z zREF AD setting Refrigerant circuit address switch Sets the refrigerant circuit address Please see 1 3 address setting for refrigerant circuit address conversion table REFRIGERANT CIRCUIT ADDRESS SWITCH Factory setting REF AD x 1 0 REF AD x 10 0 Rotary SW Description...

Страница 882: ...number remote controller address in the remote controller group is set 3 wire type Only for manual address setting Set the remote controller address in the 0 1 2 15 order Blank is not allowed REMOTE CONTROLLER ADDRESS SWITCH Factory setting 0 Rotary SW Description Remarks RC AD Remote controller address Remote controller address 07 101 FUNCTION SETTING FUNCTION SETTING ...

Страница 883: ...ller The settings may be selected between the following two Function Number or Setting Number Settings will not be changed if invalid numbers or setting numbers are selected PREPARATION 1 Turn on the power to the indoor unit By turning on the power indoor units initializes EEV so make sure the piping air tight test and vacuuming have been conducted before turning on the power Also check again to m...

Страница 884: ...error will be displayed by continuously pressing the MANUAL AUTO for 10 sec or more In this case release the button or turn off the power An explanation of the displayed information as shown below SELECTION AND CONFIRMATION OF CUSTOM CODE 4 Press the SET TEMP p or SET TEMP q buttons to select the custom code that matches the setting with the indoor unit By selecting the appropriate custom code the...

Страница 885: ...es and decreases the displayed number Start the function setting mode Changes the display digits Transmits function setting Reconfirmation of function setting Confirmation of function setting Indication of function number the ten s place Indication of function number the one s place Indication of setting number 0 9 Long press Switches between the function setting mode and 3 sec more the function s...

Страница 886: ...ill be heard if the command is accepted Pi Pi Pi PiPiPi In the following cases the setting signal is not read and a buzzer sounds The function setting No is set out of range Pi Pi Pi Pi Pi Case1 When setting number is one digit 11 1 Indoor unit will display the function setting number on OPERATION GREEN TIMER ORANGE and FILTER RED light OPERATION GREEN TIMER ORANGE Flashing times of function numbe...

Страница 887: ... numbers the ten s place Example Function number 26 Setting number 31 OPERATION LAMP GREEN TIMER LAMP ORANGE FILTER LAMP RED 0 5sec ON 0 5sec OFF 0 5sec ON 0 5sec OFF OFF OFF 1 time 3 times 2 times 6 times Phase1 12sec Phase2 12sec 0 5sec ON 0 5sec OFF 0 5sec ON 0 5sec OFF Phase1 The display of Phase1 and Phase2 is alternately repeated Phase2 Number 0 setting will not indicate TIMER LAMP and FILTE...

Страница 888: ...e FAN and the SET TEMP p buttons Whilst holding these 2 buttons press the RESET button SET TEMP RESET FAN Function setting mode display 16 Function number to be confirmed is displayed Refer to 7 Press the TIMER set button TIMER set Case1 When setting number is one digit Case2 When setting number is two digits Example Function number 26 Setting number 31 OPERATION LAMP GREEN TIMER LAMP ORANGE FILTE...

Страница 889: ...and will remain in memory even when the power is turned off However setting function is effective after power reset Record the function set in the indoor unit on a label etc and affix the label to the unit so it can be used for after sales service operations Number 0 setting will not indicate TIMER LAMP and FILTER LAMP Once the RESET button is pressed on the remote controller the OPERATION MODE wi...

Страница 890: ...t be used on the slave units PREPARATION 1 If multiple indoor units are connected to a single wired remote controller make sure to manually set up the remote controller address RC AD on the PCBs of the indoor units Refer to 1 3 Ex When four indoor units are connected 0 1 2 3 Indoor unit Indoor unit Indoor unit Indoor unit RC AD RC AD RC AD RC AD Wired remote controller 2 Turn on the power to the i...

Страница 891: ...indoor unit reject the any operation command from remote controller Function number Refer to FUNCTION DETAILS Remote controller address Remote controller address setting number 00 15 SET BACK button Switches the remote controller address setting number SET TIME and button Switches the function number Setting number Refer to FUNCTION DETAILS SET TEMP V and Λ button Switches the setting number TIMER...

Страница 892: ...o select the setting number The display flashes during setting number selection Ex Function number 30 Setting number 01 Setting number 7 Pressing the TIMER SET button confirm the setting The data will be transferred to the indoor unit ERROR When the data was not set up on the indoor unit is displayed Set up the data again according to the procedure in step 5 6 above GOOD When the data was normally...

Страница 893: ...or unit Indoor unit Repeat the procedures in steps 1 through 8 and set up the indoor units requiring function setting Wired remote controller Wired remote controller Wired remote controller RESET THE POWER AFTER SETTING UP FUNCTION OF ALL INDOOR UNITS Important If the reset is not performed function can not be read in normally After all the functions have been set the circuit breaker needs to be s...

Страница 894: ... 1 When setting of Remote controller address in Automatic address setting 0 0 0 0 Indoor unit Indoor unit Indoor unit Indoor unit RC AD RC AD RC AD RC AD Simple remote controller 1 2 When setting of Remote controller address in Manual address setting make sure to manually set up the remote controller address RC AD on the PCBs of the indoor units and Wired remote controller Refer to 1 3 1 2 3 4 Ind...

Страница 895: ...en is displayed 5 Press the SET TEMP or SET TEMP button to select F1 Menu 2 F1 settings mode or F2 Menu 2 F2 settings mode F1 Initial settings mode F2 Maintenance settings mode 6 Press the button Setting item selection screen is displayed Item No is displayed 7 Select the item number to be set with the SET TEMP or SET TEMP button and press the button to switch to thesetting screen 8 Select the 13 ...

Страница 896: ...tion setting Refer to the indoor unit installation manual for details on the function numbers and setting numbers 9 Select the 2 wire remote controller address with the SET TEMP or SET TEMP button Then press the button Select all Select the 2 wire remote controller address Ex Select the 002 03 10 Set the function number with the SET TEMP or SET TEMP button Then press the button Function number 11 ...

Страница 897: ...it Indoor unit Indoor unit Indoor unit Indoor unit Repeat the procedures in steps 1 through 8 and set up the indoor units requiring function setting Simple remote controller Simple remote controller Simple remote controller RESET THE POWER AFTER SETTING UP FUNCTION OF ALL INDOOR UNITS Important If the reset is not performed function can not be read in normally After all the functions have been set...

Страница 898: ...annot be used on the slave units PREPARATION 1 If multiple indoor units are connected to a single simple remote controller make sure to manually set up the remote controller address RC AD on the PCBs of the indoor units Refer to 1 3 Ex When four indoor units are connected 0 1 2 3 Indoor unit Indoor unit Indoor unit Indoor unit RC AD RC AD RC AD RC AD Wired remote controller 2 Turn on the power to ...

Страница 899: ...an setting changes among Remote controller address Function number and Setting number Setting number Refer to FUNCTION DETAILS START STOP button Transmits function setting SET TEMP p and q button Switches the various numbers UTY RSK With operation mode Function number Refer to FUNCTION DETAILS Remote controller address Remote controller address setting number 00 15 FAN button Each time this button...

Страница 900: ...mber 6 Press the FAN button so that the Setting number display flashes Then press either the SET TEMP p button or the SET TEMP q button to set up the setting number Ex Function number 30 Setting number 01 Setting number 7 Pressing the START STOP button confirm the setting The data will be transferred to the indoor unit ERROR When the data was normally set up on the indoor unit When the data was no...

Страница 901: ...ndoor unit Indoor unit Indoor unit Repeat the procedures in steps 1 through 8 and set up the indoor units requiring function setting Simple remote controller Simple remote controller Simple remote controller RESET THE POWER AFTER SETTING UP FUNCTION OF ALL INDOOR UNITS Important If the reset is not performed function can not be read in normally After all the functions have been set the circuit bre...

Страница 902: ...mote controller address in Automatic address setting 0 0 0 0 Indoor unit Indoor unit Indoor unit Indoor unit RC AD RC AD RC AD RC AD Wired remote controller Touch panel 1 2 When setting of Remote controller address in Manual address setting make sure to manually set up the remote controller address RC AD on the PCBs of the indoor units and Wired remote controller Touch panel Refer to 1 3 1 2 3 4 I...

Страница 903: ...ess on the Function Setting screen 002 01 00 00 Address Function No Setting No Function Setting Back Setting 5 Address screen is displayed Select the address of the indoor unit whose function number is to be set by touching or When setting at all the indoor units touch All 002 01 Address Cancel OK All When the OK is touched the display returns to the Function Setting screen 6 Touch the Function No...

Страница 904: ...1 When the OK is touched the Function Setting verification screen is displayed 10 Touch the YES of the verification screen No Yes Function Setting Function setting will be performed OK In case of OK 002 01 30 01 Address Function No Setting No Function Setting Back Setting When the data was normally set up on the indoor unit In case of ERROR 002 01 30 Address Function No Setting No Function Setting...

Страница 905: ...red remote controller Touch panel Wired remote controller Touch panel RESET THE POWER AFTER SETTING UP ADDRESS OF ALL INDOOR UNITS Important If the reset is not performed address can not be read in normally After all the addresses have been set the circuit breaker needs to be switched off for at least 2 minutes After the 2 minutes has passed power can be restored The set address is stored in the P...

Страница 906: ...When setting of Remote controller address in Automatic address setting 0 0 0 0 Indoor unit Indoor unit Indoor unit Indoor unit RC AD RC AD RC AD RC AD Wired remote controller 1 2 When setting of Remote controller address in Manual address setting make sure to manually set up the remote controller address RC AD on the PCBs of the indoor units and Wired remote controller Refer to 1 3 1 2 3 4 Indoor ...

Страница 907: ...ate the address setting mode hold down the three buttons of MENU and ENTER at the same time for 2 seconds or longer Address setting mode initial display 4 Select the 13 in Menu 2 Settings Then press the ENTER button 07 126 FUNCTION SETTING FUNCTION SETTING ...

Страница 908: ...g the or button to select the setting number Then press the ENTER button Ex Function number 30 Setting number 01 Setting number GOOD ERROR When the data was not set up on the indoor unit is displayed Set up the data again When the data was normally set up on the indoor unit 8 Pressing the ENTER button to return to the address selection screen If setting has been completed pressing the MENU button ...

Страница 909: ...ting Wired remote controller RESET THE POWER AFTER SETTING UP ADDRESS OF ALL INDOOR UNITS Important If the reset is not performed address can not be read in normally After all the addresses have been set the circuit breaker needs to be switched off for at least 2 minutes After the 2 minutes has passed power can be restored The set address is stored in the PCB and will remain in memory even when th...

Страница 910: ...4GALH SP mode 00 to 05 0 to 50 Pa ARXA24GBLH SP mode 00 to 14 40Pa ARXA30GBLH 50Pa ARXA36GBLH SP mode 00 to 12 ARXA45GBLH SP mode 00 to 11 60Pa ARXC36GBTH SP mode 02 to 16 100Pa ARXC72GBTH SP mode 04 to 27 150Pa ARXC90GBTH SP mode 05 to 24 ARXC96GATH SP mode 05 to 29 ARXN18GATH SP mode 05 to 10 50Pa ARXN24GATH SP mode 05 to 15 ARXN30GATH SP mode 05 to 25 ARXN34GATH ARXN36GATH 60Pa ARXN45GATH ARXN0...

Страница 911: ...sed upon Central remote controller or individual controller set Once indoor unit received signal from External controller Indoor unit changed Fan mode forcibly When set 01 Indoor unit is continued operation based upon Central remote controller or individual controller set Once indoor unit received signal from External controller Indoor unit stop forcibly Connection of the wired remote controller 2...

Страница 912: ...ION SET1 SET2 RB AD X1 RB AD X10 REF AD X1 REF AD X10 DIP switch type A DIP switch type B Rotary switch type C SWITCH TYPE DIP switch type B ON DIP switch type A ON Rotary switch type C 07 131 FUNCTION SETTING FUNCTION SETTING ...

Страница 913: ...rohibited u Factory setting SET1 1 SET1 2 SET1 3 u OFF OFF OFF Fixed at OFF ON ON ON Setting prohibited z zSET2 setting Operation mode selecting switch u Factory setting SET2 1 SET2 2 Description Remarks u OFF OFF Priority given to the first command Priority is given to the operation mode which is set first ON OFF Priority given to external input of RB unit Priority is given to the operation mode ...

Страница 914: ... for RB unit address conversion table RB UNIT ADDRESS SWITCH Factory setting RB AD x 1 0 RB AD x 10 0 Rotary SW Description Remarks RB AD x 1 RB unit address Switch 1 RB unit address the first digit RB AD x 10 RB unit address Switch 2 RB unit address the second digit z zREF AD setting Refrigerant circuit address switch Sets the refrigerant circuit address Please see 1 3 address setting for refrige...

Страница 915: ...te controller only Do not use DIP Switch 2 Wired remote controller SWITCH POSITION z zWired remote controller Model UTY RNKÝ 1 2 3 4 5 6 Front case back side DIP Switch 2 All switches fixed at OFF DIP Switch 1 ON ON OFF z zSimple remote controller Model UTY RSKÝ Model UTY RHKÝ 1 2 3 4 5 6 1 2 3 4 5 6 DIP Switch 1 DIP Switch 1 ON OFF ON OFF 07 134 FUNCTION SETTING FUNCTION SETTING ...

Страница 916: ...ctory setting SW4 u OFF Fixed at OFF ON Setting prohibited z zSW5 setting prohibited u Factory setting SW5 u OFF Fixed at OFF ON Setting prohibited z zSW6 setting Memory backup setting Wired remote controller only Set to ON to use batteries for the memory backup If batteries are not used all of settings stored in memory will be delete if there is a power failure u Factory setting SW6 Memory backup...

Страница 917: ...witch ON OFF ON DIP SWITCH SETTING z zSW1 setting Memory backup setting If there is a power failure when the memory backup is enabled the setting stored in the memory will be saved u Factory setting SW1 Memory backup u OFF Disable ON Enable z zSW2 setting prohibited u Factory setting SW2 u OFF Fixed at OFF ON Setting prohibited 07 136 FUNCTION SETTING FUNCTION SETTING ...

Страница 918: ...g Press the set time buttons to set the Group remote controller address Reverse Advance Check that it is Group remote controller address Press the ENTER button Check the and flash for two seconds Hold down again the set time buttons and simultaneously for two seconds or more to complete setting 07 137 FUNCTION SETTING FUNCTION SETTING ...

Страница 919: ... 16 Touch Panel Controller can be installed to 1 system When installing two or more Touch Panel Controller set up so that Address No does not overlap Please refer to the OPERATING MANUAL of Touch Panel Controller for details Please keep Address No of Touch Panel Controller from overlapping the controller Central Remote Controller Network Convertor for LonWorks Modbus convertor and Network Converto...

Страница 920: ...lete Note Address No can be set between 00 and 15 Up to maximum 16 Central Remote Controller can be installed to 1 system When installing two or more Central Remote Controller set up so that Address No does not overlap Please refer to the OPERATING MANUAL of Central Remote Controller for details Please keep Address No of Central Remote Controller from overlapping the controller Touch Panel Control...

Страница 921: ... Address Setting screen 001 01 R C Address Setting Current Address Back Manual Addressing Address Reset 2 Manual Addressing screen is displayed Set the address with or 01 001 Manual Addressing Cancel OK System Unit When the OK is touched a verification screen is displayed 3 When the Yes on the verification screen is touched a message screen is displayed No Yes Manual Addressing Manual address sett...

Страница 922: ...reen is displayed When the Yes is touched a verification screen is displayed No Yes R C Address Setting The address will be returned to factory setting OK 3 When the Close on the message screen is touched the display returns to the R C Address Setting screen Turn on the power again Setting is reflected after the power is turned on again R C Address Setting Close 07 141 FUNCTION SETTING FUNCTION SE...

Страница 923: ...ing screen is displayed Select the Master or Slave R C Master Slave Setting Cancel OK Master Slave When the OK is touched the display returns to the Initial Setting screen Note Please set only one Master remote controller Units other than Master are set to Slave automatically Do not perform RC Mater Slave Setting during setting or operating from the Master unit 07 142 FUNCTION SETTING FUNCTION SET...

Страница 924: ...l stop verification mode starts No Yes I U Address Verification Indoor unit position will be checked OK 5 When indoor unit position verification ends a screen displaying the indoor units in a list is displayed When the screen has multiple pages they can be switched by touching the Next Page or Previous Page 1 002 1 01 01 2 002 2 01 02 3 002 3 01 03 End Next Page Page 1 2 I U Address Verification N...

Страница 925: ... button 2 The address of this unit is displayed on the screen Set the Unit Number with the or buttons System Number cannot be changed is displayed Address automatically Remote controller address allocated Not displayed Address manually allocated 01 to 32 Press the ENTER button to return to the Menu 2 item selection screen Note Perform manual address setting only when setting the address with an ar...

Страница 926: ...elect 1 Reset with the or buttons If not resetting press the MENU button to return to the Menu 2 item selection screen is displayed Address automatically allocated Not displayed Address manually allocated Not reset Reset Press the ENTER button to return to the Menu 2 item selection screen 07 145 FUNCTION SETTING FUNCTION SETTING ...

Страница 927: ...s at initial booting display Monitor mode screen If there s 0 or more than 2 Master units the number will be displayed If Master is 0 press the ENTER button to return to the Menu 2 item selection screen If Master is more than 2 press the ENTER button to return to the screen of 2 If Master is 0 or more than 2 press the MENU button to return to the Menu 2 item selection screen Number of Master units...

Страница 928: ...ote controller address of the remote controller group Indoor units displayed can be switched by or button a Refrigerant circuit address 00 to 99 b Indoor Unit address 00 to 63 c System Number 002 Indoor unit d Remote controller address 01 to 32 3 Press the MENU button to return to the Menu 2 item selection screen a b c d 07 147 FUNCTION SETTING FUNCTION SETTING ...

Страница 929: ...e controller address system number and unit number Set the unit number with the SET TEMP or SET TEMP button System number cannot be changed System number Address automatically allocated Unit number Press the button to return to the Menu 2 F1 item selection screen Note Only set addresses manually when using different numbers for addresses A remote controller address for the indoor unit needs to be ...

Страница 930: ...he 2 wire remote controller address select 1 Reset with the SET TEMP or SET TEMP button If not resetting select 0 Not reset with the SET TEMP or SET TEMP button 0 Not reset 1 Reset Address automatically allocated Press the button to return to the Menu 2 F1 item selection screen 07 149 FUNCTION SETTING FUNCTION SETTING ...

Страница 931: ...settings at initial booting display Monitor mode screen If there s 0 or more than 2 Master units the number will be displayed If Master is 0 press the button to return to the Menu 2 F1 item selection screen If Master is more than 2 press the button to return to the screen of 2 To suspend the settings part way through press the FAN button Return to the Menu 2 F1 item selection screen Number of Mast...

Страница 932: ...isplayed can be switched by the SET TEMP or SET TEMP button If an indoor unit other than VRF is connected is displayed a b 2 2 Press the button to display the Refrigerant system address and Indoor unit address a System number 002 Indoor unit b Unit number 01 to 32 c Refrigerant system address 00 to 99 d Indoor unit address 00 to 63 c d 3 Press the FAN button to return to the Menu 2 F2 item selecti...

Страница 933: ...it ad dress number of outdoor unit and indoor unit does not overlap And the sum total of the Refrigerant circuit address of Network convertor for Single split AC and the Refrigerant circuit address of the outdoor unit and the indoor unit is a maximum of 100 TERMINAL RESISTER SETTING SET 2 Set to ON when there is no termination resistance in the segment separated by the signal amplifier Default OFF...

Страница 934: ...Central remote controller Network convertor for Group remote controller and Network convertor for LONWORKS must not be same REFRIGERANT CIRCUIT ADDRESS SETTING For Split system z zExample Refrigerant circuit address SW setting Rotary SW110 10 digit Rotary SW111 1 digit 01 0 1 99 9 9 Setting range 00 99 Arbitrary numbers can be set When connecting the Network convertor for Single split AC set up th...

Страница 935: ...he factory D19 Example 1 When A1 is set Example 2 When A12 is set 4 Press SW3 the mode button to select the address The displayed address changes as follows each SW3 button is pressed When the manual setting is selected the indicators change as follows A1 A2 A8 A3 A7 A4 A6 A5 Filter mode OFF A30 A27 A28 A25 A26 A29 A1 A56 Filter mode ON D19 Ex Address No 5 is selected Press the SW3 when A9 A16 or ...

Страница 936: ...on or press SW7 the reset button to exit the address setting mode and return to the normal mode If an address setting error occurs 26 is displayed on the D19 indicator the address will not be set Perform address setting again Normal mode D19 Address setting error D19 07 155 FUNCTION SETTING FUNCTION SETTING ...

Страница 937: ...to 16 or more KNX convertor Remote Controller Address setting is 15 The sum total of the Touch panel controller Central remote controller Network convertor for Group remote controller Network convertor for LONWORKS Modbus convertor and KNX convertor is a maximum of 16 Address of the Touch panel controller Central remote controller Network convertor for Group remote controller Network convertor for...

Страница 938: ...ets Default Programming Button Prog Button Used for communication with the ETS of tool for KNX ETS is a software which runs on Windows platform based computers Push to toggle between the modes Runtime mode Default Programming mode PROG LED off PROG LED on CONFIGURATION AND SETUP This is a fully compatible KNX device which must be configured and setup using standard KNX tool ETS For how to configur...

Страница 939: ...oggle between the modes Runtime mode Default Programming mode PROG LED off PROG LED on CONFIGURATION AND SETUP This is a fully compatible KNX device which must be configured and setup using standard KNX tool ETS For how to configure the settings from the ETS refer to the Interface Specification ETS database for this device can be downloaded from http fujitsu general com global support downloads sp...

Страница 940: ...the Rotary switch is set to 16 or more Modbus convertor Remote Controller Address setting is 15 The sum total of the Touch panel controller Central remote controller Network convertor for Group remote controller Network convertor for LONWORKS and Modbus convertor is a maximum of 16 Address of the Touch panel controller Central remote controller Network convertor for Group remote controller Network...

Страница 941: ...n be set Refer to Installation Manual MODBUS COMMUNICATION BAUD RATE SETTING SET 6 4 ON 19200bps OFF 9600bps Default MODBUS COMMUNICATION PARITY SETTING SET 6 3 ON odd OFF even Default When the STOP bit setting is 2bit parity is set to None regardless of the setting of this switch MODBUS COMMUNICATION STOP BIT SETTING SET 6 2 Stop bit can be set 1 bit or 2 bit ON 2bit OFF 1bit Default MODBUS TERMI...

Страница 942: ...T 6 3 ON odd OFF even Default When the STOP bit setting is 2bit parity is set to None regardless of the setting of this switch MODBUS COMMUNICATION STOP BIT SETTING SET 6 2 Stop bit can be set 1 bit or 2 bit ON 2bit OFF 1bit Default MODBUS TERMINAL RESISTER SETTING SET 7 4 Modbus communication terminal resistance can be set Enable or disable Terminal resistance 120Ω In case of circuit terminal res...

Страница 943: ...bove mentioned way 3 Press SW3 mode button to set special mode 2 Special mode 2 is the address setting mode 4 Press SW4 set button Present address is displayed Ex Address No 15 is factory setting 5 Press SW3 mode button to select the address The displayed address changes as follows each time the mode button is pressed A01 A02 A00 A15 Ex Address No 3 is selected 6 Press SW4 set button to set the se...

Страница 944: ... 6 1 2 PURPLE PINK lBLUE mRED nWHITE oBLACK Factory setting Standard static pressure B 0 25 Pa 1 2 3 4 5 1 2 BLUE PURPLE lPINK mWHITE nBLACK Accessories Low static pressure z zLayout of control box CN110 Change this wire TYPE A to TYPE B WIRE FAN MOTOR Be sure to connect the wire with connector If connection is improper it will not operate properly Note Setting of static pressure must be fall with...

Страница 945: ...nd FUNCTION DETAILS in 2 3 INDOOR UNIT setting by wireless remote controller Wired remote controller Air flow is set by function number 26 static pressure Refer to BUTTON NANE AND FUNCTION FUNCTION SETTING and FUNCTION DETAILS in 2 4 INDOOR UNIT setting by wired remote controller Simple remote controller Air flow is set by function number 26 static pressure Refer to BUTTON NANE AND FUNCTION FUNCTI...

Страница 946: ...mote controller When the master wired remote controller setting is not performed mode cool heat selection priority goes to wired remote controller which executed first EXAMPLE z zExample 1 OK Group connection RB group RB unit Set to master WRC z zExample 2 Prohibited When indoor units which connected to different RB units are operated by one wired remote controller administrative indoor unit setti...

Страница 947: ...a verification screen is displayed Master Indoor Unit Setting Back Set Master Indoor Unit Setting Not Master Indoor Unit 3 When the Yes is touched after the data is transmitted to the indoor unit the display returns to the Master Indoor Unit Setting screen No Yes Master Indoor Unit Setting The connected indoor unit will be set as the master indoor unit OK 4 When the Back on the Master Indoor Unit ...

Страница 948: ...fter selecting Priority on Administrative Indoor Unit in setting of priority mode of outdoor unit Another indoor unit was set to Administrative Indoor Unit already Release the setting Administrative Indoor Unit of another indoor unit Operation Lock Display 2 Press the MODE button Display 1 b when setting and display 1 a when releasing The display blinks when the MODE button is pressed and the disp...

Страница 949: ...ler address No RB unit 1 3 2 Set to master WRC Note In remote controller group the cool heat mode is changed over according to a detected room temperature of an indoor unit with the smallest remote controller address number 07 168 FUNCTION SETTING FUNCTION SETTING ...

Страница 950: ... referenced In addition the data of an arbitrary 2 periods can be displayed for comparison z zIndoor unit rotation operation function Reduces the power consumption by rotating the indoor units which are set to forced thermostat OFF Operating the air conditioner even in the spring and autumn when the heat load is comparatively light may have an energy saving effect Because it is an intermittent ope...

Страница 951: ... especially in the summer winter and other times when the heat load is high In addition because the upper limit capacity of the outdoor unit is limited directly it is a control which easily exhibits an energy saving effect compared to rotation control However because the outdoor unit does not operate above the limited capacity there may be a loss of comfort depending on the indoor heat load The op...

Страница 952: ...ctual power consumption Step 1 Step 2 Step 3 Group A Group B Group C Group D Group A Group B Group C Group D Group A Group B Group C Group D Group A Group B Group C Group D ON ON ON OFF Step 1 Set temperature shift Step 2 Thermostat OFF Step 3 Outdoor unit stop Normal Indoor units outside the scope of energy saving control Specifies the maximum average electric power kW for the entire air conditio...

Страница 953: ...pply system Deciding the electricity meter installation sites number and the outdoor units which are connected Deciding the appropriate VT CT specifications Electrical Wiring Installation Restriction of Electricity Meter Electricity Meter System 3 Procuring the electricity meters and related hardware and materials Electrical Wiring 4 Electricity meters and related hardware and materials installati...

Страница 954: ...e control Control target value Outdoor unit capacity upper limit rate Reduced by peak cut control Control target value Target average power kW Electric charge power consumption Basic charge Usage charge Demand charge Basic charge Charge billed according to contract with the electric power company Includes meter reading cost and billing cost Usage charge Charge billed according the power consumed D...

Страница 955: ...l become ineffective if the outdoor unit is performing a protective operation oil recovery and defrosting As a result the electric power consumed may exceed the target electric power 3 Relationship between unit protection and energy saving function For VRF there are operations and restrictions for protecting units The energy saving function operates within the range of these protective operations ...

Страница 956: ...nts trouble may occur 1 Forced thermostat OFF outdoor unit forced OFF and outdoor unit capacity save System Controller BACnet GATEWAY Energy saving control prohibited Energy saving control operating Energy saving control prohibited Network Convertor for LonWorks 2 Electricity meter installation Among energy saving control there are functions which require installation of an electricity meter Power...

Страница 957: ...ally electricity charge apportionment calculation can be performed at any time Because an actual System Controller calculate power charge apportionment data in one day units electricity charge apportionment calculation can be performed at an arbitrary day in one day units Example 1 When the tenants of a tenant building etc are billed for their air conditioning electricity charge once a month if th...

Страница 958: ...y VT PT ratio Normally unnecessary for the voltage value level used by outdoor units and indoor units CT Current Transformer Transform the power line current value to a current measurable by an electricity meter Transformation ratio is indicated by CT ratio There are types which is inserted between power cables and types which are coupled to the power cables Pulse unit Pulse unit indicates the rel...

Страница 959: ...ss pulses are possible Line length restriction 150m or less Between Electricity meter to Outdoor unit Wiring specifications Control and instrumentation cable CVV S Control use Vinyl insulated Vinyl sheathed cable Shielding 2 2 conductor 1 25mm2 Line length restriction 25m or less Between Electricity meter to Touch panel controller Wiring specifications 2 core twisted pair 0 33mm2 22AWG 3 1 Pulse s...

Страница 960: ... air conditioner Refrigerant system 1 Heat Pump type Refrigerant system 1 Example of installation for indoor units and outdoor units SBK SBK SBK SBK SBK SBK MBK SBK MBK Whm Whm Whm SBK MBK 3 phase electric power Single phase electric power MBK Main Breaker SBK Sub Breaker Whm Electricity meter 2nd floor air conditioner Refrigerant system 2 Heat Recovery type 1st floor air conditioner Refrigerant s...

Страница 961: ...gle phase electric power MBK Main Breaker SBK Sub Breaker Whm Electricity meter 2nd floor air conditioner Refrigerant system 2 Heat Recovery type Roof air conditioner All Refrigerant system 1st floor air conditioner Refrigerant system 1 Heat Pump type Refrigerant system 2 Refrigerant system 1 Tenant A Tenant B Tenant C Tenant D 07 180 FUNCTION SETTING FUNCTION SETTING ...

Страница 962: ...be installed for all the units which perform apportionment calculation Peak cut control function Only for System controller Installation of an electricity meter is essential Power consumption graph display function Only for System controller Installation of an electricity meter is essential Installation example Whm Whm Whm Whm Whm Whm Electricity meter Outdoor unit group Remote controller group RB...

Страница 963: ... VRF Network system 1 VRF Network system 2 VRF Network system 3 VRF Network system 1 VRF Network system 2 VRF Network system 3 Whm Whm Whm Whm 2 With the electricity charge apportionment function an electricity meter system cannot span TPC Whm Whm Whm Whm TPC1 management range TPC2 management range TPC2 TPC1 Create an electricity meter system within the range of the units managed by each TPC An el...

Страница 964: ...Whm I F Connect the electricity meter that measures the units managed by the appropriate TPC to the electricity meter I F belonging to the TPC main unit Whm Whm TPC1 management range TPC2 management range TPC2 TPC1 Whm I F Whm I F 07 183 FUNCTION SETTING FUNCTION SETTING ...

Страница 965: ... Whm Whm 4 Outdoor unit indoor unit RB unit mixed in 1 meter is possible Whm 5 There are no restrictions on outdoor units which connect an electricity meter An arbitrary electricity meter can be connected to an arbitrary outdoor unit 07 184 FUNCTION SETTING FUNCTION SETTING ...

Страница 966: ...1 separately connect the electricity meter to VRF air conditioners because there are some functions 2 that are electricity meter unsupported However UTY VGGXZ1 which connects a group remote controller is an exception 2 Electricity charge apportionment function The electricity charge apportionment function cannot be used with single types air conditioners which are con nected to a network converter...

Страница 967: ...Whm Indoor unit Externally linked unit Externally linked unit Indoor unit 6 Installation of electricity meter which divides remote control groups is prohibited Whm Whm Whm Whm Whm Whm Whm Remote controller group Remote controller group 7 Installation of electricity meter which divides outdoor unit groups is prohibited Whm Whm Whm 8 Installation of electricity meter which divides RB groups is OK Wh...

Страница 968: ...ricity charge apportionment function install the electricity meter so that it does not cross over the contract setting set by electricity charge apportionment Whm Whm Whm Whm Whm Whm Contract 1 Contract 2 Contract 3 Whm Whm Whm Whm Whm Whm Whm Whm Contract 1 Contract 2 Contract 3 07 187 FUNCTION SETTING FUNCTION SETTING ...

Страница 969: ...rtionment with outdoor unit only Connect the electricity meter to the outdoor unit Electricity meter is not connected to outdoor unit Electricity meter is not connected to only some outdoor units Whm Whm Outdoor unit indoor unit electricity charge apportionment Connection of an electricity meter to the outdoor unit and indoor unit is necessary Electricity meter is not connected to some indoor unit...

Страница 970: ...nected The following units can be linked to the DX Kit by using external output terminals A External fan B Units linked to run stop state external output At electricity apportionment the DX Kit itself and units A and B mentioned above can be handled Set the electricity value at ON beforehand for the units A and B from the Parameter Setting screen The input value is included in the calculation as a...

Страница 971: ...y from the units A and B If there is a unit related to the DX Kit other than A and B if the DX Kit is connected as an independent electricity meter system and installed so that other units are included it may be included in electricity charge apportionment All the value of that electricity meter is charged to the DX Kit Whm Whm DX Kit B External fan A Run stop state External output linked units DD...

Страница 972: ...e electricity charge apportionment function energy saving function perform control using the power consumption data from an electricity meter it is necessary to set an electricity meter system on the System Controller When installing electricity meters as shown below 5 electricity meters systems are set Whm Whm Whm Whm Whm Whm Electricity meter system 1 Electricity meter system 2 Electricity meter...

Страница 973: ... case the settings are as follows Set point Set item Set value Description Remarks Electricity meter Set in accordance with the product manual When there is a product unique setting setting is performed in accordance with the product manual Pulse units value VT CT ratio output coefficient etc Outdoor unit Meter No setting Arbitrary Set an unique electricity meter No for electricity meter identific...

Страница 974: ...er 6 2 1 OUTDOOR UNIT Electricity meter pulse setting The pulse constant value VT ratio x CT ratio However truncated after the decimal point Set the approximate number of power meter pulses that are equivalent to 1kWh When set number of pulses come from the electricity meter the outdoor unit communicates 1 to the system controller System controller Electricity meter system setting Unit to be measu...

Страница 975: ...8 EXTERNAL INPUT OUTPUT DTV_VR2E018E_11 CHAPTER08 2017 10 31 ...

Страница 976: ... 2 2 EXTERNAL OUTPUT 08 22 1 2 3 OPTIONAL PARTS 08 24 1 2 4 INDOOR UNIT EXTERNAL INPUT OUTPUT FUNCTION SUMMARY 08 25 1 3 RB UNIT 08 26 1 3 1 EXTERNAL INPUT 08 26 1 3 2 OPTIONAL PARTS 08 29 1 4 TOUCH PANEL CONTROLLER 08 30 1 4 1 EXTERNAL INPUT 08 30 1 4 2 EXTERNAL OUTPUT 08 34 1 4 3 OPTIONAL PARTS 08 34 1 5 CENTRAL REMOTE CONTROLLER 08 35 1 5 1 EXTERNAL INPUT 08 35 1 5 2 EXTERNAL OUTPUT 08 38 1 5 3...

Страница 977: ...Optional parts Low noise mode CN131 UTY XWZXZ6 Cooling Heating priority CN132 Outdoor unit operation peak control CN133 Emergency batch stop CN134 Electricity meter pulse CN135 UTY XWZXZF Error status CN136 UTY XWZXZ6 Operation status CN137 Base heater CN115 UTY XWZXZ9 TERMINAL POSITION z zVR II series and V III series Input 4 Input 3 Input 1 Output 1 Input 5 Input 2 1 CN135 ORANGE Outdoor unit PC...

Страница 978: ...PC board z zJ IIIL series CN136 BLK EXT OUT 1 CN137 BLU EXT OUT 2 CN131 YEL CN132 GRN CN134 RED CN133 WHT CN135 ORG EXT IN 1 PLUSE IN EXT IN 4 EXT IN 2 EXT IN 3 CN115 BLK BASE HEATER Base heater CN115 Black Outdoor unit PCB Input 4 CN134 Red Input 3 CN133 White Input 2 CN132 Green Input 1 CN131 Yellow Input 5 CN135 Orange Output 1 CN136 Black Output 2 CN137 Blue 08 02 EXTERNAL INPUT OUTPUT EXTERNA...

Страница 979: ...Input 3 CN133 White Input 2 CN132 Green Input 1 CN131 Yellow BASE HEATER CN115 BLK Input 5 CN135 Orange PULSE IN CN134 CN133 CN132 CN135 CN136 CN137 CN131 EXT OUT 1 EXT IN 4 EXT IN 3 EXT IN 2 EXT IN 1 EXT OUT 2 ORG RED WHT GRN YEL BLK BLU Output 1 CN136 Black Output 2 CN137 Blue 08 03 EXTERNAL INPUT OUTPUT EXTERNAL INPUT OUTPUT ...

Страница 980: ...oor unit operation peak control CN134 Red OFF Normal operation ON Batch stop or Emergency stop operation 2 3 CN135 Orange 4 No pulse No information from electricity meter Pulse Power usage information from electricity meter Slave unit can connect only input5 CN135 Note 1 The external input priority mode must be set by pressing push button on PC board of outdoor unit 2 Batch stop or Emergency stop ...

Страница 981: ...the operation by remote controller is possible z zWhen function setting is Emergency stop mode Connector Input signal Command CN134 ON Emergency stop OFF Normal CN134 Remote Controller Indoor unit outdoor unit Command Operation Emergency stop Normal On On On On Off Stop NOTE All indoor units of same refrigerant system stops when Emergency stop operates When the Emergency stop is triggered indoor u...

Страница 982: ...ge exceeding 24V across pins 1 2 1 2 CN136 Black or CN137 Blue connected unit DC power supply External 12 24V Connected load Operation Indicator or Error Indicator 6 4 5 P C B CN137 Output CN136 Output Operation Error 12 24V 12 24V 0V 0V Stop Normal A twisted pair cable 22AWG should be used Maximum length of cable is 150m Use an external input and output cable with appropriate external dimension d...

Страница 983: ...it operation peak control Emergency batch stop EXTERNAL CONNECT KIT 1 UTY XWZXZ6 For external output Error display Operation display For external input Electricity meter pulse EXTERNAL CONNECT KIT 1 UTY XWZXZF For external output Base heater EXTERNAL CONNECT KIT 1 UTY XWZXZ9 08 07 EXTERNAL INPUT OUTPUT EXTERNAL INPUT OUTPUT ...

Страница 984: ...city 30 03 Energy saving level 5 Operated at 100 capacity 2 If you use Low noise mode operation select low noise level from below 42 00 Low noise level 1 lower than rated value 42 01 Low noise level 2 lower than level 1 NOTE For selecting relay minimum permissible load must be less than 1 mA When you use Apply voltage Take polarity for PIN 1 Number inside bracket indicates function number and sett...

Страница 985: ...r of cables to be installed The wire connection should be separate from the power cable line INPUT SELECT Use either one of these types of terminal according to the application Both types of terminals cannot be used simultaneously z zApply voltage terminal CNA01 CNA03 When a power supply must be provided at the input device you want to connect use the Apply voltage terminal CNA01 CNA03 1 2 1 2 3 I...

Страница 986: ...ke a branch outside the indoor unit using a pull box etc as shown on below example Input device 1 Indoor unit Indoor unit Indoor unit Input device 2 Load resistance Load resistance DC power supply 12 24V connected unit P C B P C B P C B CNA01 CNA01 CNA01 08 10 EXTERNAL INPUT OUTPUT EXTERNAL INPUT OUTPUT ...

Страница 987: ...om Apply voltage terminals Be sufficiently careful when wiring When connected to Dry contact terminals of multiple indoor units with a connected unit insulate each indoor unit with relay etc as shown on below example Input device 1 Indoor unit Indoor unit Indoor unit Power supply for relay Input device 2 K1 K6 Relay Device for DC Current P C B P C B P C B K1 K4 K5 K6 K2 K3 CNA02 CNA02 CNA02 NOTE W...

Страница 988: ...d Ch1 of CNA01 or CNA02 OFF ON Operation ON OFF Stop Ch1 input of CNA01 or CNA02 Remote Controller Indoor unit Operation On On Off Stop In the case of Pulse input Connector Input signal Command CNA01 or CNA02 Ch1 OFF ON Operation Ch2 OFF ON Stop Operation On On The width of pulse must be longer than 200msec Off Off Stop CNA01 or CNA02 Ch1 input Ch2 input Remote Controller On Indoor unit NOTE The l...

Страница 989: ...ormal On On On On Off Stop In the case of Pulse input Connector Input signal Command CNA01 or CNA02 Ch1 OFF ON Emergency stop Ch2 OFF ON Normal Operation On On The width of pulse must be longer than 200msec Off Off Stop CNA01 or CNA02 Ch1 input Ch2 input Remote Controller Indoor unit On On On Command Emergency stop Normal NOTE All indoor units of same refrigerant system stops when Emergency stop o...

Страница 990: ...ormal In the case of Pulse input Connector Input signal Command CNA01 or CNA02 Ch1 OFF ON Forced stop Ch2 OFF ON Normal Operation On On The width of pulse must be longer than 200msec Off Off Stop CNA01 or CNA02 Ch1 input Ch2 input Remote Controller Indoor unit On On On Command Forced stop Normal NOTE When the forced stop is triggered indoor unit stops and Operation Stop operation by a remote contr...

Страница 991: ... device 2 Load resistance Load resistance DC power supply 12 24V connected unit Wired R C or Simple R C Remote controller group P C B P C B P C B CNA01 CNA01 CNA01 Example 2 Prohibited Input device 1 Input device 2 Load resistance Load resistance DC power supply 12 24V connected unit Wired R C or Simple R C Remote controller group P C B P C B P C B CNA 01 CNA 01 CNA 01 08 15 EXTERNAL INPUT OUTPUT ...

Страница 992: ...r Fan setting when cooling thermostat OFF Number 49 00 Follow the setting on the remote controller Forced thermostat off is one of the function to save energy For example case of outdoor temperature is lower than Indoor temperature Indoor unit of air conditioner worked as Fan operation based upon receiving signal from external controller Cooling Only 31 C 28 C 24 C 28 C Cooling operation Thermosta...

Страница 993: ...tus Outdoor temp Indoor temp ON Outdoor temp Indoor temp OFF Normal Forced thermostat off Open Close Signal detected by external controller Command from external controller EEV Indoor unit Normal means that Indoor unit is continued appropriate operation until Forced thermostat off signal received at condition which are set by central and individual controller or detected by thermo sensors of indoo...

Страница 994: ... Forced ther mostat off signal received Indoor unit start operation under Fan mode Example of Electrical circuit 1 2 1 2 CNA04 Indoor unit Service parts Relay External controller Indoor unit circuit board Max 150 m Dry contact external input wire Specification of external input Item Spec Terminal CNA04 Output voltage DC 12V Wire diameter AWG22 Twist 0 33mm2 Service parts No 9368778019 Requirement ...

Страница 995: ...8 C Cooling operation Thermostat on Fan stop Thermostat off Direct digital controller Thermistor Thermistor Thermistor Thermistor Ventilator Indoor Temperature Indoor Temperature Outdoor Temperature Outdoor Temperature System figure example 28 C 31 C Indoor unitとExternal Input W ire Service parts 以外はすべ て現地調達になります Relay External controller Outdoor thermistor Indoor thermistor Outdoor Temperature In...

Страница 996: ...ich are set by central and individual controller or detected by thermo sensors of indoor unit Function setting of indoor unit 49 01 Indoor unit Function No Set Setting No 49 01 Setting No Indoor unit is continued appropriate operation until Forced thermostat off signal received at condition which are set by central and individual controller or detected by thermo sensors of indoor unit Once receive...

Страница 997: ...uit board Max 150 m Dry contact external input wire Specification of external input Item Spec Terminal CNA04 Output voltage DC 12V Wire diameter AWG22 Twist 0 33mm2 Service parts No 9368778019 Requirement for relay switch Item Spec Min permissible load 1mA or less 08 21 EXTERNAL INPUT OUTPUT EXTERNAL INPUT OUTPUT ...

Страница 998: ...put2 Pins 1 3 0V Normal DC 12V Error External output3 Pins 1 4 0V Indoor unit fan stop DC 12V Indoor unit fan operation External output4 Pins 1 5 0V Auxiliary heater OFF DC 12V Auxiliary heater ON OUTPUT SELECT z zWhen indicator etc are connected directly 1 2 3 4 5 6 P C B CNB01 Operation indicator Error indicator Indoor unit Fan status indicator connected unit z zWhen connecting with unit equippe...

Страница 999: ...is on and Room Temperature Tr decrease below 10 C signal output is off The output also turns OFF on defrost operation and oil recovery operation z zFan delay switch Indoor Unit This is used to continue indoor unit fan operation for 1 minute after thermo OFF in heating mode 1 minute delay control set by Dip sw2 3 on PCB is ON CAUTION Please install auxiliary heater between the indoor unit and the o...

Страница 1000: ...terminal EXTERNAL CONNECT KIT 1 UTY XWZXZB For control input port Dry contact terminal EXTERNAL CONNECT KIT 1 UTY XWZXZD For forced thermostat off port Apply voltage terminal EXTERNAL CONNECT KIT 1 UTY XWZXZ7 For forced thermostat off port Dry contact terminal EXTERNAL CONNECT KIT 1 UTY XWZXZE 08 24 EXTERNAL INPUT OUTPUT EXTERNAL INPUT OUTPUT ...

Страница 1001: ... 2 Edge DC12 24 V 10 mA or less CNA01 Ch1 PIN1 2 Ch2 PIN1 3 Pulse 1 CNA03 PIN1 2 Edge 1 Default setting is Edge signal if you use pulse signal must be set Dip SW2 2 to ON position INDOOR UNIT EXTERNAL OUTPUT FUNCTION Item Dry contact Apply voltage Function Specifications Operation status Error status Indoor unit fan operation status Auxiliary heater output Terminal Terminal output voltage Wire siz...

Страница 1002: ... input cable with appropriate external dimension depending on the number of cables to be installed The wire connection should be separate from the power cable line INPUT SELECT Use either one of these types of terminal according to the application Both types of terminals cannot be used simultaneously z zDry contact terminal CNA01 When a power supply is unnecessary at the input device you want to c...

Страница 1003: ...with relay etc as shown on below example RB unit RB unit RB unit Power supply for relay Input device K1 K3 Relay Device for DC Current P C B P C B P C B K1 K2 K3 CNA 01 CNA 01 CNA 01 NOTE When connected to multiple RB units directly it will cause breakdown 08 27 EXTERNAL INPUT OUTPUT EXTERNAL INPUT OUTPUT ...

Страница 1004: ...e allowable current is DC 5mA to 10mA Recommended DC5mA Provide a load resistance such that the current becomes DC10mA or less Select very low current use contacts usable at DC12V DC1mA or less d The polarity is for pin 1 and for pin 3 Connect correctly When connected to Apply voltage terminals of multiple RB units with a connected unit be sure to make a branch outside the RB unit using a pull box...

Страница 1005: ...ooling priority CNA01 or CNA02 Priority mode Heating On Off Cooling 1 3 2 OPTIONAL PARTS Usage Name and shapes Q ty Models For control input port Dry contact terminal EXTERNAL CONNECT KIT 1 UTY XWZXZ6 For control input port Apply voltage terminal EXTERNAL CONNECT KIT 1 UTY XWZXZB 08 29 EXTERNAL INPUT OUTPUT EXTERNAL INPUT OUTPUT ...

Страница 1006: ...e Apply voltage terminal by connecting the CN201 on the TM201 printed circuit board to the CN411 or the CN412 on the printed circuit board of the panel side The Dry contact terminal connected to the CN411 is set when shipped from the factory TM201 K1 K2 Connect with the CN201 Dry contact terminal CN411 Apply voltage terminal CN412 z zDry contact terminal TM201 CN411 When a power supply is unnecess...

Страница 1007: ... PCB RED CN412 WHITE CN411 Connection example 2 When the electricity meter is connected CN201 2 K1 K2 K1 K2 CH1 CH2 TM201 3 DC power supply 12 24 V T U P N I L A N R E T X E Electricity meter PCB PCB RED CN412 WHITE CN411 2 Make the power supply DC 12 to 24 V Select a power supply capacity with an ample surplus for the connected load 3 Do not impress a voltage exceeding 24 V across K1 K2 4 The all...

Страница 1008: ...ng the application Emergency stop Edge Pulse All on All off Electricity meter Pulse INPUT SIGNAL TYPE The input signal type can be selected Edge L H Emergency stop or All on CH1 L H Emergency stop reset or All off Pulse L H 300ms or more Emergency stop or All on CH1 Emergency stop reset or All off CH2 L H 50ms or more Electricity meter signal CH1 When Edge was selected only CH1 can be used 08 32 E...

Страница 1009: ...more CH1 Indoor unit All on Emergency stop ON OFF All off Normal In the case of Pulse input Terminal Input signal Command TM201 CH1 Pulse All on Emergency stop CH2 All off Normal OFF OFF ON ON TM201 CH1 CH2 Indoor unit The width of pulse must be longer than 300msec All on Emergency stop All off Normal 08 33 EXTERNAL INPUT OUTPUT EXTERNAL INPUT OUTPUT ...

Страница 1010: ...de a load resistance such that the current becomes DC15mA or less 19 Polarity is for pins 1 3 and for pins 2 4 OPERATION STATUS External output1 The output for CN410 1 2 is ON when at least one more indoor units is operating The output is OFF when all of indoor units is stopped CN410 1 2 Output Indoor units Operation Stop 12V 0V ERROR STATUS External output2 The output for CN410 3 4 is ON when Err...

Страница 1011: ...gnal to be input externally at external input terminals INPUT SELECT There are 2 kinds of input method of External input terminal Dry contact or Apply voltage contact z zDry contact When a power supply is unnecessary at the input device you want to connect connect to CN6 and CN7 1 PCB CN6 White CN7 Green Connected unit 1 Short circuit detection resistance R ON 500 ohm Open circuit detection resist...

Страница 1012: ...ecomes DC5mA or less A twisted pair cable 22AWG should be used Maximum length of cable is 25m INPUT SIGNAL TYPE The input signal type can be selected Press the button and move the cursor to the Operation menu Emergency Stop button Enables Emergency stop by external input All On All Off button Enables batch operation On Off by external input Not Used button Does not receive external input signals P...

Страница 1013: ...unit All on Emergency stop On Off All off Normal In the case of Pulse input Connector Input signal Command CN6 or CN11 OFF ON All on Emergency stop CN7 or CN12 OFF ON All off Normal Off Off On On CN6 or CN11 CN7 or CN12 Indoor unit The width of pulse must be longer than 300msec All on Emergency stop All off Normal 08 37 EXTERNAL INPUT OUTPUT EXTERNAL INPUT OUTPUT ...

Страница 1014: ...OPERATION STATUS External output1 The output for CN9 3 4 is ON when at least one more indoor units is operating The output is OFF when all of indoor units is stopped CN9 3 4 Output Indoor units Operation Stop 12V 0V ERROR STATUS External output2 The output for CN9 1 2 is ON when Error of at least one more indoor unit or outdoor unit or Central remote controller is generated CN9 1 2 Output Indoor u...

Страница 1015: ...Pulse 1 Central Remote Controller Dry contact Screen icon Screen icon CN6 PIN1 2 Edge CN6 Ch1 PIN1 2 CN7 Ch2 PIN1 2 Pulse 1 Apply voltage Screen icon Screen icon CN11 PIN1 3 Edge DC24 V 5mA or less CN11 Ch1 PIN1 3 CN12 Ch2 PIN1 3 Pulse 1 1 Default setting is Edge signal if you use pulse signal must be set pulse signal from screen icon CONTROLLER EXTERNAL OUTPUT FUNCTION Central Controller Output F...

Страница 1016: ...9 NOTES DTV_VR2E018E_11 CHAPTER09 2017 07 21 ...

Страница 1017: ...NG CONCENTRATION LIMIT 09 02 2 INSTALLATION PRECAUTIONS 09 04 2 1 INDOOR UNIT INSTALLATION PRECAUTIONS 09 04 2 2 OUTDOOR UNIT INSTALLATION PRECAUTIONS 09 07 3 COMPATIBILITY OF VRF SYSTEM 09 08 4 ABOUT CONNECTION BETWEEN SERIES 09 13 4 1 PIPING CONNECTION 09 13 4 2 WIRING CONNECTION 09 14 ...

Страница 1018: ... be large enough that the refrigerant gas will not exceed the concentration limit even if the refrigerant gas leaks z zConcentration limit Concentration limit is the limit of Freon gas concentration where immediate measures can be taken without hurting the human body when refrigerant leaks in to the air The concentration limit shall be described in units of Kg m3 Freon gas weight in per m3 air to ...

Страница 1019: ...each system is independent total amount of replenished refrigerant of each system shall be adopted Total amount of replenished refrigerant in refrigerant facility kg When the result of calculation exceeds the limiting concentration perform the same calculations by shifting to the second smallest and the third smallest rooms until the final result is below the limiting concentration Refrigerant con...

Страница 1020: ... shortening the length of the refrigerant pipes 2 Lower the capacity of the outdoor unit Separate the outdoor unit into multiple units to lower the outdoor unit capacity for each refrigerant system and reduce the refrigerant charging amount Countermeasure 3 Provide gas leak alarm linked with mechanical ventilator Countermeasure 3 Countermeasure 1 Opening effective to ventilation Gas leak alarm Flo...

Страница 1021: ... Contents Countermeasures Reference When the ceiling is high If the indoor unit is installed where the installation height given in the installation manual is exceeded the temperature difference between the floor and ceiling of the room will be large and the heating effect will be poor Moreover even if the indoor unit is installed within the installation height a similar phenomena will occur when ...

Страница 1022: ...y inside the ceiling 1 Always perform heat insulation processing Heat insulating material Glass wool 25mm 31 32in thick or more When the remote controller installation site is bad If the cold or warm air blown out from the air conditioner directly contacts the thermostat section of the remote controller the outlet temperature of the air conditioner may be sensed and room temperature control will b...

Страница 1023: ...ficult to turn off by the thermostat 1 Replace the indoor unit thermistor with a Remote sensor unit optional parts and install the sensor where the room temperature can be correctly detected When the outlet air is sucked in at duct type Cooling operation does not cool the room and heating operation does not heat the room because the short circuited indoor unit is not turned on by the thermostat 1 ...

Страница 1024: ...et at the following places Installation precautions Contents Countermeasures Reference When installed near adjacent houses Perform installation work so that operating sound does not disturb the neighbors 1 Install a soundproof barrier 2 Change the installation site When there is the possibility of strong wind 1 If the outdoor unit is exposed to strong wind capacity may drop frost may form during h...

Страница 1025: ... unit A GA H or A GB H or A GC H 1 A LA H or A LB H 2 Outdoor unit VR Ⅱ series 4 OK Prohibited V Ⅲ series OK OK V Ⅱ series 4 OK OK J Ⅲ L series 4 OK OK J Ⅲ series 3 4 OK 3 OK J Ⅱ S series 3 4 OK 3 OK J Ⅱ series 3 4 OK 3 OK 1 2 arbitrary character 3 Following indoor units cannot be connected ARXC60 72 90 96 4 Large airflow duct ARXN18 45 can be connected to V III series only 09 08 NOTES NOTES ...

Страница 1026: ...3 V Ⅲ series ARXD18GALH OK Case 4 ARXD18LATH OK Case 5 V Ⅱ series ARXD18GALH OK Case 6 ARXD18LATH OK Case 7 J Ⅲ L series ARXD18GALH OK Case 8 ARXD18LATH OK Case 9 J Ⅲ series ARXD18GALH OK Case 10 ARXD18LATH OK Case 11 J Ⅱ S series ARXD18GALH OK Case 12 ARXD18LATH OK Case 13 J Ⅱ series ARXD18GALH OK Case 14 ARXD18LATH OK 09 09 NOTES NOTES ...

Страница 1027: ...red Remote Controller Touch panel UTY RNR Z UTY RNR OK 2 OK Wired Remote Controller 2 wire UTY RLR OK 2 OK Wired Remote Controller UTY RNK OK OK Simple Remote Controller with master control UTY RSR 2 UTY RSK OK OK Simple Remote Controller without master control UTY RHR 2 UTY RHK OK OK Wireless Remote Controller UTY LNH OK 3 OK 1 Different VRF series may be connected for each of the 4 VRF networks ...

Страница 1028: ...lar flow type UTY LBHXD 4 OK 4 OK Human Sensor Kit for Cassette circular flow type UTY SHZXC 4 OK 4 OK Signal amplifier UTY VSGXZ1 OK OK Signal amplifier UTY VSGX 1 OK 1 OK Network Convertor UTY VTGX UTY VTGXV OK OK Network Convertor UTY VGGXZ1 UTY VGGX OK OK Network Convertor for LONWORKS UTY VLGX OK OK BACnet Gateway Hardware UTY VBGX OK OK BACnet Gateway Software UTY ABGXZ1 UTY ABGX 2 OK 2 OK K...

Страница 1029: ...Tool UTY AMGXZ1 2 OK 2 OK 1 Since Signal filter mode is not contained please use UTY VSGXZ1 when use Signal filter mode 2 Different VRF series may be connected for each of the 4 VRF networks supported by the unit but different series may not coexist within the same network 3 It is not connectable with Large airflow duct type ARXN18 45 4 Following indoor units can be connected A G AH arbitrary char...

Страница 1030: ...OK V II Outdoor unit VR II Outdoor unit J II Outdoor unit Refrigerant pipe Refrigerant pipe Refrigerant pipe Separation tube Refrigerant system 1 Refrigerant system 2 Refrigerant system 3 Separation tube Separation tube RB unit EXAMPLE2 Prohibited VR II Outdoor unit V II Outdoor unit J II Outdoor unit Refrigerant pipe RB unit Refrigerant system 1 Separation tube 09 13 NOTES NOTES ...

Страница 1031: ...e Transmission line Refrigerant system 1 VRF network system Refrigerant system 2 Refrigerant system 3 z zConnection method to terminal Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit RB unit IN U OUT U RB unit IN U OUT U RB unit IN U OUT U Indoor unit Indoor unit Indoor unit Refrigerant system 1 Refrigerant system 2 Refrigerant system 3 VR II Outdoor unit J II O...

Страница 1032: ...t system 3 Master Master Slave Slave Slave z zConnection method to terminal Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit RB unit IN U OUT U RB unit IN U OUT U RB unit IN U OUT U Indoor unit Indoor unit Indoor unit Refrigerant system 1 Refrigerant system 2 Refrigerant system 3 VR II Outdoor unit J II Outdoor unit V II Outdoor unit Master Master Slave Slave Sla...

Страница 1033: ... 1 VRF network system Refrigerant system 2 Refrigerant system 3 z zConnection method to terminal Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit RB unit IN U OUT U RB unit IN U OUT U RB unit IN U OUT U Indoor unit Indoor unit Indoor unit Refrigerant system 1 Refrigerant system 2 Refrigerant system 3 VR II Outdoor unit J II Outdoor unit V II Outdoor unit Master M...

Страница 1034: ...10 OPTIONAL PARTS DTV_VR2E018E_13 CHAPTER10 2017 10 31 ...

Страница 1035: ...10 32 5 3 INSTALLATION 10 34 5 4 REFRIGERANT CIRCUIT 10 36 5 5 WIRING DIAGRAMS 10 38 5 6 ELECTRIC CHARACTERISTICS 10 41 5 7 SAFETY DEVICES 10 42 6 CONTROLLER 10 43 7 ADAPTOR CONVERTOR MAINTENANCE 10 45 8 CASSETTE GRILLE 10 48 9 OTHERS 10 49 9 1 PARTS LIST 10 49 9 1 1 INDOOR UNIT 10 49 9 1 2 OTHERS 10 57 10 OPTIONAL PARTS INSTALLATION 10 64 10 1 DRAIN PUMP UNIT 10 64 10 2 FRESH AIR INTAKE KIT MODEL...

Страница 1036: ...acity at rated condition of indoor unit connected under the targeted separation tube z zFor 2 pipes UTP AX054A UTP AX090A UTP AX180A UNIT kW Liquid pipe 2 2 or more to 19 6 1 1 or more to 18 5 1 1 or more to 18 5 Gas pipe 2 2 or more to 19 6 1 1 or more to 18 5 1 1 or more to 18 5 Liquid pipe 2 2 or more to 28 0 1 1 or more to 26 9 1 1 or more to 18 0 Liquid pipe 28 1 or more to 56 0 27 0 or more ...

Страница 1037: ... 10 02 OPTIONAL PARTS OPTIONAL PARTS z zFor 2 pipes UTP AX567A UNIT kW Liquid pipe 56 1 or more 55 0 or more 1 1 or more to 101 2 Gas pipe 56 1 or more 55 0 or more 1 1 or more to 101 2 ...

Страница 1038: ...to 26 9 1 1 or more to 18 0 Discharge gas pipe Discharge gas pipe 28 1 or more to 56 0 27 0 or more to 54 9 1 1 or more to 28 0 Suction gas pipe 2 2 or more to 28 0 1 1 or more to 26 9 1 1 or more to 18 0 Suction gas pipe 28 1 or more to 56 0 27 0 or more to 54 9 1 1 or more to 28 0 Liquid pipe 56 1 or more 55 0 or more 1 1 or more to 101 2 Discharge gas pipe 56 1 or more 55 0 or more 1 1 or more ...

Страница 1039: ...TS 1 1 SEPARATION TUBE FOR 2 PIPES UTP AX054A z zPort diameters and dimensions Liquid pipe Gas pipe Q ty Q ty 1 1 z zHeat insulation Heat insulation Application Tape Q ty Q ty 2 Large x 1 for gas pipe Small x 1 for liquid pipe 8 Unit mm ...

Страница 1040: ...090A z zPort diameters Liquid pipe Gas pipe Q ty Q ty 1 1 z zHeat insulation Heat insulation Application Q ty 2 for Liquid pipe x1 for Gas pipe x1 z zDimensions Liquid pipe Gas pipe EXPANDER EXPANDER Tape Q ty 8 EXPANDER EXPANDER 20 100 Unit mm ...

Страница 1041: ...80A z zPort diameters Liquid pipe Gas pipe Q ty Q ty 1 1 z zHeat insulation Heat insulation Application Q ty 2 for Liquid pipe x1 for Gas pipe x1 z zDimensions Liquid pipe Gas pipe REDUCER REDUCER Tape Q ty 8 130 15 REDUCER 95 15 REDUCER Unit mm ...

Страница 1042: ...AX567A z zPort diameters Liquid pipe Gas pipe Q ty Q ty 1 1 z zHeat insulation Heat insulation Application Q ty 2 for Liquid pipe x1 for Gas pipe x1 z zDimensions Liquid pipe Gas pipe REDUCER REDUCER Tape Q ty 8 REDUCER 100 15 REDUCER Unit mm ...

Страница 1043: ...S UTP BX090A z zPort diameters Liquid pipe Discharge gas pipe Q ty Q ty 1 1 Suction gas pipe Q ty 1 z zHeat insulation Heat insulation Application Q ty 3 for Liquid pipe x1 for Discharge gas pipe x1 for Suction gas pipe x1 REDUCER EXPANDER EXPANDER Tape Q ty 8 Unit mm ...

Страница 1044: ... 10 09 OPTIONAL PARTS OPTIONAL PARTS z zDimensions Liquid pipe Discharge gas pipe Suction gas pipe 95 15 REDUCER EXPANDER EXPANDER 20 100 ...

Страница 1045: ...A z zPort diameters Liquid pipe Discharge gas pipe Q ty Q ty 1 1 Suction gas pipe Q ty 1 z zHeat insulation Heat insulation Application Q ty 3 for Liquid pipe x1 for Discharge gas pipe x1 for Suction gas pipe x1 REDUCER REDUCER Tape Q ty 8 Unit mm ...

Страница 1046: ... 10 11 OPTIONAL PARTS OPTIONAL PARTS z zDimensions Liquid pipe Discharge gas pipe Suction gas pipe 130 15 REDUCER 95 15 REDUCER ...

Страница 1047: ... diameters Liquid pipe Discharge gas pipe Q ty Q ty 1 1 Suction gas pipe Q ty 1 z zHeat insulation Heat insulation Application Q ty 3 for Liquid pipe x1 for Discharge gas pipe x1 for Suction gas pipe x1 EXPANDER EXPANDER REDUCER REDUCER Tape Q ty 8 Unit mm ...

Страница 1048: ... 10 13 OPTIONAL PARTS OPTIONAL PARTS z zDimensions Liquid pipe Discharge gas pipe Suction gas pipe EXPANDER 20 100 EXPANDER 20 100 REDUCER 100 15 REDUCER ...

Страница 1049: ...ies z zPort diameters Liquid pipe Discharge gas pipe Q ty Q ty 1 1 Suction gas pipe Q ty 1 z zHeat insulation Heat insulation Application Q ty 3 for Liquid pipe x1 for Discharge gas pipe x1 for Suction gas pipe x1 L joint pipe Q ty 2 L joint pipe Q ty 2 Q ty 2 Q ty 2 L joint pipe Q ty 2 Q ty 2 Tape Q ty 8 ...

Страница 1050: ... 10 15 OPTIONAL PARTS OPTIONAL PARTS z zDimensions Liquid pipe Discharge gas pipe Suction gas pipe L joint pipe L joint pipe 100 90 70 60 L joint pipe ...

Страница 1051: ...eries z zPort diameters Liquid pipe Gas pipe Q ty Q ty 1 1 z zHeat insulation Heat insulation Application Q ty 2 for Liquid pipe x1 for Gas pipe x1 z zDimensions Liquid pipe Gas pipe L joint pipe Q ty 2 L joint pipe Q ty 2 Q ty 2 Tape Q ty 8 L joint pipe L joint pipe Unit mm ...

Страница 1052: ... 3 pipes 3 6 Branches 3 8 Branches 3 6 Branches 3 8 Branches 28 0 or less UTR H0906L UTR H0908L UTP J0906A UTP J0908A 28 1 to 56 0 UTR H1806L UTR H1808L UTP J1806A UTP J1808A Each Value above such as 28 0 28 1 and 56 0 kw means total cooling capacity at rated condition of indoor unit connected under the targeted header tube ...

Страница 1053: ...ES MODEL UTR H0906L z zPort diameters Liquid pipe Gas pipe Closed pipe A Closed pipe B Closed pipe C Closed pipe insulation z zHeat insulation Header insulation liquid Header insulation gas z zDimensions Liquid pipe Gas pipe Q ty 3 Q ty 2 Q ty 2 Q ty 6 Q ty 1 Q ty 1 ...

Страница 1054: ...R H0908L z zPort diameters Liquid pipe Gas pipe Closed pipe A Closed pipe B Closed pipe C Closed pipe insulation z zHeat insulation Header insulation liquid Header insulation gas z zDimensions Liquid pipe Gas pipe Q ty 5 Q ty 4 Q ty 2 Q ty 8 Q ty 1 Q ty 1 ...

Страница 1055: ...eters Liquid pipe Gas pipe Closed pipe A Closed pipe B Closed pipe C Closed pipe insulation z zHeat insulation Header insulation liquid Header insulation gas z zDimensions Liquid pipe Gas pipe REDUCER EXPANDER Q ty 3 Q ty 2 Q ty 2 Q ty 6 Q ty 1 Q ty 1 130 15 REDUCER EXPANDER ...

Страница 1056: ...eters Liquid pipe Gas pipe Closed pipe A Closed pipe B Closed pipe C Closed pipe insulation z zHeat insulation Header insulation liquid Header insulation gas z zDimensions Liquid pipe Gas pipe EXPANDER REDUCER Q ty 5 Q ty 2 Q ty 4 Q ty 8 Q ty 1 Q ty 1 130 15 REDUCER EXPANDER ...

Страница 1057: ...A z zPort diameters Liquid pipe Dis charge gas pipe Suction gas pipe Closed pipe A Closed pipe B Closed pipe C Closed pipe insulation z zHeat insulation Heat insulation Application Q ty 3 for Liquid pipe x1 for Discharge gas pipe x1 for Suction gas pipe x1 Q ty 3 Q ty 5 Q ty 2 Q ty 9 ...

Страница 1058: ... 10 23 OPTIONAL PARTS OPTIONAL PARTS z zDimensions Liquid pipe Dis charge gas pipe Suction gas pipe ...

Страница 1059: ...Liquid pipe Dis charge gas pipe Suction gas pipe Closed pipe A Closed pipe B Closed pipe C Closed pipe insulation z zHeat insulation Heat insulation Application Q ty 3 for Liquid pipe x1 for Discharge gas pipe x1 for Suction gas pipe x1 Q ty 5 Q ty 9 Q ty 2 Q ty 15 Unit mm ...

Страница 1060: ... 10 25 OPTIONAL PARTS OPTIONAL PARTS z zDimensions Liquid pipe Dis charge gas pipe Suction gas pipe ...

Страница 1061: ...Dis charge gas pipe Suction gas pipe Closed pipe A Closed pipe B Closed pipe C Closed pipe insulation z zHeat insulation Heat insulation Application Q ty 3 for Liquid pipe x1 for Discharge gas pipe x1 for Suction gas pipe x1 REDUCER REDUCER EXPANDER Q ty 3 Q ty 4 Q ty 4 Q ty 9 Unit mm ...

Страница 1062: ... 10 27 OPTIONAL PARTS OPTIONAL PARTS z zDimensions Liquid pipe Dis charge gas pipe Suction gas pipe 80 20 REDUCER 130 15 REDUCER EXPANDER ...

Страница 1063: ...Dis charge gas pipe Suction gas pipe Closed pipe A Closed pipe B Closed pipe C Closed pipe insulation z zHeat insulation Heat insulation Application Q ty 3 for Liquid pipe x1 for Discharge gas pipe x1 for Suction gas pipe x1 REDUCER EXPANDER REDUCER Q ty 5 Q ty 6 Q ty 6 Q ty 15 Unit mm ...

Страница 1064: ... 10 29 OPTIONAL PARTS OPTIONAL PARTS z zDimensions Liquid pipe Dis charge gas pipe Suction gas pipe 80 20 REDUCER 130 15 REDUCER EXPANDER ...

Страница 1065: ... UTR EV14XB AS E12GACH AS E14GACH AS E012GCAH AS E014GCAH AG E012GCAH AG E014GCAH EV kit Hanger Refrigerant pipe flare connection liquid pipe Indoor unit side ø 6 35 mm Outdoor unit side ø 6 35 mm Name and Shape Q ty Name and Shape Q ty Name and Shape Q ty Name and Shape Q ty 1 2 1 1 Large 5 4 1 Small 2 1 1 2 2 EV kit Coupler heat insulation Special nut A M10 large frange Special nut B M10 small f...

Страница 1066: ...Q 18 0 Input power W 17 24 31 96 Running current A 0 11 0 16 0 22 0 64 Refrigerant type R410A Dimensions H x W x D Net mm 198 298 268 260 658 428 Gross 262 833 374 348 1250 775 Weight Net kg 7 7 5 8 31 5 Gross 9 5 10 5 11 39 5 Connection pipe Outdoor unit side Suction gas pipe mm ø12 70 ø19 05 ø22 22 ø28 58 Discharge gas pipe ø9 52 ø12 70 ø19 05 ø22 22 Liquid pipe None ø15 88 Indoor unit side Gas ...

Страница 1067: ... 10 32 OPTIONAL PARTS OPTIONAL PARTS 5 2 DIMENSIONS MODELS UTP RX01AH UTP RX01BH UTP RX01CH Unit mm Ceiling hanging Outdoor unit side Indoor unit side Wall hanging ...

Страница 1068: ... 10 33 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX04BH Unit mm ...

Страница 1069: ...ol box side Since the sound of refrigerant flow may be felt as an unusual sound please do not install in the underpart of the roof such as a bedroom which sound worries MODELS UTP RX01AH UTP RX01BH UTP RX01CH z zCeiling installation Unit mm 500 or more 500 or more 20 or more 20 or more Service access Control box z zWall installation Service space Grille Grille 20 or more 20 or more 300 or more E g...

Страница 1070: ...L PARTS OPTIONAL PARTS MODEL UTP RX04BH z zCeiling installation Unit mm 500 or more 700 or more 400 or more 500 or more 280 or more 1 280 or more 1 1 When piping is not connected 20 or more 20 or more Service access ...

Страница 1071: ... gas to Indoor unit GAS LINE Suction gas SV1 D1 SV2 B2 SV3 B1 SV4 S1 MODEL UTP RX01BH GAS LINE Discharge gas to Indoor unit GAS LINE Suction gas SV1 D1 SV2 B2 SV3 B1 SV4 S1 SV5 S2 MODEL UTP RX01CH GAS LINE Discharge gas to Indoor unit GAS LINE Suction gas SV1 D1 SV2 B2 SV3 B1 SV4 S1 SV5 S2 SV6 S3 ...

Страница 1072: ...AS LINE Suction gas SV1 D1 SV2 B2 SV3 B1 SV4 S1 SV5 S2 SV1 D1 SV2 B2 SV3 B1 SV4 S1 SV5 S2 SV1 D1 SV2 B2 SV3 B1 SV4 S1 SV5 S2 SV1 D1 SV2 B2 SV3 B1 SV4 S1 SV5 S2 LIQUID LINE SYMBOL DESCRIPTION MARK DESCRIPTION SV1 D1 Solenoid valve Discharge 1 SV2 B2 Solenoid valve Bypass 2 SV3 B1 Solenoid valve Bypass 1 SV4 S1 Solenoid valve Suction 1 SV5 S2 Solenoid valve Suction 2 SV6 S3 Solenoid valve Suction 3 ...

Страница 1073: ... 10 38 OPTIONAL PARTS OPTIONAL PARTS 5 5 WIRING DIAGRAMS MODEL UTP RX01AH MODEL UTP RX01BH ...

Страница 1074: ... 10 39 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX01CH ...

Страница 1075: ... 10 40 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX04BH ...

Страница 1076: ...RTS 5 6 ELECTRIC CHARACTERISTICS Model Voltage V Frequency Hz MCA A MFA A UTP RX01AH 230 50 0 13 20 UTP RX01BH 0 19 UTP RX01CH 0 26 UTP RX04BH 0 76 MCA Min Circuit Amps Max Operating Current Full Load MFA Main Fuse Circuit breaker Amps ...

Страница 1077: ... 10 42 OPTIONAL PARTS OPTIONAL PARTS 5 7 SAFETY DEVICES Model PCB fuse UTP RX01AH 250V 3 15A x 1 UTP RX01BH 250V 3 15A x 1 UTP RX01CH 250V 3 15A x 1 UTP RX04BH 250V 3 15A x 4 ...

Страница 1078: ...nits can be controlled With yearly timer CENTRAL REMOTE CONTROLLER UTY ALGXZ1 Option UTY PLGXA2 UTY PLGXR2 UTY PLGXE2 UTY PLGXP2 UTY PLGXX2 UTY ALGX Option UTY PLGXA1 UTY PLGXR1 UTY PLGXE1 Maximum 400 groups 400 indoor units can be controlled Monitoring status of operation DVD ROM Software protection key UTY APGXZ1 Option UTY PEGXZ1 UTY PPGXP2 UTY APGX Option UTY PEGX Maximum 1600 groups 1600 indo...

Страница 1079: ...TY RSR UTY RSK UTY RHR UTY RHK Background light Easy operation With Operation mode Without Operation mode UTY LNH On Off sleep program timer Easy operation SET TEMP START STOP UTY RNK On Off weekly timer Built in thermo sensor WIRED REMOTE CONTROLLER UTY RLR Large LCD On Off weekly timer UTY RNR Z2 UTY RNR Z1 Large LCD touch panel On Off weekly timer ...

Страница 1080: ...ETWORK CONVERTOR for LONWORKS UTY VTGX Split system convertor UTY VGGXZ1 Split system convertor Group remote convertor UTY VTGXV Split system convertor UTY VLGX LON LON Convertor KNX CONVERTOR for VRF UTY VKGX VRF network system convertor KNX CONVERTOR for INDOOR UNIT UTY VKSX Can be control a indoor unit via this convertor from KNX system ...

Страница 1081: ...witching can be controlled by connecting other sensor switches UTY TERX UTY TEKX UTY TERX UTY TEKX MODBUS CONVERTOR for VRF UTY VMGX MODBUS CONVERTOR for INDOOR UNIT UTY VMSX Can be control a indoor unit via this converter from Modbus system BACnet GATEWAY Hardware UTY VBGX VRF network system to the BMS system using BACnet protocol BACnet GATEWAY Software UTY ABGXZ1 UTY ABGX DVD ROM Software prote...

Страница 1082: ...XZ1 UTY ASGX UTY AMGX DVD ROM Software protection key DVD ROM Software protection key Software protection key with software Software protection key with software WIRELESS LAN ADAPTER UTY TFSXZ1 Remotely manage an Air Conditioning system using mobile devices such as Smartphones and tablets ...

Страница 1083: ... 10 48 OPTIONAL PARTS OPTIONAL PARTS 8 CASSETTE GRILLE UTG UG A W For Cassette type UTG UF C W For Compact Cassette type IR receiver attached UTG UK C W UTG UK A B For Circular Flow Cassette type ...

Страница 1084: ...H AUXA18GALH AUXA24GALH AUXA30GALH AUXA34GALH AUXA36GALH AUXA45GALH AUXA54GALH Circular flow cassette AUXM018GLAH AUXM024GLAH AUXM030GLAH AUXK018GLAH AUXK024GLAH AUXK030GLAH AUXK034GLAH AUXK036GLAH AUXK045GLAH AUXK054GLAH Low static pressure duct concealed floor ARXB07GALH ARXB09GALH ARXB12GALH ARXB14GALH ARXB18GALH Mini duct ARXK04GCLH ARXK07GCLH ARXK09GCLH ARXK12GCLH ARXK14GCLH ARXK18GCLH ARXK24...

Страница 1085: ...ct Floor AG A004GCAH AG A007GCAH AG A009GCAH AG A012GCAH AG A014GCAH Compact Floor EEV external AG E004GCAH AG E007GCAH AG E009GCAH AG E012GCAH AG E014GCAH Floor ceiling AB A12GATH AB A14GATH AB A18GATH AB A24GATH Ceiling AB A30GATH AB A36GATH AB A45GATH AB A54GATH Wall mounted AS A004GTAH AS A007GTAH AS A009GTAH AS A012GCAH AS A014GCAH AS A04GACH AS A07GACH AS A09GACH AS A12GACH AS A14GACH Wall m...

Страница 1086: ...UXA54GALH Circular flow cassette AUXM018GLAH AUXM024GLAH AUXM030GLAH AUXK018GLAH AUXK024GLAH AUXK030GLAH AUXK034GLAH AUXK036GLAH AUXK045GLAH AUXK054GLAH Low static pressure duct concealed floor ARXB07GALH ARXB09GALH ARXB12GALH ARXB14GALH ARXB18GALH Mini duct ARXK04GCLH ARXK07GCLH ARXK09GCLH ARXK12GCLH ARXK14GCLH ARXK18GCLH ARXK24GCLH Slim duct slim concealed floor ARXD04GALH ARXD07GALH ARXD09GALH ...

Страница 1087: ...A012GCAH AG A014GCAH Compact Floor EEV external AG E004GCAH AG E007GCAH AG E009GCAH AG E012GCAH AG E014GCAH Floor ceiling AB A12GATH AB A14GATH AB A18GATH AB A24GATH Ceiling AB A30GATH AB A36GATH AB A45GATH AB A54GATH Wall mounted AS A004GTAH AS A007GTAH AS A009GTAH AS A012GCAH AS A014GCAH AS A04GACH AS A07GACH AS A09GACH AS A12GACH AS A14GACH Wall mounted EEV external AS E004GTAH AS E007GTAH AS E...

Страница 1088: ...LH AUXA45GALH AUXA54GALH Circular flow cassette AUXM018GLAH AUXM024GLAH AUXM030GLAH AUXK018GLAH AUXK024GLAH AUXK030GLAH AUXK034GLAH AUXK036GLAH AUXK045GLAH AUXK054GLAH Low static pressure duct concealed floor ARXB07GALH ARXB09GALH ARXB12GALH ARXB14GALH ARXB18GALH Mini duct ARXK04GCLH ARXK07GCLH ARXK09GCLH ARXK12GCLH ARXK14GCLH ARXK18GCLH ARXK24GCLH Slim duct slim concealed floor ARXD04GALH ARXD07G...

Страница 1089: ...009GCAH AG A012GCAH AG A014GCAH Compact Floor EEV external AG E004GCAH AG E007GCAH AG E009GCAH AG E012GCAH AG E014GCAH Floor ceiling AB A12GATH AB A14GATH AB A18GATH AB A24GATH Ceiling AB A30GATH AB A36GATH AB A45GATH AB A54GATH Wall mounted AS A004GTAH AS A007GTAH AS A009GTAH AS A012GCAH AS A014GCAH AS A04GACH AS A07GACH AS A09GACH AS A12GACH AS A14GACH Wall mounted EEV external AS E004GTAH AS E0...

Страница 1090: ...018GLAH AUXM024GLAH AUXM030GLAH AUXK018GLAH AUXK024GLAH AUXK030GLAH AUXK034GLAH AUXK036GLAH AUXK045GLAH AUXK054GLAH Low static pressure duct concealed floor ARXB07GALH ARXB09GALH ARXB12GALH ARXB14GALH ARXB18GALH Mini duct ARXK04GCLH ARXK07GCLH ARXK09GCLH ARXK12GCLH ARXK14GCLH ARXK18GCLH ARXK24GCLH Slim duct slim concealed floor ARXD04GALH ARXD07GALH ARXD09GALH ARXD12GALH ARXD14GALH ARXD18GALH ARXD...

Страница 1091: ...V external AG E004GCAH AG E007GCAH AG E009GCAH AG E012GCAH AG E014GCAH Floor ceiling AB A12GATH AB A14GATH AB A18GATH AB A24GATH Ceiling AB A30GATH AB A36GATH AB A45GATH AB A54GATH Wall mounted AS A004GTAH AS A007GTAH AS A009GTAH AS A012GCAH AS A014GCAH AS A04GACH AS A07GACH AS A09GACH AS A12GACH AS A14GACH Wall mounted EEV external AS E004GTAH AS E007GTAH AS E009GTAH AS E012GCAH AS E014GCAH AS E0...

Страница 1092: ... AJ A72LALH AJ A90LALH AJ 108LALH AJ 126LALH AJ 144LALH AJ 040LBLAH AJ 045LBLAH AJ 054LBLAH AJ 040LELAH AJ 045LELAH AJ 054LELAH AJ 072LELAH AJ 090LELAH AJ 108LELAH AJ A40LALH AJ A45LALH AJ A54LALH AJ 040LCLAH AJ 045LCLAH AJ 054LCLAH AJ 072LALBH AJ 090LALBH AJ 108LALBH AJ 126LALBH AJ 144LALBH AJ 162LALBH RB unit UTP RX01AH UTP RX01BH UTP RX01CH UTP RX04BH Touch panel controller UTY DTG Z1 UTY DTG C...

Страница 1093: ...GB UTZ KXGC For Cassette type For Circular flow Cassette type For Compact cassette type UTZ VXAA For Compact cassette type UTG AKXA W UTG AGYA W For Cassette type For Circular flow Cassette type UTR YDZK UTR YDZC For Cassette type For Circular flow Cassette type PANEL SPACER WIDE PANEL INSULATION KIT for High Humidity FRESH AIR INTAKE KIT Install when the condition under the roof is over 80 in hum...

Страница 1094: ... necessary separately UTY SHZXC For Circular flow cassette type Touch Panel Wired RC Model UTY RNR Z2 is necessary UTR STA For Compact Floor type UTY LRH B1 For Cassette type The wireless remote controller Model UTY LNH is necessary separately The wireless remote controller Model UTY LNH is necessary separately UTY LBHXD For Circular flow cassette type HALF CONCEALED KIT IR RECEIVER UNIT IR RECEIV...

Страница 1095: ...ssure duct type For Large airflow duct type 018GLBH model 507 239 UTD LFNA For Large airflow duct type 024 030GTBH models 644 5 250 4 UTD GXSA W UTD GXSB W UTD GXSC W For Slim duct 04 14 models For Slim duct 18 model For Slim duct 24 model AUTO LOUVER GRILLE KIT AUTO LOUVER GRILLE KIT UTD GXTA W UTD GXTB W UTD GXTC W For Mini duct Slim duct 04 14 models For Mini duct Slim duct 18 model For MIni du...

Страница 1096: ... UTR DPB24T For Ceiling type FLANGE Square FLANGE Round UTD SF045T For Medium static pressure duct type For Large airflow duct type 018GLBH model 21 21 20 173 174 174 174 174 97 97 20 164 32 5 holes 1 063 40 206 7 5 10 174 174 173 5 173 5 174 174 10 1 093 234 103 7 5 UTD RF204 For Medium static pressure duct type For Large airflow duct type 018GLBH model 225 235 195 205 85 UTY XSZX REMOTE SENSOR U...

Страница 1097: ...T KIT UTY XWZXZ6 For Outdoor unit RB unit UTY XWZXZ9 For Outdoor unit UTY XWZXZC For Indoor unit UTY XWZXZB For Indoor unit RB unit UTY XWZXZD For Indoor unit UTY XWZXZ7 For Indoor unit Central remote controller EXTERNAL CONNECT KIT EXTERNAL CONNECT KIT UTY XWZXZA For Touch panel controller Central remote controller UTY XWZXZ8 For Central remote controller ...

Страница 1098: ... 10 63 OPTIONAL PARTS OPTIONAL PARTS EXTERNAL CONNECT KIT UTY XWZXZE For Indoor unit EXTERNAL CONNECT KIT UTY XWZXZF For Outdoor unit ...

Страница 1099: ... fuse 1 Direction of pipe connection 2 Angle of pipe connection z zApplication indoor units Type Model name Low static pressure duct concealed floor ARXB07GALH ARXB09GALH ARXB12GALH ARXB14GALH ARXB18GALH z zMounting position Max 1000 107 176 51 217 Connected drain pipe VP25 I D 25 O D 32 Front view Unit mm Front view Right side Left side Strong and slide ceiling 470 or more 100 or more 154 127 720...

Страница 1100: ... and insert it until it touches the drain pump unit and indoor unit When there is no screw hole Puncture holes at the following position and then install Ceiling Good Bad Bad Good Air Level meter Level meter 10mm or less 10mm or less z zInstalling hose Max 1m Downward Vertical Vertical loop Upward Trap Horizontal Bend radius is 60mm or more Part Hose Downward gradient of 1 50 to 1 100 Example of w...

Страница 1101: ...eding Trap Bad Rise VP25 O D 32mm or more VP30 O D 38mm or more Observe the following procedures to construct centralized drain pipe fittings z zElectrical wiring Control box cover Drain pump unit Drain pump wire Connector Blue Float switch wire Connector Red Circuit board Indoor unit Control box To indoor unit circuit board ...

Страница 1102: ...Vertical Control method Control board of indoor unit safety device Float switch Thermal fuse 1 Direction of pipe connection 2 Angle of pipe connection z zApplication indoor units Type Model name Medium static pressure duct ARXA24GBLH ARXA30GBLH ARXA36GBLH ARXA45GBLH Large airflow duct ARXN018GLBH z zMounting position Max 1000 163 176 46 270 Connected drain pipe VP25 I D 25 O D 32 Rear view Unit mm...

Страница 1103: ... Tighten the nut securely Make sure that the drain pump unit is not slanted Hose band Big Hose band Small Joint hose Thread the hose band through the joint hose and secure to the drain pump unit and indoor unit z zInstalling hose Max 1m Downward Vertical Vertical loop Upward Trap Horizontal Bend radius is 60mm or more Part Hose Downward gradient of 1 50 to 1 100 Example of wrong construction Bad B...

Страница 1104: ...g Trap Bad Rise VP25 O D 32mm or more VP30 O D 38mm or more Observe the following procedures to construct centralized drain pipe fittings Max 1 m z zElectrical wiring Control box cover Drain pump unit Drain pump wire Connector Blue Float switch wire Connector Red Circuit board Indoor unit Control box To indoor unit circuit board ...

Страница 1105: ...H AB A36GATH AB A45GATH AB A54GATH z zInstalling drain pump unit Electrical wiring Drain pump wire Connector Blue Drain hose B Drain hose A Drain pump assy Drain pan assy Float switch wire Connector Red To indoor unit circuit board z zInstalling pipe 1 5 to 2 m Max 500 mm Supporter Rise Trap Air Bleeding Bad Bad Bad ...

Страница 1106: ...r unit INSTALLATION EXAMPLE Indoor unit Panel Outlet air Outlet air Room air Outside Under the roof Room Standard Locally purchased Connecting Duct Hood Locally purchased Hood Locally purchased Air filter Locally purchased Air filter Locally purchased Outlet air Outlet air Room air Fresh air Intake kit Outlet air Outlet air Room air Duct fan Locally purchased Locally purchased Connecting Duct Fres...

Страница 1107: ...ONAL PARTS SPECIFICATIONS Model name UTZ VXAA Fresh air intake Max fresh air intake volume for High 10 Connection duct type mm ø 100 Pcs 1 Dimension HxWxD Net mm 120 x 570 x 570 Gross 165 x 585 x 585 Weight Net kg 3 5 Gross 5 5 ...

Страница 1108: ...rrounding the product are high Don t intake the air of below 0 C into the Fresh air intake kit The upper Iimit of the product s temperature range should respond to the outdoor temperature range z zAbout duct fan When installing the duct fan connect the drive relay Locally purchased and operate with the indoor unit Please ensure the intake air volume is below 10 of the product s air volume HI When ...

Страница 1109: ...MENSIONS Unit mm 570 Min 450 108 100 45 257 201 570 683 390 120 150 to 200 328 398 310 Ceiling opening space Inspection hatch TOP VIEW SIDE VIEW SIDE VIEW When installing this kit inspection hatch is necessary It is necessary when servicing ...

Страница 1110: ... 10 75 OPTIONAL PARTS OPTIONAL PARTS AIRFLOW 0 50 100 150 200 0 50 100 150 200 Unit mm 450 Measurement position of shown in the graph Airflow m3 h Static pressure of Fresh air intake kit Pa ...

Страница 1111: ... Extended length of the wire Max 25m z zConnection diagram For Relay Output voltage DC12 2V Permissible current 50mA 1 2 3 4 5 6 25m Make the distance from the PC board to the Relay Unit within 25 m Locally purchased Indoor unit P C B CNB01 Fan other power Fuse Relay z zIndoor unit status operation stop 12V 0V Indoor unit fan CNB01 1 4 output z zWire External output Wire color RED Wire color WHITE...

Страница 1112: ...e for louver 2 Extension wire for louver red white Name and shape Q ty Application Extension wire for receiver kit 1 Extension wire for receiving kit Wire External output 1 For connect indoor unit to relay of duct fan For single or multi Wire External output 1 For connect indoor unit to relay of duct fan For VRF Wire External output 1 For connect indoor unit to relay of duct fan For VRF Bolt 4 For...

Страница 1113: ...ecting duct Locally purchased INSTALLATION EXAMPLE Indoor unit Panel Outlet air Outlet air Room air Outside Under the roof Room Standard Locally purchased Connecting Duct Hood Locally purchased Hood Locally purchased Air filter Locally purchased Air filter Locally purchased Outlet air Outlet air Room air Fresh air Intake kit Outlet air Outlet air Room air Duct fan Locally purchased Locally purchas...

Страница 1114: ...CATIONS Model name UTZ VXRA UTZ VXGA Fresh air intake Max fresh air intake volume for High 2 way intake 10 1 way intake 5 Connection duct type mm ø 100 Pcs 2 Dimension HxWxD Net mm 120 x 840 x 840 Gross 165 x 860 x 860 Weight Net kg 5 5 Gross 9 0 ...

Страница 1115: ...rounding the product are high Don t intake the air of below 0 C into the fresh air intake kit The upper limit of the product s temperature range should respond to the outdoor temperature range z zAbout duct fan When installing the duct fan connect the drive relay Locally purchased and operate with the indoor unit Please ensure the intake air volume is below 10 of the product s air volume HI When t...

Страница 1116: ...cessary It is necessary when servicing Either one of inspection hatches must be installed 840 450 Inspection hatch 400 to 450 450 55 55 7 0 840 120 288 418 376 246 71 914 100 Min Inspection hatch Min TOP VIEW SIDE VIEW The size is different according to indoor unit used SIDE VIEW Standard type Slim type ...

Страница 1117: ...0 200 0 50 100 150 200 250 300 350 400 1000 1 Way Intake 2 Way Intake Airflow m3 h Measurement position of shown in the graph Static pressure of Fresh air intake kit Pa Unit mm 1000 Measurement position of shown in the graph for 2 Way Intake for 1 Way Intake ...

Страница 1118: ... Extended length of the wire Max 25m z zConnection diagram For Relay Output voltage DC12 2V Permissible current 50mA 1 2 3 4 5 6 25m Make the distance from the PC board to the Relay Unit within 25 m Locally purchased Indoor unit P C B CNB01 Fan other power Fuse Relay z zIndoor unit status operation stop 12V 0V Indoor unit fan CNB01 1 4 output z zWire External output Wire color RED Wire color WHITE...

Страница 1119: ...the insulation to tube of drain pump for prevent condensation Name and shape Q ty Application Insulation 3 Affixing the insulation outside of the kit Insulation 4 Affixing the insulation outside of the cover Binder 1 Fixing tube of drain pump Extension wire for louver 2 Extension wire for louver Extension wire for receiver kit 1 Extension wire for receiver kit Wire External output 1 For connect in...

Страница 1120: ...nge or Rectangular duct Extension Square Duct Limit 1 0m Max duct length between indoor unit and Grille Net Dimension H x W x D mm 180x683x 84 9 180x883x 84 9 180x1083x 84 9 Weight Net kg 2 0 2 5 3 0 Gross 3 0 3 5 4 0 Color White Louver Motor Stepping Motor Material Flame retardant ABS Accessories Fitting Flame etc Operation range Cooling C 18 to 32 RH 80 or less Heating C 16 to 30 NOTE Auto louve...

Страница 1121: ...cinity of room entrance It may cause condensation on the outlet port Near a wall surface It may cause condensation on the wall during cooling Area filled with mineral oil or containing a large amount of splashed oil or steam such as a kitchen The place where it will be exposed to direct sunlight Or else it may cause a change in color When the installation area is exposed to direct sunlight take me...

Страница 1122: ... W Burring hole Burring hole Hole Hole The inside diameter of the bush z zMODELS UTD GXSB W UTD GXTB W Burring hole Burring hole Hole Hole The inside diameter of the bush z zMODELS UTD GXSC W UTD GXTC W Burring hole Burring hole Hole Hole The inside diameter of the bush Unit mm ...

Страница 1123: ...8 OPTIONAL PARTS OPTIONAL PARTS ACCESSORY PARTS Name and shape Q ty Installation manual 1 Operating manual 1 Grille 1 Bracket frame 1 Name and shape Q ty Screw A 16 Screw B 6 Cable clip 2 Binder 3 Bushing 1 ...

Страница 1124: ...el is a trademark of Intel Corporation or its subsidiaries in the U S and or other countries Echelon LONWORKS and the Echelon logo are trademarks of Echelon Corporation registered in the United states and other countries MODBUS is a registered trademark of Schneider Electric BACnet is a trademark or registered trademark of the American Society of Heating Refrigerating and Air Conditioning Engineer...

Отзывы: